Fema TAS-1-IDC User Manual Download Page 10

User’s Manual Series TAS-1

FEMA ELECTRÓNICA - Page 10

The TSAT board adds analog output capabilities to the TAS-1
instruments. Jumper selectable for voltage ( 0/10 Vdc) and for
current (4/20mA and 0/20mA in modes SINK and SOURCE) adds
a galvanic isolation of 2KVeff.

The analog output adjustment is done via the frontal keypad. The
analog output value is adjusted related to the display indication.
This allows the intelligent use of the correction functions for offsets
and fast readjustment of the TAS-1 series, meaning that when

7.1.3- START-UP

1.- Place jumpers on TSAT board for Vdc or mA output

2.- Plug the TSAT board on the bus pins (Expansion Bus) on
board AL2 or EXP

3.- To configure the analog output you need to know the analog
output signal and the related  display indication

Input Signal

Indication

Analog Output

4  mA

0

0 Vdc (00000 miliVots)

20 mA

100.00

10 Vdc (10000 miliVolts)

7- AVAILABLE OPTIONS - INSTALLING AND CONFIGURING

7.1- ANALOG OUTPUT - TSAT OPTION BOARD

readjusting the input/display readings, the analog output
does not need to be readjusted most of the times.

in case of trouble with the input signal, such as loop
break or sensor break, the analog output signal will
exhibit always the same behaviour predefined by the
operator on the menu.

7.1.1- CONNECTIONS

Voltage Output

.-

Terminal 12 (Negative)
Terminal 13 (Positive)

Current Output

.-

Terminal 13 (Negative)

(Source = Active)

Terminal 14 (Positive)

Current Output

.-

Terminal 12 (Negative)

(Sink=Pasive needs

Terminal 13 (Positive)

external power supply)

R

l

-  

Terminal 12

Terminal 13

R

l

+

-

Vext

Terminal 12

Terminal 13

7.1.2- TECHNICAL CHARACTERISTICS

Output Signals

0/10 Vdc, 0/20 mA and 4/20 mA (and others)

Resolution

12 bits

Accuracy

<0.1% FS

Ripple

<0.01% FS

Thermal Drift

100 ppm/ºC

Pass Band

1.5 Hz (-3 dB)

Response Time

250 ms (99% of indication)

Isolation Levels

2KVeff (50 Hz, 1 minute)

mA Output

RLmax

500 Ohms (Source Mode)

Imax

21.5 mA aprox.

SINK Output maximum 40Vdc on terminals

Vdc Output

RL min

1 KOhm

Vmax

11 Vdc aprox.

R

l

-  

+  

Terminal 13

Terminal 14

Terminal 12

Terminal 13

Terminal 14

Jumpers to the left.-
Output in Vdc

Jumpers to the right.-
Output in mA

Note .- Analog output units are entered with 3 decimals, this
is, in miliVolts and microAmperes.

4.- Make connections, power the unit and configure the board
(see next page)

Summary of Contents for TAS-1-IDC

Page 1: ...CA Page 1 FEMA ELECTR NICA INTELLIGENT PANEL METERS Series TAS 1 Intelligent Panel Meters info fema es www fema es USER S MANUAL AC Current DC Current AC Voltages DC Voltages TAS 1 IAC TAS 1 IDC TAS 1...

Page 2: ...ration 6 4 6 Manual Adjustment 7 4 7 Dealing with Errors 7 4 8 Advanced Indication 7 4 9 Blocking the Keypad 7 4 10 Resetting the system Default values 7 4 11 Messages and Errors 8 5 Configuring with...

Page 3: ...Level Input Signal correction Key DP Decimal Point Position Key PROG Allows the introduction of the PROGRAMMING codes 4 digit codes as shown on page 4 These codes when validated activate different inp...

Page 4: ...t 14 14 INPUT ONERR OFF ON 1 1 Visualization 14 13 DISPLAY NULL LAST 1 1 ON OFF 1 1 OFF ON 3 2 1 FIL 2 FIL 3 FIL 1 FILT A D Q N AVERA REAL 1 1 INPUT STEP XXXXX Alarm 1 Alarm 2 Alarm 3 Alarm 4 13 11 AL...

Page 5: ...ion XXXX X 1 Press DP 2 message DP during 1 second Press 2 to fix decimal point position 2 To fix at other positions press 1 2 3 4 or 5 3 Validate changes pressinf message INPUT shows the configuratio...

Page 6: ...m activation The hysteresis points are defined on parameter HYST for each alarm Security Mode activated on alarms acting as minimum Securty Mode deactivated Output relay are inactive until the set poi...

Page 7: ...Code 14 11 Function Code 14 22 Function Resets the unit to the default manufacturing values It is needed to reconfirm the action by pressing INTRO after the message Acquisition Mode Real STEPValue 10...

Page 8: ...recovers the normal working state when situation clears Errors Errors are associated with critical situtations which disable the hability to measure the signal The error remains active on display unt...

Page 9: ...tion 32 000 points ENVIRONMENTAL DATA Working Temperature 0 50 C Storage Temperature 20 85 C Humidity 0 85 non condensaded MECAHNICALDATA Dimensions Standard 1 8 DIN 96 x 48 x 124 mm 3 78 x 1 89 x 4 8...

Page 10: ...ot need to be readjusted most of the times in case of trouble with the input signal such as loop break or sensor break the analog output signal will exhibit always the same behaviour predefined by the...

Page 11: ...essage ERROR Informs that at least one of the values is not correct and the whole configuration could not be applied Repeat the process from the begining 7 2 INSTALLING THE OPTION BOARDS The Option Bo...

Page 12: ...mposed of 1 4 bits b0 0 Value contained on register 00 00H is an indication number b0 1 Value contained on register 00 00H is not an indication Word b4 b3 b2 b1 0 Reserved 3 Ovr 6 Con 9 MErr1 12 Reser...

Page 13: ...acion MASTER and SLAVE ADDRESS 1 CHARACTER Instrument Address FUNCTION 1 CHARACTER Function 04H register read READING STARTREGISTER 2 CHARACTERS Register 00 00H Display Value NUMBER OF REGISTERS TO RE...

Page 14: ...tering the Menu Introduce the programming code 14 23 Message E INP TEK board recognized Configuring the external contacts Parameter INP_1 Contact 1 ON Active OFF NotActive Parameter FUN_T Function ass...

Page 15: ...unit to control a machine or process where injury to personnel or damage to equipment or process may occur as a result of failure of the unit External Protection Fuse to be added for 230 Vac 80mA fuse...

Page 16: ...YS COUNTERS PROCESS SIGNALS TEMPERATURES TACHOMETERS SERIAL RSREPEATERS CLOCKS CHRONOMETERS PANEL METERS AC ELECTRICAL SIGNALS DC ELECTRICAL SIGNALS TEMPERATURES LOADCELLS PROCESS SIGNALS TACHOMETERS...

Reviews: