4. Analogue input module CPX−4AE−T
4−22
Festo P.BE−CPX−AX−EN en 0503b
C
h
anne
l p
a
r
amete
r
s
:
Measu
r
e
d v
a
l
ue
sm
oo
t
h
in
g
c
h
anne
l x
Function no.
4828 + m * 64 +
9
(channel 0 ... 3)
m = module number (0 ... 47)
Description
Sets whether or not the measured values of the individual channels are to be
smoothed. The parameter can be set for the individual channels independently of
each other.
Bit
Bit 0/1:
channel 0
Bit 2/3:
channel 1
Bit 4/5:
channel 2
Bit 6/7:
channel 3
Values
Channel 3
Channel 2
Channel 1
Channel 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
0
0
0
0
0
0
No measured value
smoothing (presetting)
0
1
0
1
0
1
0
1
Smoothing 2 values
1
0
1
0
1
0
1
0
Smoothing 4 values
1
1
1
1
1
1
1
1
Smoothing 8 values
Remark
Interference can be suppressed with the measured value smoothing.
Tab.4/12:
Measured value smoothing channel x
C
h
anne
l p
a
r
amete
r
s
: S
ens
or
c
o
nnecti
o
n
d
esi
g
ns
c
h
anne
l x
Function no.
4828 + m * 64 +
10
m = module number (0 ... 47)
Description
Set the connection design of the temperature sensor for the channels. The para
meter can be set for the individual channels independently of each other.
Bit
Bit 0/1:
sensor connection design channel 0
Bit 2/3:
sensor connection design channel 1
Bit 4/5:
sensor connection design channel 2
Bit 6/7:
sensor connection design channel 3
Values
Channel 3
Channel 2
Channel 1
Channel 0
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
0
0
0
0
0
0
2−cable (presetting)
0
1
0
1
0
1
0
1
3−cable
1
0
1
0
1
0
1
0
4−cable
Remark
For sensor connection designs see section 4.3.3
Tab.4/13:
Sensor connection designs channel x
Summary of Contents for CPX-2AA-U-I
Page 2: ......
Page 19: ...Overview and connection technology I O modules 1 1 Festo P BE CPX AX EN en 0503b Chapter 1...
Page 44: ...1 Overview and connection technology I O modules 1 26 Festo P BE CPX AX EN en 0503b...
Page 45: ...Analogue input module CPX 2AE U I 2 1 Festo P BE CPX AX EN en 0503b Chapter 2...
Page 83: ...Analogue input module CPX 4AE I 3 1 Festo P BE CPX AX EN en 0503b Chapter 3...
Page 122: ...3 Analogue input module CPX 4AE I 3 40 Festo P BE CPX AX EN en 0503b...
Page 123: ...Analogue input module CPX 4AE T 4 1 Festo P BE CPX AX EN en 0503b Chapter 4...
Page 157: ...Analogue output module CPX 2AA U I 5 1 Festo P BE CPX AX EN en 0503b Chapter 5...
Page 198: ...5 Analogue output module CPX 2AA U I 5 42 Festo P BE CPX AX EN en 0503b...
Page 199: ...Technical appendix A 1 Festo P BE CPX AX EN en 0503b Appendix A...
Page 221: ...Index B 1 Festo P BE CPX AX EN en 0503b Appendix B...
Page 222: ...B Index B 2 Festo P BE CPX AX EN en 0503b Contents B Index B 1...