FlameSpec Flame Simulator Manual
Doc. No.
F300V0020.01
For more information & technical support: (+1) 714-671-8500 · [email protected]
3
Note: factory default settings for Detectors sensitivity is Medium
Simulator Kit
FLS-FSIM-IR3-KIT
FLS-FSIM-IR3-H2-KIT
FLS-FSIM-UV-IR-KIT
Use with
Detector Model
FLS-IR3-HD
FLS-IR3-H2-HD
FLS-UV-IR-HD
FLS-IR3
FLS-IR3-H2
FLS-UV-IR
ft. (m)
ft. (m)
ft. (m)
Detector
Sensitivity
Setting
Extreme
23.0 (7.0)
23.0 (7.0)
21.3 (6.5)
High
16.0 (5.0)
16.0 (5.0)
16.0 (5.0)
Medium
10.0 (3.0)
10.0 (3.0)
13.0 (4.0)
Low
3.3 (1.0)
3.3 (1.0)
3.3 (1.0)
3
LED Status, Faults & Warnings
The flame simulator has a tri-color LED which indicates the operational status of the simulator as
described in the table below.
LED Status
Indication
Action
Flashing green
Normal operation
Ready for use
Flashing orange
Battery at medium capacity
Charge battery for 3 hours
Solid orange
Unit is in fail mode
Return for repair
Solid red
No power
Recharge/replace the battery
Off
No power
Recharge/replace the battery
Flashing green LED
but simulator fails to
activate detector
alarm
Detector is unable to read the
signal from the Simulator
1.
Check you are within the specified distance
from the detector according to the detector’s
sensitivity setting.
2.
Check detector is powered and operational.
3. Check simulator window is clean.
4. Check detector window is clean, and not in
fault or indicating 2mA output to the panel
indicating a dirty window.
Note: Any alarm delay set in the detector will
require the simulator to be aimed at the detector
for that period plus up to 10 more seconds.