Fenwal Controls Series 35-703 Manual Download Page 4

Effective: March 2020

4

F-35-703

Flame Current Measurement

Flame current is the current that passes through the flame from    
sensor to ground. A good burner ground that matches the 
control ground is critical for reliable flame sensing.

LOCAL FLAME SENSE

With power off, connect a DC microamp meter as shown in the 
figure below. During the TFI, the meter should be protected 
from high voltage surge which could damage the meter. A 
jumper wire must be installed across the terminals of the meter. 
Once the flame is established, and sparking terminates, remove 
the jumper wire to measure flame current. The flame sense 
current must be 0.7 uA minimum for proper operation.

REMOTE FLAME SENSE

With power off, remove sense wire from S1 terminal, and install 
a DC microamp meter between the S1 terminal and sense wire. 
Establish flame, then measure flame current. The flame sense 
current must be 0.7 uA minimum for proper operation.

DIMENSIONS

Figure 4. Enclosure

Figure 5. Potted

Figure 6. Integral Standoff

35-703

Note: 

All dimensions are in inches

Summary of Contents for Series 35-703

Page 1: ... to ANSI Z21 20 CAN CSA C22 2 No 199 M89 Input Power 102 to 138 VAC 50 60 Hz Input Current 350 mA 120 VAC with main and pilot gas valve relays energized control only Main Gas Valve 1 5A max 120 VAC Pilot Gas Valve 1 5A max 120 VAC Operating Temperature 40 F to 160 F 40 C to 71 C Storage Temperature 40 F to 185 F 40 C to 85 C Flame Sensitivity 1 0 µA minimum Flame Failure Response 0 8 seconds maxim...

Page 2: ...and entering lockout If the pilot burner relights normal operation resumes FLAME FAILURE RECYCLE MODE With the Recycle After Loss of Flame option upon loss of flame the pilot and main gas valves are de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the pilot burner relights normal o...

Page 3: ...HOOTING Note During a fault condition the LED will flash on for 1 4 second and off for 1 4 second as needed to indicate the fault code The code will repeat every 3 seconds Removing power from the control will clear the fault code L2 SPARK BURNER BURNER GROUND H V OUT 120V THERMOSTAT OR CONTROL DEVICE L1 PV MV L2 L2 V2 L1 B GND PV1 MV1 L1 L2 120V THERMOSTAT OR CONTROL DEVICE PV MV L2 L2 V2 L1 B GND...

Page 4: ...the meter A jumper wire must be installed across the terminals of the meter Once the flame is established and sparking terminates remove the jumper wire to measure flame current The flame sense current must be 0 7 uA minimum for proper operation REMOTE FLAME SENSE With power off remove sense wire from S1 terminal and install a DC microamp meter between the S1 terminal and sense wire Establish flam...

Page 5: ...rge 0 None Single Try Only 1 15 Seconds 2 30 Seconds 3 45 seconds 4 4 minutes Pre Purge 0 None 1 15 Seconds 2 30 Seconds 3 45 Seconds 4 4 minutes Tries for Ignition Flame Sense Method and Reset Method 0 1 try local sense 1 1 try remote sense 2 1 try local sense 3 1 try remote sense 5 3 try local sense 6 3 try remote sense 7 3 try local sense 8 3 try remote sense Configuration and Wiring Options 5 ...