System overview, CTEL system
Festo – P.BE-CPX-CTEL-EN – 1601b – English
17
Setting the I/O mode
DIL switch group 1
S1.1
S1.2
Function
OFF
OFF
Module unused
OFF
ON
Operation as pure output module
ON
OFF
Operation as pure input module
ON
ON
Mixed operation (inputs and outputs)
1)
Factory setting
2)
No devices connected; DIL switch group 2 without function
Tab. 2.5
If the CTEL master module is not used, i.e. there are no devices connected, DIL switch
group 2 has no function and the I/O length is automatically set to 0 bytes in each case.
Setting the I/O length
DIL switch group 2
S2.1
S2.2
Function
OFF
OFF
8 bytes I/Os (2 bytes per I-Port)
OFF
ON
16 bytes I/Os (4 bytes per I-Port)
ON
OFF
24 bytes I/Os (6 bytes per I-Port)
ON
ON
32 bytes I/Os (8 bytes per I-Port)
1)
Factory setting
Tab. 2.6
The I/O length specified always applies for all 4 I-Ports (max. 8 bytes per I-Port).