SERIES 2000 COMMUNICATIONS MANUAL
M41 Issue 1.1
3.8
Programmer read/write parameter codes
The table below shows the meaning of all the parameter codes available in the profile
generator.
PARAMETER
CODE
SS
FIELD
MEANING
READ
ONLY
DATA
FIELD
C
N/A
Profile setpoint
YES
TYPE 1
D
N/A
Delay start time in mins
NO
TYPE 1
E
N/A
Segment Elapsed time in mins
YES
TYPE 1
H
N/A
Profile hold band in digits
NO
TYPE 1
I
N/A
Profile hold type
NO
TYPE 1
(coded)
J
N/A
Profile repeats
NO
TYPE 1
K
N/A
Number of repeats remaining
YES
TYPE 1
L
YES
Segment target level in digits
NO
TYPE 1
M
N/A
Current event status
YES
TYPE 4
N
N/A
Ready mode event status
NO
TYPE 4
P
N/A
Profile pointer
NO
TYPE 1
Q
N/A
Profile status
YES
TYPE 5
R
YES
Segment event outputs
NO
TYPE 4
T
YES
Segment time in minutes
NO
TYPE 6
X
N/A
Profile currently running
YES
TYPE 1
3.9
Controller Set status codes.
Writing a set command to the instrument with a parameter as follows will produce the
specified action if the address field matches the address of the instrument. In the examples
given the instrument address is assumed to be 20.
CODE
MESSAGE
REPLY
MEANING
M
S20M<CR>
*20M<CR>
Set controller to Manual mode
A
S20A<CR>
*20A<CR>
Set controller to Auto mode
P
S20P<CR>
*20P<CR>
Turn on the pretuner
T
S20T<CR>
*20T<CR>
Turn on the adaptive tuner
O
S20O<CR>
*20O<CR>
Turn off pretuner and adaptive tuner
U
S20U<CR>
*20U<CR>
Unlatch any latched alarms