4. Commissioning
4−22
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
4.5.4
Execute record (record select mode)
I/O diagram
Requested record no
Output data
Acknowledge start
SPOS.ACK
Motion complete
SPOS.MC
Actual record no
Input data
N − 1
N
N + 1
1
0
1
0
1
0
1
0
Start
CPOS.START
N − 1
N
1
0
1
2
3
4
5
6
7
t
min
t
min:
At least 1 bus cycle waiting time Recommendation: 1 PLC cycle
Not required if consistent data transmission is used
Fig.4/3:
Record start sequence
1
Set the desired record number in the PLC’s output data. Until
the start, the CMAX responds with the number of the record
last executed.
2
If SPOS.ACK (Acknowledge start) = 0, the PLC can intitiate
execution of the record with a rising edge at CPOS.START.
3
The CMAX accepts the record number and starts positioning.
The actual record number is set to the new record in the PLC
input data and SPOS.MC is reset.
Summary of Contents for CPX-CMAX-C1-1
Page 2: ......
Page 22: ...Contents and general safety instructions XX Festo P BE CPX CMAX SYS EN en 0908NH...
Page 23: ...CMAX system overview 1 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 1...
Page 31: ...Fitting and pneumatic installation 2 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 2...
Page 60: ...2 Fitting and pneumatic installation 2 30 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 61: ...Electrical installation 3 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 3...
Page 79: ...Commissioning 4 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 4...
Page 122: ...4 Commissioning 4 44 Festo P BE CPX CMAX SYS EN en 0908NH...
Page 123: ...Diagnostics and error handling 5 1 Festo P BE CPX CMAX SYS EN en 0908NH Chapter 5...
Page 163: ...Technical appendix A 1 Festo P BE CPX CMAX SYS EN en 0908NH Appendix A...
Page 176: ...A Technical appendix A 14 Festo P BE CPX CMAX SYS EN en 0908NH...