7. Electrical installation
66
Festo P.BE-CMMP-AS-3A-HW-EN 0708NH
The motor is connected to terminals U, V, W. The motor temperature switch (PTC or NC
contact) is connected to the +Mtdig and –Mtdig terminals, if this uses the same cable as
the motor phases. If an analogue temperature sensor (e.g. KTY81) is used in the motor,
then this is connected to [X2A] or [X2B] via the encoder cable.
The connection of the shaft encoder via the D-SUB plug to [X2A] / [X2B] is diagrammatically
shown in Fig. 7.1.
The PE connection of the CMMP-AS servo positioning controller must be connected to the
operational earth.
The CMMP-AS servo positioning controller must first be fully wired. Only then can the
operating voltages be activated for the intermediate circuit and the power supply. If the
polarity of the operating voltage connections is reversed, or if the operating voltage is
too high or the operating voltage and motor connections are incorrectly connected, the
CMMP-AS servo positioning controller will be damaged.
7.2
Entire CMMP-AS system
An entire CMMP-AS servo positioning controller system is shown in fig. 7.2. The following
components are required to operate the servo positioning controller:
Components
-
Main power switch
-
Circuit breaker
-
Fault-current circuit breaker (RCD), all-current sensitive 300 mA
-
24 VDC power supply
-
CMMP-AS servo positioning controller
-
Motor with motor and encoder cables
A PC with a serial connection cable is required for parameterising.