![FGD FlameSpec UV-IR User Manual Download Page 30](http://html1.mh-extra.com/html/fgd/flamespec-uv-ir/flamespec-uv-ir_user-manual_2285568030.webp)
FlameSpec
UV-IR
User Manual
F110V0020.05
Medium Sensitivity
Fuel
Size
Distance Feet
(m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
49 (15)
1.0
Gasoline
1 x 1 ft
49 (15)
1.3
Methane
32-in Plume
30 (9)
0.9
LPG
32-in Plume
33 (10)
1.2
Diesel
1 x 1 ft
36 (11)
1.2
JP5
1 x 1 ft
36 (11)
1.2
Kerosene
1 x 1 ft
36 (11)
0.9
Methanol
1 x 1 ft
30 (9)
1.3
Ethanol
1 x 1 ft
31 (9.5)
2.9
Isopropanol
1 x 1 ft
36 (11)
0.8
Polypropylene
1 x 1 ft
23 (7)
0.9
Paper
1 x 1 ft
23 (7)
1.0
H2
32-in Plume
33 (10)
1.0
Low Sensitivity
Fuel
Size
Distance
Feet (m)
Average Response Time
(Seconds)
N-Heptane
1 x 1 ft
16 (5)
1.0
LPG
32-in Plume
13 (4)
1.2
JP5
1 x 1 ft
16 (5)
1.2
Methanol
1 x 1 ft
10 (3)
2.7