ID
Parameter
Instances Data type
Access
1
)
Array
size
20092
Operating time
1
UINT32
ro
–
20093
Hardware version
1
UINT8
ro
–
20099
Unlock test commands
1
UINT16
rw
–
1) ro = read only; rw = read write
Tab. 6: Parameter
9
Diagnostics and fault clearance
9.1
Diagnostics messages
ID hex (dec)
Message
Description
01 | 01 | 010C
(16843020)
Output signal short-
circuit/overload
Short circuit/overload in output signal.
Remedy
–
Check connected load for correct function,
in particular for current consumption.
–
Check wiring.
Diagnos-
tics
status
Error
02 | 01 | 0016
(33619990)
Undervoltage in logic
supply PS 24 V DC
Undervoltage of the logic supply PS 24 V DC was
detected.
Remedy
–
Check logic supply PS.
Diagnos-
tics
status
Warning
Error
02 | 01 | 0017
(33619991)
Overvoltage in logic
supply PS 24 V DC
Overvoltage in the logic supply PS 24 V DC has been
detected.
Remedy
–
Check logic supply PS.
Diagnos-
tics
status
Warning
02 | 01 | 0105
(33620229)
Undervoltage in load
supply PL 24 V DC
Undervoltage in the load supply PL 24 V DC has been
detected.
Remedy
–
Check load supply PL.
Diagnos-
tics
status
Error