2.2

 

Placement on wall  

 

1.

 

Mount screws & washers in the brackets towards the wall. 
(Screws elements are 

not

 included the installation kit) 

 

2.3

 

Installation of SSO:s (1-15) 

NOTE!

  To  calculate  correct  cable  dimensions  you  can  use 

Ferroamp

online 

cable 

calculator, 

available 

at 

www.ferroamp.com

 under the support section. 

 

1.

 

Unscrew the front plate as shown above. The front plate is 

attached with a PE-cable to the cabinet. 

 

2.

 

Connect  L-,  L+  &  PE  from  each  SSO  to  designated  screw 

terminal.  

3.

 

Make sure that all terminals are tightened to 2.5 Nm, use a 

torque wrench. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Power Distribution 15

Page 1: ...Installation manual Swe En Power Distribution 15 Rev A01 Rev B01...

Page 2: ......

Page 3: ...troduction 6 1 1 Included items 6 1 2 Warnings and recommendations 6 1 3 Explanation of safety notices 6 1 4 Dimensions 6 1 5 Components 7 1 6 Connections 7 1 7 Inlets and cable glands 7 2 Installatio...

Page 4: ...uta enheter till liksp nningsn tet n r det r sp nningssatt VARNING Risk f r elektrisk st t och ljusb ge om produkten inte hanteras i enlighet med manualens instruktioner VARNING Anv nd inte produkten...

Page 5: ...felaktig eller v rdsl s installation NOTERA Ferroamp rekommenderar att ndhylsor anv nds f r samtliga anslutningar med m ngtr diga ledare 2 1 N dv ndiga verktyg Skruvmejslar o Sp r 1x5 mm o Kryss TBD...

Page 6: ...15 NOTERA F r att ber kna korrekt kabeldimension anv nd Ferroamps kabelkalkylator som finns tillg nglig p www ferroamp se under supportfliken 1 Skruva loss t ckpl ten enligt bilden ovan T ckpl ten r k...

Page 7: ...alen p kopplingssk pets front 3 Underh ll Vid byte av utl st s kring skall en s kring med f ljande specifikation anv ndas Driftklass gPV Dimensioner 10x38 mm M rkstr m 15 A M rksp nning 1000 VDC Brytf...

Page 8: ...to connect units to the DC nanogrid when it is energized WARNING Risk of electrical shock arc if the product is not used according to the instructions in the manual WARNING Do not use the product if y...

Page 9: ...tallation NOTE We recommend that you use end terminals for all connection points that have multi threaded conductors 2 1 Required tools Screwdrivers o Slot drive 1x5 mm o Philips TBD Socket wrench o N...

Page 10: ...calculate correct cable dimensions you can use Ferroamp s online cable calculator available at www ferroamp com under the support section 1 Unscrew the front plate as shown above The front plate is at...

Page 11: ...arning label on the front door 3 Maintenance When a fuse trips replace it with a fuse with the following specifications Characteristic gPV Dimensions 10x38 mm Current rating 15 A Voltage rating 1000 V...