Diagnostics and fault clearance
9
8
Parameterisation
Various parameters are available for reading out information about the modules in an automation
system CPX-AP-A and for adapting the modules to the application situation.
Write access to the parameters is typically performed by the higher-level controller using the device
descriptions specific to the host system.
ID
Parameter
Instances Data type
Access
1
)
Array
size
246
Fieldbus serial number
1
UINT32
ro
–
791
Product key
1
CHAR
ro
12
960
Firmware version
1
CHAR
ro
30
20000
Module code
1
UINT32
ro
–
20014
Input debounce time
–
0: 0.1 ms
–
1: 3.0 ms (factory setting)
–
2: 10 ms
–
3: 20 ms
1
ENUM_ID
rw
–
20085
Measured value of temperature AP-ASIC [°C] 1
INT16
ro
–
20087
Current measured value of logic supply (PS) 1
UINT16
ro
–
20088
Current measured value of load supply (PL)
1
UINT16
ro
–
20093
Hardware version
1
UINT8
ro
–
1) ro = read only; rw = read write
Tab. 7: Parameter
9
Diagnostics and fault clearance
9.1
Diagnostics messages
The following table contains the diagnostic messages of the module.
ID hex (dec)
Message
Description
01 | 01 | 010B
(16843019)
Short circuit / Over-
load sensor supply
A short circuit/overload of the sensor supply was detected
Remedy
–
Check the connected sensors for proper
function, especially current consumption.
–
Check sensor cable.
Diag-
nostic
status
Error
02 | 01 | 0016
(33619990)
Undervoltage in logic
supply (PS) 24 V DC
Undervoltage in logic supply (PS) 24 V DC
Remedy
–
Check power supply.