BLUEHELIX PRO C
40
EN
Compensation curve and curve offset
Press the
reset button
(detail 6 - fig. 1) for 5 seconds to access the “Sliding temperature”
menu; the display shows “CU” flashing.
Use the DHW buttons (detail 1 - fig. 1) to adjust the desired curve from 1 to 10 according
to the characteristic (fig. 11). By setting the curve to 0, the sliding temperature adjust-
ment is disabled.
Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display
shows “OF” flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust parallel curve offset
according to the characteristic (fig. 12).
Press the
reset button
(detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temper-
ature" menu.
If the room temperature is lower than the required value, it is advisable to set a higher
order curve and vice versa. Proceed by increasing or decreasing in steps of one and
check the result in the room.
fig. 11 - Compensation curves
fig. 12 - Example of compensation parallel curve offset
Adjustments from Remote Timer Control
A
If the Remote Timer Control (optional) is connected to the boiler, the above ad-
justments are managed according to that given in table 1.
Table. 1
System water pressure adjustment
The filling pressure read on the boiler water gauge with the system cold must be approx
1.0 bar. If the system pressure falls to values below minimum, the boiler stops and fault
F37
is displayed. Operate the filling knob (detail 1 - fig. 13) and bring it to the initial value.
Always close the knob afterwards.
Once the system pressure is restored, the boiler will activate the 300-second air venting
cycle indicated on the display by
FH
.
fig. 13 - Filling knob
3. INSTALLATION
3.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSON-
NEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL
MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NA-
TIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.
3.2 Place of installation
B
The combustion circuit is sealed with respect to the place of installation
and therefore the unit can be installed in any room except in a garage. The
place of installation must be sufficiently ventilated to prevent the creation
of dangerous conditions in case of even small gas leaks. Otherwise there
may be a risk of suffocation and intoxication or explosion and fire. This
safety precaution is required by EEC Directive No. 2009/142 for all gas
units, including so-called sealed chamber units.
The unit is designed to operate in a partially protected place, with a minimum tempera-
ture of -5°C. If provided with the special antifreeze kit, it can be used with a minimum tem-
perature down to -15°C. The boiler must be installed in a sheltered place, for instance
under the slope of a roof, inside a balcony or in a protected recess.
The place of installation must be free of flammable materials, objects and dusts or cor-
rosive gases.
The boiler is arranged for wall mounting and comes as standard with a hooking bracket.
Wall fixing must ensure stable and effective support for the generator.
A
If the unit is enclosed in a cabinet or mounted alongside, there must be suffi-
cient space for removing the casing and for normal maintenance activities
3.3 Plumbing connections
Important
B
The safety valve outlet must be connected to a funnel or collection pipe to pre-
vent water spurting onto the floor in case of overpressure in the heating circuit.
Otherwise, if the discharge valve cuts in and floods the room, the boiler manu-
facturer cannot be held liable.
B
Before installation, flush all the pipes of the system thoroughly to remove any
residuals or impurities that could affect proper operation of the unit.
In case of replacement of generators in existing installations, the system must
be completely emptied and cleaned of any sludge and pollutants. For that pur-
pose only use suitable guaranteed products for heating systems (see next sec-
tion), that do not harm metals, plastics or rubber.
The manufacturer declines
any liability for damage caused to the generator by failure to properly
clean the system
.
Carry out the relevant connections according to the diagram in fig. 14 and the symbols
on the unit.
fig. 14 - Plumbing connections
1 =
System delivery - Ø 3/4”
2 =
DHW outlet - Ø 1/2”
3 =
Gas inlet - Ø 1/2”
4 =
DHW inlet - Ø 1/2”
5 =
System return - Ø 3/4”
Heating temperature setting
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
DHW temperature adjustment
Adjustment can be made from the Remote Timer Control menu
and the boiler control panel.
Summer/Winter Switchover
Summer mode has priority over a possible Remote Timer Control
heating demand.
Eco/Comfort selection
On disabling DHW from the Remote Timer Control menu, the
boiler selects the Economy mode. In this condition, the
eco/com-
fort
button (detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the
boiler selects the Comfort mode. In this condition it is possible
select one of the two modes with the
eco/comfort
button (detail 7
- fig. 1) on the boiler panel.
Sliding Temperature
Both the Remote Timer Control and the boiler card manage Slid-
ing Temperature adjustment: the boiler card Sliding Temperature
has priority.
20
30
40
50
60
70
80
90
85
20
10
0
-10
-20
1
2
3
4
5
6
8
9
10
7
20
30
40
50
60
70
80
90
85
20
30
40
50
60
70
80
90
85
1
2
3
4
5
6
8
9
10
7
1
2
3
4
5
6
8
9
10
7
OFFSET = 20
OFFSET = 40
A
C
1
1 2 3 4
5
150
35.5
76 54 51 80.5
157
105
35
103
cod. 3541F554 - Rev. 00 - 11/2018