7
Malfunctions
7.1
Diagnostics via LEDs
Display
Meaning
Measure
Status indication:
–
Piston outside the sensing range
–
Piston not at switching point
Normal operating case
Both LEDs
off
Error:
–
Power supply fault
–
Connecting cable or sensor defective
–
Check power supply
–
Check connecting cable
–
Replace device
Green LED
flashes at
6 Hz
Hardware error
–
Disconnect and connect proximity
sensor
–
Replace device
Tab. 5
7.2
General malfunctions
Error description
Possible cause
Measures/remedy
Proximity sensor defective
–
Replace proximity sensor
Operating voltage not connected
or outside the operating voltage
range
–
Comply with operating
voltage range
Short circuit or overload at the
output
–
Rectify short circuit/over
load
Magnetic or ferromagnetic objects
close to the proximity sensor
–
Keep magnetic or ferromag
netic objects clear of the
proximity sensor
–
Conditions during teachin of
the switching point must cor
respond to operating condi
tions (e.g. no screwdriver in
the locking screw)
Incorrect or unexpected
signals at the output
Orientation of the proximity
sensor rotated 180° in the slot
after adjustment of the switching
point
–
Reset switching point (with
auto teachin or operating
key)
Proximity sensor defective
–
Replace proximity sensor
Switching output does not
react in accordance with
the settings
Short circuit or overload at the
output
–
Rectify short circuit/over
load
Capacitive operating key
does not react to input
Dirt or moisture on the proximity
sensor
–
Wipe proximity sensor with a
dry cloth
Tab. 6
8
Technical data
SDBT-MSX
Operating voltage range
[V DC]
10 … 30
Max. output current
[mA]
100
Operating temperature range
[°C]
–40 … +85 (UL: +80)
Ambient temperature with
flexible cable installation
[°C]
–20 … +85 (UL: +80)
Degree of protection
(EN 60529)
IP 65 / IP 68
Tab. 7