Bus node
CPX-FB40
Festo
SE
& Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0
www.festo.com
Brief description
Translation of the original instructions
8101660
2018-11a
[8101662]
Bus node CPX-FB40
English
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
For all available product documentation
è
www.festo.com/pk
1
Intended use
The module described in this document is intended for use as a participant in an
Ethernet POWERLINK network in an industrial environment. Outside of industrial
environments, e.g. in commercial and mixed-residential areas, actions to suppress
interference may have to be taken.
The module is intended exclusively for use in CPX terminals from Festo for installation
in machines or automated systems and may be used only in the following ways:
– in an excellent technical status
– in original status without unauthorised modifications, except for the adapta
tions described in this documentation
– within the limits of the product defined through the technical data.
2
Safety
This documentation is directed exclusively at technicians trained in control and
automation technology.
You can find detailed information in the description for the module
(
è
P.BE-CPX-FB40-…) as well as in the CPX system description
(
è
P.BE-CPX-SYS-…).
Warning
Electric shock
Injury to people, damage to the machine and system
For the electrical power supply, use only PELV circuits in accordance with
IEC 60204-1 (Protective Extra-Low Voltage, PELV).
Observe the general requirements of IEC 60204-1 for PELV circuits.
Use only voltage sources which guarantee reliable electrical isolation of the
operating and load voltage in accordance with IEC 60204-1.
Always connect all circuits for operating and load voltage supplies U
EL/SEN
,
U
VAL
and U
OUT
.
Note
Electrostatically sensitive devices
Do not touch any components.
Observe the handling specifications for electrostatically sensitive
devices.
Note
Take into consideration the specifications and notes in the module description
and the assembly instructions for the components.
Commission the module only if fully mounted and wired.
Ethernet POWERLINK
®
, SPEEDCON
®
are registered trademarks of the
respective trademark owners in certain countries.
3
Electrical connections and indicators
1
2
3
4
5
1
Rating plate
2
Network- and CPX-specific LEDs
3
4
DIL switch cover
5
for CPX-MMI or
the adapter
for the CPX-FMT
1)
M12 socket, D-coded, 4-pin
2)
M12 socket, A-coded, 5-pin
3)
Adapter NEFC-M12G5-0.3-U1G5 for paramet
erisation via a USB connection
Fig. 1
3.1 Network connections
Socket
Connection [X1]/[X2]
Pin
Signal
Explanation
M12, 4-pin
1
2
3
4
Housing
TD+
RD+
TD–
RD–
FE
Transmitted data +
Received data +
Transmitted data –
Received data –
Screening/F E
1)
The screened connection is connected to the earth potential of the CPX terminal through an RC element.
Fig. 2
3.2 LED indicators - normal operating status
Behaviour of the LED indicators in normal operating status:
– the green LEDs BS, PS and PL are illuminated
– the green LEDs L/A1 and L/A2 are illuminated or flash if a network cable is con
nected
– the yellow LED (M) is illuminated, flashes or is dark
– the red LEDs (BE, SF) are not illuminated.
A network cable does not need to be connected at both network connec
tions.
Network-specific LED indicators
CPX-specific LED indicators
BS (green)
PS (green)
Power system
BE (red)
PL (green)
Power load
L/A1 (green)
Link/activity port 1
SF (red)
L/A2 (green)
Link/activity port 2
M (yellow)
Modify
1)
Detailed information (
è
description for the module P.BE-CPX-FB40-…)
2)
Detailed information (
è
CPX system description P.BE-CPX-SYS-…)
3)
Flashes in case of error, error diagnostics (
è
CPX system description P.BE-CPX-SYS-…)
4)
Parameterisation revised or “Force” active.
Fig. 3
4
Mounting and dismantling
Warning
Electric shock
Injury to people, damage to the machine and system
Switch supply power off before assembly work.
2
3
1
1
Screws
2
Module
3
Interlinking block
Fig. 4