![Fiamm SODIUM SoNick 48TL160H Installation & Operating Instructions Manual Download Page 16](http://html.mh-extra.com/html/fiamm/sodium-sonick-48tl160h/sodium-sonick-48tl160h_installation-and-operating-instructions-manual_2285880016.webp)
FIAMM SoNick I&O - 48TL160H rev.0
– July 2013
pag.16
5.1.2 BMS functions
Main functions of the integrated Battery Management System (BMS) are:
Battery Thermal Management: battery needs to be warm before it starts receive or deliver
energy. The thermal management of the BMS performs the warm-up process automatically
as soon as it is powered.
Battery Charge Process: the BMS is equipped with a charge controller which is able to
regulate the charging parameters (voltage and current) in order to obtain the best charging
performance.
Battery Power/Energy Output Checks: the BMS calculate the battery SOC to provide a
reliable and safe operation and to avoid overcharge or over discharge.
Battery Operating Conditions Checks: the BMS continuously measures all the battery
parameters such as voltages, currents, temperatures, insulation levels providing a
continuous monitoring of the operating conditions.
Redundant Control: the controller is equipped with a safety redundant microprocessor
(Watchdog) for safe operations.
Battery communication: the BMS has various communication capability using different
communication ports: USB, RS485, optional CAN Bus or Ethernet.
5.2 Battery Specification
Characteristics
Values
Nominal Voltage
48 Vdc
Operating Voltage Range
42 to 60 Vdc
Nominal Capacity
160 Ah at C4 to 42V
Nominal Energy
7600 Wh at C4 to 42V
Continuous Discharge Current
65A
DC Bus Voltage Range
53
– 59 Vdc
Internal Low Voltage
Disconnect
40 Vdc
Power Fuse Rating
200A
Communication Port
RS 485 / USB / Ethernet / CAN-bus
Alarm Dry Contact
230Vac 2A
Length
496 mm
Width
578 mm
Height
325 mm
Weight
90 kg
Continuous Operating
Ambient Temperature
-20 to +60°C (-4 to 140°F)
Terminal Bolt Torque
7-8 Nm, 5-6 Ft-Lbs, 60-70 In-Lbs
Terminal Bolt Size
M8
Table I