36
DOMINA OASI F 24 - 30 E
FERELLA BOIL F 24 - 30 MEL
KEA AIR COMPACT E
Version - 09.2002
Flow Diagram 4
Checking Fan/Fume Circuit
Does the fan turn?
Is the relay RY02 closed?
Proceed with diagrams 2-3
NO
Are there 230V at the
fan terminals?
YES
Check the electrical connection
of the air pressure switch
NO
Check and if necessary
change the air pressure switch
NO
Check and if necessary
change the fan
YES
Is the air pressure
switch activated?
YES
NO
Check and if
necessary change
the air pressure
switch
YES
Is the pressure
difference in the air
pressure switch greater
than 180 Pascal?
Proceed with
diagram 5
YES
NO
Check and
clean the fan
Check that the air inlet
and fume outlet are
correct and clean
Check that the Venturi tube
and the air pressure switch
tubes are clean
Check that
the diaphragm is correct
NO