3. Electrical installation
3−7
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
3.2.1
VPWP proportional directional control valve
The VPWP has one incoming (In) and one outgoing (Out) axis
interface. See Tab.3/2.
Digital output DO (brake)
A digital output (DO) at pin 2 is also available for controlling
a valve for a brake or clamping unit. This is controlled via the
CMAX I/O data (see section 4.5).
Note
For the control via CMAX to function correctly, it is compul
sory that the clamping unit or brake be connected with the
following logic (see also section 3.4.3, Fig.3/4):
Pin 2: 0 V = clamping unit/brake closed
Pin 2: 24 V = clamping unit/brake open
Voltage output
(load voltage)
The load supply voltage provided at pin 4 can also be used
for switching a valve when the load supply voltage V
VAL
fails,
for example. See section 3.4.3.
Pin
Allocation
DO
1
n.c. = (not connected)
4
3
2
Digital output (brake)
2
1
3
0 V
2
1
4
+ 24 V voltage output
(load voltage)
Tab.3/4: Pin allocation DO connection of the VPWP,
M8 4−pin, socket
Summary of Contents for CPX-CMAX-C1-1
Page 2: ......
Page 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Page 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Page 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Page 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Page 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Page 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Page 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Page 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...