Festo CPA…-ASI-8E8A-Z 1108a English
30
Type CPA...-ASI-8E8A-Z
Additional supply (load voltage)
– Rated value (protected against
incorrect polarity)
– Residual ripple
– Current consumption
21.6 ... 26.4 V DC
(24 V DC ± 10 %)
≤ 4 Vpp
See valves
Valves
(see Pneumatics manual P.BE-CPA-…)
– Current consumption for 8 valve
solenoid coils (at 24 V)
– Switching on
– after current reduction (stationary)
Watchdog function active
after approx. 40 ... 100 ms
≤ 280 mA (for appr. 25 ms)
≤ 130 mA
Digital inputs
3)
– Design
– Logic level
– Sensor supply (US+/Us−)
– Response delay
8 digital inputs each as per
IEC 1131-2 type 2
24 V DC, PNP,
status display (LED)
ON:
11 ... 30 V
OFF: -30 ... 5 V
≥ AS-interface bus
voltage − 2.5 V
Typ. 3 ms (at 24 V)
Diagnosis (see section 2).
– AS-Interface voltage and address,
watchdog, I/O status
– Additional power supply not applied
or undervoltage
LED display
LED display, peripheral fault
1)
The device is intended for use in industrial environments. Measures
may need to be implemented in residential areas for interference
suppression.
2)
Factory setting, set to 0
H
by some programming devices ≤ Spec. 2.1
when addressing the slave!
3)
The inputs are resistant to short circuits. If a short circuit occurs,
the slave will be switched off. The AS-Interface master regards this
slave as missing. When the short circuit is eliminated, the slave
indicates immediately that it is capable of functioning.