7

Commissioning

Note

• Commissioning only by qualified personnel.
• When incompressible media (e.g. neutral water) are used, switching the valve

causes pressure surges in the tubing system. Prior to commissioning, check
the compatibility of the devices in the system to avoid damaging them. If
necessary, adjust your application parameters.

• Observe the information on the rating plate.
• Start up the solenoid valve only when it is completely assembled and installed.
• Check the connection points for leaks.
• Prior to commissioning, check for compliance with the operating conditions and

the permissible limit values (e.g. operating medium, operating pressure, differ-
ential pressure, voltage and frequency, ambient temperature and media temper-
ature

Î

Technical data).

8

Operation

• Observe the operating conditions.
• Always observe the permissible limit values.

Warning

Danger of burning on hot surfaces.
The surface temperature of the solenoid valve can exceed 75 °C.
• Do not touch the solenoid valve.

9

Dismantling

Warning

Danger of injury due to hot media under pressure.
The media in the piping system and the solenoid valve can be hot and can be
under pressure.
• Allow the solenoid valve and pipelines to cool and depressurise them.

Note

The solenoid valve may be dismantled only by qualified personnel.

1. Depressurise the pipeline.
2. Switch off the voltage.
3. Completely drain the pipeline and valve.

– Allow the solenoid valve and pipeline to cool off.
– Make sure that no one is in front of the outlet opening.
– Catch escaping media in a suitable container.

4. Remove the solenoid valve from the pipeline (unplug the electrical plug con-

nector, detach the mounting bracket and unscrew the fittings).

10

Changing the solenoid coil

The solenoid coil can be changed for repairs.

Warning

Danger of injury from hot surfaces.
The surface temperature of the solenoid valve can exceed 75 °C.
• Let the solenoid valve cool off.

Dismantling:

1. Switch off the voltage.
2. Disconnect the electrical plug connector.
3. Undo the knurled nut and remove the solenoid coil from the armature guiding

tube.

Mounting:

1. Push the O-ring and solenoid coil over the armature guiding tube.
2. Secure the solenoid coil with the O-ring and knurled nut.

– Torque for tightening the knurled nut: finger-tight (about 1...1.5 Nm).

11

Service and maintenance

• Check the solenoid valve for leakage at least every 6 months.
• Check the functioning of the solenoid valve at least every 6 months.
• Regularly clean the outside of the valve with a soft cloth. The permissible

cleaning agent is soap suds.

12

Eliminating malfunctions

Malfunction

Possible cause

Remedy

Solenoid valve
not closing

Solenoid valve is defective.

• Replace the solenoid valve.

Flow direction is incorrect

• Install the solenoid valve in accord-

ance with the flow arrow

Nominal voltage is still applied

• Check electrical connection.

Differential pressure too low

• Make sure the specified minimum

differential pressure is supplied.

Solenoid valve
does not open

Solenoid coil or solenoid valve is
defective.

• Replace the solenoid coil.
• Replace the solenoid valve.

Nominal voltage interrupted or
not sufficient

• Check voltage.

Fig. 3

• Send defective solenoid coils to Festo's repair service. For information about

spare parts and auxiliary equipment see www.festo.com/spareparts.

13

Technical data

General

VZWP-L-M22C-...-P4-...

Valve function

2/2-way, closed, monostable

Design

Solenoid valve, servo controlled

Actuation type

Electrical

Mounting position

Solenoid preferably vertical

Sealing principle

Soft

Operating medium

– Neutral, gaseous and fluid media
– No chemically unstable gases

Direction of flow

Non-reversible

Viscosity

[mm

2

/s]

š

22

Grade of filtration

[

μ

m]

40

Temperature of medium

[°C]

–10...+80

Ambient temperature

[°C]

–10...+35

Protection class

IP65 as per DIN EN 60529

Degree of contamination

3 as per IEC 60664-1

Attachment type

In-line installation

Valve housing material

Brass

Seal

NBR, FKM

Fig. 4

Electrical data

VZWP-...1-...

VZWP-...2A-...

VZWP-...3A-...

Nominal voltage

– DC voltage
– AC voltage (50...60 Hz)

[V DC]
[V AC]

24 (±10%)


110 (±10%)


230 (±10%)

Rated output

[W]
[VA]

6.8


7.5


10.5

Surge resistance

[kV]

2.5

4.0

Duty cycle

100% (continuous duty)

Electrical connection

Device plug per DIN EN 175301-803, format A

Connecting cable

– Cable cross-section

[mm

2

]

0.75...1.5

– Cable diameter

[mm]

5...9

– Cable entry thread

M20x1.5

Fig. 5

Port size

[

˝

]

¼

y

½

¾

1

Pipe thread per DIN ISO 228
Pipe thread per ANSI B 1.20.1

G

¼

N

¼

G

Å

N

Å

G

½

N

½

G

¾

N

¾

G1
N1

Max. operating pressure

[bar]

40

Overload pressure

[bar]

45

Min. differential pressure

[bar]

0.5

Nominal size (DN)

[mm]

13

25

Standard nominal flow rate

[l/min]

1600

2100

2650

8750

12250

Flow factor K

v

[m

3

/h]

1.5

2.0

2.5

8.2

11.5

Switching times for gaseous media

1)

– On

[ms]

100

130

– Off

[ms]

250

300

Tightening torques

– Pipe connection

[Nm]

35

60

105

200

350

– Mounting of solenoid coil

[Nm]

2

Weight

[g]

600

575

550

1500

1400

1)

Depending on the viscosity, longer switching times with fluid media

Fig. 6

Summary of Contents for VZWP-L-M22C-P4 Series

Page 1: ... und mit festen Stoffen ist unzulässig Verwenden Sie das Magnetventil nur in der gekennzeichneten Durchflussrich tung Halten Sie alle geltenden nationalen und internationalen Vorschriften ein 4 Produktvarianten Merkmale Typen schlüssel Beschreibung Typ VZWP Elektrisch betätigtes Prozessventil servogesteuert Ventilart L Muffenventil Ventilfunktion M22C 2 2 Wegeventil in Ruhestellung geschlossen NC ...

Page 2: ...ca 1 1 5 Nm 11 Wartung und Pflege Prüfen Sie das Magnetventil mindestens alle 6 Monate auf Leckage Prüfen Sie das Magnetventil mindestens alle 6 Monate auf Funktion Reinigen Sie das Ventil regelmäßig außen mit einem weichen Lappen Zulässiges Reinigungsmittel ist Seifenlauge 12 Störungsbeseitigung Störung Mögliche Ursache Abhilfe Magnetventil schließt nicht Magnetventil defekt Magnetventil austausc...

Page 3: ...ally unstable gases abrasive media and solids is imper missible Use the solenoid valve only in the marked flow direction Comply with all applicable national and international regulations 4 Product variants Features Type code Description Type VZWP Servo controlled solenoid actuated process valve Valve type L In line valve Valve function M22C 2 2 way valve normally closed NC mechanical reset Connect...

Page 4: ...or leakage at least every 6 months Check the functioning of the solenoid valve at least every 6 months Regularly clean the outside of the valve with a soft cloth The permissible cleaning agent is soap suds 12 Eliminating malfunctions Malfunction Possible cause Remedy Solenoid valve not closing Solenoid valve is defective Replace the solenoid valve Flow direction is incorrect Install the solenoid v...

Reviews: