28
Medium Sensitivity
Fuel
Size
Distance ft (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
98 (30)
2.2
Gasoline
1 x 1 ft
98 (30)
1.5
Methane
32
” plume
82 (25)
0.8
LPG
32
” plume
98 (30)
1.4
Diesel
1 x 1 ft
79 (24)
3.9
JP5
1 x 1 ft
79 (24)
1.9
Kerosene
1 x 1 ft
79 (24)
2.5
Methanol
1 x 1 ft
75 (23)
1.2
Ethanol
1 x 1 ft
75 (23)
1.6
Isopropanol
1 x 1 ft
75 (23)
1.0
Polypropylene
1 x 1 ft
66 (20)
2.6
Paper
1 x 1 ft
39 (12)
0.8
Low Sensitivity
Fuel
Size
Distance ft (m)
Average Response
Time (Seconds)
N-Heptane
1 x 1 ft
49 (15)
1.2
LPG
32
” plume
49 (15)
1.4
JP5
1 x 1 ft
39 (12)
8.8
Methanol
1 x 1 ft
39 (12)
1.2