Flow over valve seat

The valve is closed by spring force with the medium flow.
– Medium pressure supports valve closing.
– The valve is opened with operating pressure.
– Only suitable for gaseous media, because use of incompressible media causes

pressure surges in the piping.

Flow under valve seat

The valve is closed by spring force or with operating pressure against the medium
flow.
– Medium pressure supports the valve opening.
– In certain constructions, medium pressure that is too high or operating pressure

that is too low can lead to the valve not completely closing.

Control function

Single-acting

Closed via spring force or through reduced
spring force (normally closed - NC)

Opened via spring force (normally open - NO)

Fig. 3

Position indicator

The pneumatic position indication shows the position of the actuator rod.

Indicator cylinder above

Indicator cylinder below

Actuator rod retracted, valve opened

Actuator rod extended, valve closed

Fig. 4

6

Transport and storage

 When shipping used products: comply with all legal requirements for handling

hazardous substances and transporting dangerous goods.
For return to Festo 

è

 Chap. 2.

 Store the product in a cool, dry, UV- and corrosion-protected environment. 

Ensure that storage times are kept to a minimum.

7

Mounting and installation

Note

Mounting and installation should only be carried out by qualified personnel.

7.1 Installing the angle seat valve

Prerequisites

– The piping system is unpressurised and no medium flows in it
– Lines are clean
– The line ends are mounted

Clean valve

 Remove all transport packaging. The material used in the packaging has been

specifically chosen for its recyclability (exception: oil-impregnated paper = 
residual waste).

Traces of residual grease may be evident on the product due to the production
process used.
 Clean the valve immediately before installation.

Warning

Risk of injury due to slipping or falling objects!
The angle seat valve can weigh up to 11.5 kg, depending on the product version.
Body parts can be crushed. In overhead installations, the result can be serious
head injuries.
 Angle seat valve with appropriate means of securing against falling or

slipping.

1. Bring the angle seat valve into the mounting position.

– Observe the flow direction. The permitted direction of flow is marked by an

arrow on the valve housing.

2. Connect the piping on the valve housing.

– Max. tightening torque 

è

 Fig. 5.

3. Connect the line of the operating medium.

– Pneumatic connection (2): operating medium
– Pneumatic connection (4): exhaust port

4. For single-acting actuators: mount the silencer in the exhaust port or use

a tubing connection for guided exhaust air.

Connection size

[”]

1

2

Max. tightening torque 
pipe connection

[Nm]

350

450

540

620

750

Fig. 5

8

Commissioning

Warning

Risk of injury from manipulation in the area of the angle seat valve!
Limbs can be cut or severed.
 Place only the fully mounted angle seat valve in operation.

Note

Commissioning should only be carried out by qualified personnel.

Prerequisites

– The valve is fully mounted and connected

Checking operating conditions

 Observe operating conditions and limits 

è

 Technical data and product labelling.

 Check connection points for tightness.
 Check compatibility of the devices in the system for maximum pressure 

(consider pressure peaks). If necessary, adjust the application parameters.

Placing valve in operation

1. Supply medium.
2. Slowly apply operating pressure to the valve. The operating pressure required

for reliable switching of the valve depends on the medium pressure

è

 Fig. 10 to Fig. 15.

3. Function and direction control of the individual pneumatic actuators.

9

Operation

Danger

Risk of injury from touching hot surfaces!
Valve and actuator can become hot at high temperature of medium. Severe
burns are possible.
 Do not touch the angle seat valve during operation or immediately afterward.

 Comply with operating conditions.
 Comply with maintenance conditions 

è

 Chap. 11.

After longer idle times:
 Actuate the valve several times and check for correct function.

10

Malfunctions

Malfunction

Possible cause

Remedy

Valve does not
close or closes
too slowly

VZXA-B: medium pressure is too high
or operating pressure too low

 Creating necessary differential

pressure 

è

 Technical  data.

 Adjust operating pressure.

Too many contaminants, or contamin­
ants that are too large, in the medium

 Comply with operating condi­

tions.

Valve does not
open or opens
too slowly

VZXA-A: operating pressure is too low
or medium pressure too high

 Adjust operating pressure or 

medium pressure.

VZXA-B: operating pressure too low

 Adjust operating pressure.

Medium leaking
from a leakage
hole

Seal cartridge  defective

 Replace seal cartridge

è

 Spare parts  documentation.

Medium will not
let itself be
shut off

Seat seal defective

 Replace seat seal

è

 Spare parts  documentation.

Fig. 6