22
Festo — SFAB-...-PNLK — 2022-08
Commissioning
2. Press the [Edit] key.
Ä
‘Out’ / ‘V’ or ‘Out’ / ‘MA’ flashes.
3. Set the parameter with the [A] or [B] key.
4. Press the [Edit] key.
Ä
The set value is saved. The next adjustable parameter is shown.
5. Repeat steps 3 and 4 until all parameters are set.
6. Press the [Edit] key.
Ä
RUN mode is active.
7.3.6
Replicating parameters
Requirements:
–
The configured sensor (master sensor) is operational and in RUN mode.
–
The master sensor and device sensor have the same design with reference to the parameters, i.e.
they have the same device ID.
–
The master sensor is connected with the device sensor
–
Parameterisation of the device sensor must not be blocked via IO-Link®.
Master
Sensor
Power Suppply
Device
Sensor
Fig. 13: Replicate pin allocation parameters
1. Select the ‘SPEC’ special menu from the device settings on the master sensor.
2. Press the [Edit] key repeatedly until ‘MASt’ appears.
3. Select ‘ON’ with the [A] or [B] key.
4. Press the [Edit] key.
Ä
‘REPL’ and ‘REdY’ appear.
5. Press the [A] or [B] key.
Ä
‘REPL’ and ‘RUN’ appear briefly. The parameters are transmitted to the device sensor. ‘REPL’
and ‘REdY’ appear. If an error occurs, an error message appears
6. Repeat point 5 if an additional sensor should be parameterised.
7. Press the [Edit] key.
Ä
RUN mode is active.
7.3.7
Zero point synchronisation
Requirements:
–
‘Z.AdJ’ ‘ON’ is set.
–
The operating pressure is present, but no flow rate exists.
–
RUN mode is active.
–
The measured value lies in the range 0 l/min ± 3 %FS.
1. Press the [A] key and the [B] key.