FHF AVISA AX08 Installation Instructions Manual Download Page 2

2

Housing

Polycarbonate

Colour        

Red, similar to RAL 2002

Insulation class

II

Protection degree 

IP 65 acc. to IEC 60529

Cable gland 

intended for M20 x 1.5 or Self-sealing grommet

Volume  

approx. 116 dB(A) (depending on signal tone)

Signals

32 different signal tones (see diagrams), 2nd stage can be turned on externally

Temperature range 

Operation

-25 °C to +55 °C

Storage

-40 °C to +70 °C

Weight 

AC 3 kg / DC 2.5 kg

Operating voltage

24 VDC, 115 VAC, 230 VAC

Connecting terminals

Clamping capacity 2.5 mm

2

solid conductor / 1.5 mm

2

stranded conductor

Flash power 

5 J

Cap colours

red, yellow, green, blue, clear

Technical Data AXL08

Housing

Polycarbonate

Colour         

Red, similar to RAL 2002

Insulation class

II

Protection degree 

IP 65 acc. to IEC 60529

Cable gland 

intended for M20 x 1.5 or Self-sealing grommet

Volume  

approx. 116 dB(A) (depending on signal tone)

Signals

32 different signal tones (see diagrams), 2nd stage can be turned on externally

Temperature range 

Operation

-25 °C to +55 °C

Storage

-40 °C to +70 °C

Weight  

AC 2.9 kg / DC 2.4 kg

Operating voltage

24 VDC, 115 VAC, 230 VAC

Connecting terminals

Clamping capacity 2.5 mm

2

solid conductor / 1.5 mm

2

stranded conductor

Technical Data AX08

and  TB4,  see  Fig.  2.  For  ac  units  the  second  stage  is
available  upon  the  application  of  a  third  wire  L  to  TB3,
see Fig. 3.

Mounting

The  AX08 / AXL08  series  alarm  units  are  mounted  to  a
wall  or  bulkhead  of  suitable  material  using  the  lugs 
projecting from the side of the case. The lugs are bored 
10 mm  clearance  on  250 mm  centres.  The  recommen-
ded  length  of  fixing  screws  is  30 mm.  To  maintain  the
integrity of the weather seal, the cable entry must be via
a suitable sealed gland.

Recycling

The  device  may  be  completely  recycled  as  electronic
waste.  When  the  device  is  disassembled,  plastics,
metals and electronics are to be disposed of  separately.

Installation

The  sounder  or  combined  sounder  strobe  units  can  be
affixed to most surfaces using screws through the exter-
nal  mounting  lugs.  A  20 mm  gland  entry  is  provided  for
the  supply  cable.  The  cable  and  gland  must  be  fitted  in
accordance  with  the  national  and  local  regulations.  It  is
not  necessary  to  earth  the  sounder  circuitry  but  earth
tags  should  be  used  if  earth  continuity  of  conduit  or
cable sheathing needs to be maintained..

Supply input

Ensure that the supply is correct for the voltage rating of
the sounder or combined sounder strobe being installed.
Ensure  that  the  supply  is  OFF  before  making  any 
connection and wire only in accordance with the terminal
label detail.

Sound selection

Ensure  the  supply  is  OFF  before  proceeding.  All  dc  and
ac  units  have  selectable  alarm  sounds  (see  table  below
for details) and are selectable by means of the 5 way DIL
switches SW1 for the first stage and SW2 for the second
stage.  For  dc  units  the  second  sound  is  made  available
upon the application of a third wire connected to terminal
TB 3 as shown in Fig. 1 while still connected to terminal
TB  2.  Alternatively  first  and  second  stage  sound  signals
can  be  generated  by  supply  reversal  at  terminals  TB3

The  device  complies  with  the  requirements  of  the
new  EMC-directive 2004/108/EC and the low voltage
directive 2006/95/EC. 
The conformity with the above directives is confirmed
by the CE sign.

EMC-Directive