PEGASUS D

28

EN

cod. 3540U171  -  06/2012  (Rev. 00)

EN

1. GENERAL WARNINGS

Carefully read and follow the instructions contained in this instruction booklet.

After boiler installation, inform the user regarding its operation and give him this
manual, which is an integral and essential part of the product and must be kept with
care for future reference.

Installation and maintenance must be carried out by professionally qualified person-
nel, in compliance with the current regulations and according to the manufacturer's
instructions. Do not carry out any operation on the sealed control parts.

Incorrect installation or inadequate maintenance can result in damage or injury. The
Manufacturer declines any liability for damage due to errors in installation and use,
or failure to follow the instructions.

Before carrying out any cleaning or maintenance operation, disconnect the unit from
the electrical power supply using the switch and/or the special cut-off devices.

In case of a fault and/or poor operation, deactivate the unit and do not try to repair
it or directly intervene. Contact professionally qualified personnel. Any repair/re-
placement of the products must only be carried out by qualified personnel using orig-
inal replacement parts. Failure to comply with the above could affect the safety of
the unit.

This unit must only be used for its intended purpose. Any other use is deemed im-
proper and therefore hazardous.

The packing materials are potentially hazardous and must not be left within the
reach of children.

The unit must not be used by people (including children) with limited physical, sen-
sory or mental abilities or without experience and knowledge of it, unless instructed
or supervised in its use by someone responsible for their safety.

The unit and its accessories must be appropriately disposed of, in compliance with
the current regulations.

The images given in this manual are a simplified representation of the product. In
this representation there may be slight and insignificant differences with respect to
the product supplied.

2. OPERATING INSTRUCTIONS
2.1 Introduction

Dear Customer,
Thank you for choosing a 

FERROLI

 boiler featuring advanced design, cutting-edge tech-

nology, high reliability and quality construction. Please read this manual carefully since
it provides important information on safe installation, use and maintenance.

PEGASUS D

 is a high-efficiency heat generator for domestic hot water production (op-

tional) and heating, suitable for operation with blown oil or gas burners. The boiler shell
consists of cast-iron elements, assembled with double cones and steel stays. The control
system is with microprocessor and digital interface with advanced temperature control
functions.

A

The boiler is arranged for connection to an external storage tank for hot
water production (optional). In this manual all the functions relevant to
domestic hot water production are only active with the optional hot water
tank connected as indicated in 

sec. 3.3

2.2 Control  panel

fig. 1  - Control panel

Key

1 =

Button -

2 =

3 =

Heating system temperature setting  decrease button

4 =

Heating system  temperature setting increase button

5 =

Display

6 =

Summer  / Winter mode selection button

7 =

Not used

8 =

Reset button

9 =

Unit On / Off  button

10 =

Sliding Temperature" menu button

16 =

Outside sensor temperature (with  optional outside sensor)

17 =

Appears on connecting the outside  Sensor or the Remote Timer Control (op-
tionals)

18 =

Room temperature (with optional Remote Timer  Control)

19 =

Burner On

20 =

Antifreeze operation

21 =

Heating system  pressure

22 =

Fault

23 =

Heating  delivery temperature / setting

24 =

Heating symbol

25 =

Heating mode

26 =

Set heating delivery  temperature reached

27 =

Summer mode

2.3 Lighting  and turning off
Boiler not electrically powered

fig. 2 - Boiler not electrically powered

B

The antifreeze system does not work when the power and/or gas to the unit are
turned off. To avoid damage caused by freezing during long idle periods in win-
ter, it is advisable to drain all water from the boiler, or add a suitable antifreeze
to the heating system, in compliance with that prescribed in  sec. 3.3.

Boiler lighting

Open the fuel on-off valves.

Switch on the power to the unit.

fig. 3 - Boiler lighting

For the following 120 seconds the display will show FH which identifies the heating
system air venting cycle.

During the first 5 seconds the display will also show the card software version.

When the message FH disappears, the boiler is ready to operate automatically
whenever domestic hot water is drawn or in case of a room thermostat demand.

Turning the  boiler off

Press the 

on/off

 button (detail 9 - fig. 1) for 1 second.

fig. 4 - Turning the boiler off

When the boiler is turned off, the electronic board is still powered.
Heating operation is disabled. The antifreeze system remains activated.
To relight the boiler, press the 

on/off

 button (detail  9 - fig. 1) again for 1 second.

fig. 5

The boiler will be immediately ready to operate whenever  domestic hot water is drawn
or in case of a  room thermostat demand.

Shutting down the boiler for prolonged periods

To turn off the boiler:

Press the ON/OFF button (9 - fig. 1)

Close the gas cock ahead of the boiler.

Disconnect the power to the unit.

B

To avoid damage caused by freezing during long idle periods in winter, it is ad-
visable to drain all the water from the boiler; DHW and system. Otherwise, drain
just the DHW circuit and add a suitable antifreeze to the heating system, com-
plying with that prescribed in sec. 3.3.

eco

comfort

m

od

e

r e s e t

bar

5

7

9

10

2

1

8

6

4

3

16

17

18

20

21

22

23

25

24

26

27

19

eco

comfort

m

od

e

r e s e t

eco

comfort

m

od

e

r e s e t

eco

comfort

m

o

de

r e s e t

eco

comfort

m

o

de

r e s et

eco

bar

Summary of Contents for PEGASUS D

Page 1: ...E E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATION D INS...

Page 2: ...a digitale con funzionalit avanzate di termoregolazione A La caldaia predisposta per il collegamento ad un bollitore esterno per acqua calda sanitaria opzionale In questo manuale tutte le funzioni re...

Page 3: ...e modificarla con i tasti sanitario part 1 e 2 fig 1 Regolare la curva desiderata da 1 a 10 secondo la caratteristica fig 11 Regolando la curva a 0 la regolazione a temperatura scorrevole risulta disa...

Page 4: ...e di acqua calda sanitaria Effettuare gli allacciamenti idraulici secon do lo schema fig 14 pompe e valvole di non ritorno devono essere fornite a parte Effettuare collegamenti elettrici come indicato...

Page 5: ...golazione della pressione 4 2 Messa in servizio B La messa in servizio deve essere effettuata da Personale Qualificato e di sicura qualificazione Verifiche da eseguire alla prima accensione e dopo tut...

Page 6: ...chiusura della camera fumi 3 Scovolo 7 Tappo per l analisi della combustione Analisi della combustione All interno della caldaia nella parte superiore dell antirefouleur stato inserito un punto di pr...

Page 7: ...po l inter vento del termostato fumi il funzionamento della caldaia viene impe dito per 20 minuti Contatto termostato fumi aperto Verificare il termostato Cablaggio interrotto Verificare il cablaggio...

Page 8: ...80 4x2 80 Pressione gas alimentazione G20 mbar 20 20 20 Pressione max valle valvola gas G20 mbar 15 13 15 Pressione min valle valvola gas G20 mbar 2 5 2 5 2 5 Portata gas max G20 m3 h 2 68 3 69 5 24 P...

Page 9: ...82 Elettrodo rilevazione 126 Termostato fumi 130 Circolatore sanitario opzionale 138 Sonda esterna non fornito 139 Unit ambiente non fornito 246 Trasduttore di pressione 278 Sensore doppio Sicurezza...

Page 10: ...n effettuato a cura dell azienda inosservanza delle istruzioni e delle avvertenze previste dall azienda produttrice e riportate sui manuali di utilizzo a corredo del prodotto errata installazione o in...

Page 11: ...gua sanitaria descritas en este manual son v lidas s lo si el acumulador sa nitario opcional est conectado como se indica en sec 3 3 2 2 Panel de mandos fig 1 Panel de control Leyenda 1 Tecla 2 Tecla...

Page 12: ...1 Si se elige la curva 0 la regulaci n con temperatura adaptable queda desactivada fig 9 Curva de compensaci n Si se pulsan las teclas de la calefacci n 3 y 4 fig 1 se accede al desplazamiento paralel...

Page 13: ...ca de la caldera puede controlar un acumulador exterior para la pro ducci n de agua caliente sanitaria Realizar las conexiones hidr ulicas seg n el esque ma fig 14 las bombas y las v lvulas antirretor...

Page 14: ...ene que ser efectuada por personal cualificado Con troles que se han de efectuar durante el primer encendido tras las operacio nes de mantenimiento que exigen desconectar la caldera y despu s de toda...

Page 15: ...e de la c mara de humos 3 Cepillo 7 Tap n para el an lisis de la combusti n An lisis de la combusti n Dentro de la caldera en la parte superior del cortatiro hay un punto de toma de humo 7 fig 19 Para...

Page 16: ...s la cual la caldera queda bloqueada durante 20 segundos Contacto del termostato de humos abierto Controlar el termostato Cableado interrumpido Controlar el cableado Chimenea mal dimensio nada u obstr...

Page 17: ...taci n gas G20 mbar 20 20 20 Presi n m xima despu s de la v lvula de gas G20 mbar 15 13 15 Presi n m nima despu s de la v lvula de gas G20 mbar 2 5 2 5 2 5 Caudal m ximo de gas G20 m3 h 2 68 3 69 5 24...

Page 18: ...do 82 Electrodo de detecci n 126 Termostato de humos 130 Bomba de circulaci n del agua sanitaria opcional 138 Sonda exterior no suministrada 139 Unidad ambiente no suministrada 246 Transductor de pres...

Page 19: ...go de los componentes siendo por cuenta del usuario la mano de obra y el desplazamiento Cuerpo de las calderas de chapa Un a o Cuerpo de las calderas de hierro fundido Un a o cada elemento Cuerpo de c...

Page 20: ...ayarlama fonksiyonlar na sahip dijital aray zl bir mikroi lemcidir A Kombi s cak musluk suyu retimi i in harici bir s t c kazana ba lanmak zere tasarlanm t r opsiyonel Bu kullan m k lavuzundaki s cak...

Page 21: ...ak k s m 1 ve 2 ek 1 de i tirilmesi m mk nd r E riyi 1 ile 10 saniye aras nda istedi iniz gibi ayarlay n z ek 11 E ri 0 a ayarland nda s cakl k ak ayarlamas devre d kal r ek 9 Kompenzasyon e risi Is t...

Page 22: ...ap n z pompalar ve geri d n valflar ayr ca tedarik edilmelidir A a dakiler ger ekle tiriniz cap 5 4 k sm ndaki elektrik emas nda g sterilen elektrik ba lant lar Bir FERROLI sen s r n n kullan lmas ger...

Page 23: ...Kalifiye Personel ve yeterlili e sahip ki iler ta raf ndan yap lmal d r lk al t rma an nda ve sistemden ba lant n n kesilmesi veya emniyet cihazlar nda ya da kombinin di er aksamlar nda bir bak m i le...

Page 24: ...1 Muhafaza kapa 2 Duman odas kapatma plakas 3 F r a 7 Yanma analizi t pas Yanma analizi Dumanlar n rneklemesi amac yla bir nokta kombinin i erisinde geri ak nleme cihaz n n st k sm nda bulunmaktad r k...

Page 25: ...ostat n n konta a kt r Termostat kontrol ediniz Kablolarda kopukluk var Kablo tesisat n kontrol ediniz Bacan n ebatlar yanl t r veya t kal durumdad r Duman kanal n de i tiriniz A06 Ate leme a amas nda...

Page 26: ...lar G20 n x 2x2 80 3x2 80 4x2 80 Besleme gaz bas nc G20 mbar 20 20 20 Gaz G20 valf y n nde maks bas n mbar 15 13 15 Gaz G20 valf y n nde min bas n mbar 2 5 2 5 2 5 Maks gaz k G20 m3 s 2 68 3 69 5 24...

Page 27: ...elektrotu 126 Duman termostat 130 Musluk suyu devir daim pompas opsiyonel 138 Harici sens r cihazla birlikte verilmez 139 Oda nitesi cihazla birlikte verilmez 246 Bas n d r c 278 ift sens r Emniyet Is...

Page 28: ...ranged for connection to an external storage tank for hot water production optional In this manual all the functions relevant to domestic hot water production are only active with the optional hot wat...

Page 29: ...d 2 fig 1 Adjust the required curve from 1 to 10 according to the characteristic fig 11 By setting the curve to 0 sliding temperature adjustment is disabled fig 9 Compensation curve Press the heating...

Page 30: ...Carry out the plumbing connections according to the diagram fig 14 pumps and non return valves must be supplied separately Carry out electrical connections as shown in the wiring diagram incap 5 4 A...

Page 31: ...5 Protection cap 6 Pressure adjustment screw 4 2 Start up B System start up must be carried out by Qualified Personnel Checks to be made at first lighting and after all maintenance operations that in...

Page 32: ...e brush 7 Combustion analysis plug Combustion analysis A point for sampling fumes has been included inside the boiler in the upper part of the anti backflow device detail 7 fig 19 To take the sample 1...

Page 33: ...Vent the system F04 Fume thermostat acti vated after activation of the fume thermostat boiler operation is pre vented for 20 minutes Fume thermostat contact open Check the thermostat Wiring disconnect...

Page 34: ...2x2 80 3x2 80 4x2 80 Gas supply pressure G20 mbar 20 20 20 Max pressure downstream of gas valve G20 mbar 15 13 15 Min pressure downstream of gas valve G20 mbar 2 5 2 5 2 5 Max gas delivery G20 m3 h 2...

Page 35: ...Detection electrode 126 Fume thermostat 130 DHW circulating pump optional 138 External probe not supplied 139 Room unit not supplied 246 Pressure transducer 278 Double sensor Safety Heating DSP05 7 6...

Page 36: ...temp rature A Un ballon ext rieur option servant la production d eau chaude sanita ire peut tre raccord la chaudi re Dans ce manuel toutes les fonc tions relatives la production d eau chaude sanitaire...

Page 37: ...t ristique fig 11 Si la courbe est r gl e sur 0 le r glage de la temp rature volutive est d sactiv fig 9 Courbe de compensation Appuyer sur les touches chauffage rep 3 et 4 fig 1 pour passer au d plac...

Page 38: ...eau chaude sanitaire La carte lectronique de l appareil est pr vue pour la gestion d un ballon externe pour la production d eau chaude sanitaire Effectuer les raccordements hydrauliques selon le sch m...

Page 39: ...ce B La mise en service doit tre effectu e par du personnel qualifi disposant du savoir faire et de l expertise n cessaires V rifications effectuer au premier allumage et apr s toutes les op rations d...

Page 40: ...Bouchon pour l analyse de la combustion Analyse de la combustion Un point de pr l vement des fum es a t pr vu l int rieur de la chaudi re dans la partie sup rieure de l antirefouleur rep 7 fig 19 Pour...

Page 41: ...ement du ther mostat s curit fum es apr s son d clenche ment le fonctionnement de la chaudi re est d sactiv pendant 20 minutes Contact de thermostat s curit fum es ouvert V rifier le thermostat C blag...

Page 42: ...ur G20 nbre x 2x2 80 3x2 80 4x2 80 Pression d alimentation gaz G20 mbar 20 20 20 Pression maxi en aval vanne gaz G20 mbar 15 13 15 Pression mini en aval vanne gaz G20 mbar 2 5 2 5 2 5 D bit gaz maxi G...

Page 43: ...lectrode de d tection 126 Thermostat fum es 130 Circulateur eau chaude sanitaire option 138 Sonde ext rieure non fournie 139 Unit d ambiance non fournie 246 Transducteur de pression 278 Capteur double...

Page 44: ...19 20 21 22 23 24 25 26 27 2 3 2 B e sez 3 3 3 120 FH 5 FH on off 9 1 1 4 on off 9 1 1 5 9 1 B sez 3 3 eco comfort m o d e r e s e t bar 5 7 9 10 2 1 8 6 4 3 16 17 18 20 21 22 23 25 24 26 27 19 eco co...

Page 45: ...1 0 F37 13 13 A 120 FH eco comfort m o d e r e s e t eco bar eco comfort m o d e r e s e t eco bar eco comfort m o d e r e s e t eco bar ECO COMFORT Eco nomy 7 1 Comfort 7 1 20 30 40 50 60 70 80 90 8...

Page 46: ...U cod 3540U171 06 2012 Rev 00 3 3 1 3 2 A 3 3 B cap 5 1 25 Fr 1 F 10 CaCO3 15 F 236 88 B 6 C 14 cap 5 4 FERROLI 14 8 9 10 11 3 4 B 25 B 3 5 B Y 3 3A 2 B HAR H05 VV F 3x0 75 2 8 B 230 A 15 3 6 0 5 22 2...

Page 47: ...16 TEST TEST TEST 15 PEGASUS D 17 cap 5 2 1 5 17 2 2 17 3 6 17 cap 5 2 4 2 3 G20 G25 G30 G31 1 cap 5 3 2 3 17 G20 G25 D 17 G30 G31 E 17 3 4 17 A B C D G20 G25 E G30 G31 1 2 3 4 5 6 4 2 B 1 17 120 FH...

Page 48: ...PEGASUS D 48 RU cod 3540U171 06 2012 Rev 00 18 B 18 19 19 1 2 3 7 7 19 1 2 3 4 5 TEST 6 10 15 7 A 20 20 21 1 2 3 4 5 6 7 8 3 2 1 7 3 3 4 mm 5 4 8...

Page 49: ...11 44 126 246 273 275 A01 A02 A03 F04 20 A06 F10 1 F14 2 i F34 170 F35 F37 F39 F40 o A41 F42 F47 A48 A49 400 850 246 44 275 273 44 275 615 70 10 7 111 181 582 261 37 10 11 7 112 109 126 500 850 246 4...

Page 50: ...2 P Pmax 80 60 C 90 9 91 7 90 9 30 91 3 91 5 91 6 92 42 CE NOx 2 2 2 G20 x 2 x 2 80 3 x 2 80 4 x 2 80 G20 20 20 20 G20 15 13 15 G20 2 5 2 5 2 5 G20 3 2 68 3 69 5 24 G20 3 1 07 1 58 2 08 G31 x 2 x 1 75...

Page 51: ...1 82 126 130 138 139 246 278 DSP05 7 6 5 4 3 2 1 11 10 9 8 7 6 5 4 3 2 1 T1 T2 X7 7 6 5 4 3 2 1 6 5 4 3 2 1 X5 F1 F2 X1 X2 X4 X3 X6 X8 X10 2 1 T T 278 GND 5V OUT 246 L N 230V 50Hz 138 139 72 L N 4 5 6...

Page 52: ...9 10 16 17 18 19 20 21 22 23 24 25 26 27 Estate 2 3 2 B i i sez 3 3 i i i i i 3 i 120 FH i 5 i FHI on off 9 1 1 4 i i i i on off i 9 1 1 5 i i ON OFF 9 1 B i i i i i i i i sez 3 3 eco comfort m o d e...

Page 53: ...10 10 1 i i i i i 11 12 i i A i i i i i i 1 5 1 1 i 1 0 i i i i i F37 13 13 A i i i i 120 FH eco comfort m o d e r e s e t eco bar eco comfort m o d e r e s e t eco bar eco comfort m o d e r e s e t e...

Page 54: ...i i CaCO3 i i i i i i i 15 F I i i 236 88 B i i i i i i 6 C i i i i i i i i i 14 i cap 5 4 FERROLI i i i i i i i 14 i i 8 9 10 i 11 3 4 B i i i i i i i i i i i i i i i 25 i i i i i i i i i i i i i i...

Page 55: ...5 17 2 i i 2 17 i 3 i 6 17 i i cap 5 2 4 i i i i i i 2 3 i i i i i G20 G25 G30 G31 1 i cap 5 3 2 i i 3 17 i G20 G25 D 17 G30 G31 E 17 3 i i i 4 17 A B C i D G20 G25 E G30 G31 1 2 i 3 4 5 6 4 2 B i i i...

Page 56: ...i i i 19 i i i i i i i i i i i i i i i i i i i i i i i i i i 19 1 2 i i 3 7 i i i i i i i 7 19 1 i i 2 i i i i 3 i i i i 4 5 i TEST 6 10 15 7 A i i i i i i i i i i i i i i i i i i i 20 i i i i i i i i...

Page 57: ...PEGASUS D 45 7 10 11 44 126 246 273 275 A01 A02 A03 F04 20 A06 F10 1 F14 2 F34 170 F35 F37 F39 F40 A41 F42 F47 A48 A49 400 850 246 44 275 273 44 275 615 70 10 7 111 181 582 261 37 10 11 7 112 109 126...

Page 58: ...2 P i i i Pmax 80 60 C 90 9 91 7 90 9 i i i 30 91 3 91 5 91 6 92 42 EEC NOx 2 2 2 G20 x 2x2 80 3x2 80 4x2 80 G20 20 20 20 G20 15 13 15 G20 2 5 2 5 2 5 G20 3 2 68 3 69 5 24 G20 3 1 07 1 58 2 08 G31 x...

Page 59: ...1 82 126 130 138 139 246 278 DSP05 7 6 5 4 3 2 1 11 10 9 8 7 6 5 4 3 2 1 T1 T2 X7 7 6 5 4 3 2 1 6 5 4 3 2 1 X5 F1 F2 X1 X2 X4 X3 X6 X8 X10 2 1 T T 278 GND 5V OUT 246 L N 230V 50Hz 138 139 72 L N 4 5 6...

Page 60: ...ettiva Compatibilit Elettromagnetica 2004 108 Presidente e Legale rappresentante Cav del Lavoro Dante Ferroli IT Uygunluk beyani malat i FERROLI S p A Adres Via Ritonda 78 a 37047 San Bonifacio VR bu...

Page 61: ...8 Dante Ferroli RU D claration de conformit Le constructeur FERROLI S p A Adresse Via Ritonda 78 a 37047 San Bonifacio VR d clare que cet appareil est conforme aux directives CEE ci dessous Directives...

Page 62: ......

Page 63: ......

Page 64: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it...

Reviews: