Effective: October 2018
06-237172-002
3
Figure 2. 35-6084 6 Pin Local Sense
Figure 3. 8 Pin Local Sense Wiring
HIGH VOLTAGE AND REMOTE SENSE
CABLE REQUIREMENTS
The HV Ignition Cable must meet a voltage rating of 25 KV and
an insulation rating of 200 °C. Recommend length of 3ft (.9m)
or less. Consult factory for longer lengths.
Remote flame sense cable must meet a voltage rating of 250V
and an insulation rating of 200 °C. Recommended length of 10ft
(3m) or less. Consult Factory for longer lengths.
Remote Sense
BURNER
1
4
5
2
3
(2 CONTACTS)
H.V.
GND
GAS
VALVE
TH
VALVE
24 VAC
6
VALVE
GND
RESET
NC
S1
Local Sense
BURNER
1
4
5
2
3
(2 CONTACTS)
H.V.
GND
GAS
VALVE
TH
VALVE
24 VAC
6
VALVE
GND
RESET
NC
S1
FL AM E
SENSOR
Local Sense
BURNER
1
2
5
6
3
4
FC +
(2 CONTACTS)
FC -
H.V.
GND
GND
GAS
VALVE
TH
MV
24 VAC
7
8
GND
RESET
24V
ALAR M
Remote Sense
BURNER
1
2
5
6
3
4
FC +
(2 CONTACTS)
FC -
H.V.
GND
GND
GAS
VALVE
TH
MV
24 VAC
7
8
GND
RESET
24V
ALAR M
FL AM E
SENSOR
S1