2.04 Location of boiler
the introduction of the Ferroli boilers in the boiler house is very simple given their small size in relation to
capacity. The boiler must be well ventilated and room temperature during operation should not exceed 35
°
C.
Air should be allowed into the room through an opening, which is not sealed when shut, the size of 1/30th
of the room floor area or more, but not smaller than 0.5 m
2
. Location, should be arranged so as to avoid the
transmission of noise outside. The room should be built in accordance with current safety rules. Before
operating the boiler, you should make sure that the front door carrying the mounted burner can rotate 90
°
in the chosen direction of opening, to accommodate a full inspection and cleaning of the tube nest. For this
purpose it is also recommended to leave an open space in front of the boiler, not less than the length of the
flue. Under normal conditions, the boiler, not less than the length of the flue. Under normal conditions, the
boiler may be placed directly on the floor, as it is equipped with its own base made of metal beams. However,
when the room is very humid, we suggest adding a cement block 8-10 cm thick.
Fig. 11
O SPAZIO ESTRAZIONE TUBI
MIN. 600
MIN. 600
MIN. 1700
E
MIN. 1000
Clearence to remove turbulators