2. Analogue input module CPX−2AE−U−I
2−21
Festo P.BE−CPX−AX−EN en 0503b
C
h
anne
l p
a
r
amete
r
s
:
M
o
nit
or
in
g
c
h
anne
l x
Function no.
4828 + m * 64 +
6
(channel 0)
m = module number (0 ... 47)
4828 + m * 64 +
7
(channel 1)
Description
For the individual channels of the analogue input modules, monitoring of indi
vidual faults can be activated or deactivated (suppressed) independently of each
other. Active monitoring causes the following: The fault is:
sent to the CPX field bus node
displayed by the module common error LED.
Further infomation on these monitorings can be found under the description of
the relevant fault in section 2.5.1.
Bit
Bit 0:
monitoring lower limit (or less than rated range)
Bit 1:
monitoring upper limit (or rated range exceeded)
Bit 2:
monitoring wire fracture
Bit 3...6:
reserved
Bit 7:
monitoring parametrizing faults
Values
1 = active; 0 = inactive
Presetting bit 0...2:
0 (inactive)
Presetting bit 7:
1 (active)
Remark
Monitoring the upper/lower limit:
Monitoring the input signals for less than or exceeding the rated range or
monitoring the range limits defined with the parameters Lower limit ..." as
well as Upper limit ..." (depending on the data format used, see sections
2.4.4 and 2.4.5).
Monitoring wire fracture:
Only effective for the signal range 4...20 mA. A drop below the minimum input
current (I
IN
<
2.0mA) counts as a wire fracture.
Monitoring parametrizing faults:
Some channel−specific parameters are checked for non−permitted values
during parametrizing:
Filter measured value
Lower limit
Upper limit
The setting of the channel parameter Monitoring parametrizing faults" is only
effective if the module parameter Monitoring parametrizing faults" is set to
active".
Tab.2/13:
Monitoring channel x
Summary of Contents for CPX-2AA-U-I
Page 2: ......
Page 19: ...Overview and connection technology I O modules 1 1 Festo P BE CPX AX EN en 0503b Chapter 1...
Page 44: ...1 Overview and connection technology I O modules 1 26 Festo P BE CPX AX EN en 0503b...
Page 45: ...Analogue input module CPX 2AE U I 2 1 Festo P BE CPX AX EN en 0503b Chapter 2...
Page 83: ...Analogue input module CPX 4AE I 3 1 Festo P BE CPX AX EN en 0503b Chapter 3...
Page 122: ...3 Analogue input module CPX 4AE I 3 40 Festo P BE CPX AX EN en 0503b...
Page 123: ...Analogue input module CPX 4AE T 4 1 Festo P BE CPX AX EN en 0503b Chapter 4...
Page 157: ...Analogue output module CPX 2AA U I 5 1 Festo P BE CPX AX EN en 0503b Chapter 5...
Page 198: ...5 Analogue output module CPX 2AA U I 5 42 Festo P BE CPX AX EN en 0503b...
Page 199: ...Technical appendix A 1 Festo P BE CPX AX EN en 0503b Appendix A...
Page 221: ...Index B 1 Festo P BE CPX AX EN en 0503b Appendix B...
Page 222: ...B Index B 2 Festo P BE CPX AX EN en 0503b Contents B Index B 1...