Fema S40-C1 User Manual Download Page 13

FEMA ELECTRÓNICA . Series S . S40-C1

13

1.19 Configuration menu (cont.)

The ‘

Alarms

’ (‘

ALr

’) menu configures the independent activation of 

up to 2 relay outputs (or transistor or control SSR), installed with the 

R1 (or T1 or SSR) optional modules 

(see section 2.1)

For outputs up 

to 4 relays, see special modules R2 and R4 at section 

2.8

The alarm 

states are indicated in the front display with leds marked as ‘1’ and 

‘2’.

To configure an alarm, enter into the alarm menu (‘

ALr1

’ or ‘

ALr2

’) 

and configure the following parameters :

• select ‘

Active

’ (‘

Act

’) to ‘

on

• at ‘

Alarm type

’ (‘

TypE

’) select the alarm to act as a maximum type 

alarm (‘

MAX

’) or a minimum type alarm (‘

MIn

’). The maximum type 

alarm (or minimum type alarm) activates when the display value is 

higher (or lower) than the setpoint value.

• at ‘

Setpoint

’ (‘

SEt

’) enter the value for the alarm activation point

.

 

This parameter is eligible for configuration through the ‘

Fast access

’ 

menu 

(see section 1.19.12).

• configure the hysteresis value at ‘

Hysteresis

’ (‘

hySt

’). The hyster

-

esis applies to the deactivation process of the alarm. The alarm de

-

activates when the reading has passed the setpoint value plus the 

hysteresis value. Hysteresis helps to avoid repetitive switching of the 

alarm relays, due to fluctuating input signals around the setpoint.

• at ‘

Activation delay

’ (‘

dEL.0

’) configure the delay to apply before 

alarm activation. The activation delay starts counting when the set

-

point value is passed. Value from 0.0 to 99.9 seconds.

• at ‘

Deactivation  delay

’  (‘

dEL.1

’)  configure  the  delay  to  apply 

before alarm deactivation. The deactivation delay starts counting 

when the setpoint value plus the hysteresis value, is passed. Value 

from 0.0 to 99.9 seconds.
• to work with ‘windowed alarms’ (see graphical example below) 

activate ‘

Setpoint

2

’ (‘

SEt2

’) to ‘

on

’ and then configure the desired 

second setpoint value. Second setpoint must always be higher in 

value than the first setpoint.
• the ‘

Relay inverted

’ (‘

r.Inv

’) parameter inverts the normal relay 

connections. When set to ‘

on

’ the relay will be active when alarm is 

inactive. For security applications where an inactive relay controls 

the shutdown of the system.
•  the  ‘

Locked alarm

’  (‘

A.Lck

’)  parameter  disables  the  automatic 

deactivation of the alarm. Alarm deactivation must be performed 

manually, by pressing the ‘LE’ front button 

(see section 1.19.14)

• the ‘

On alarm

’ (‘

on.AL

’) parameter assigns a predefined behav

-

iour  when  alarm  is  activated.  Select  ‘

cont

’  to  continue  counting. 

Select ‘

to_0

’  to  load  ‘0’  on  displays.  Select  ‘

to_p

’  to  load  preset 

value on display. Parameter ‘

dEL.1

’ is set to 1 second when ‘

to_0

’ 

or ‘

to_p

’ are selected.

1.19.11 Alarms

On alarm

Continue

To zero

To preset

Alarm 1

Setpoint

Hysteresis

Setpoint 2

Active

Alarm type

Alarms

Activation delay

Deactivation delay

Relay inverted

Locked alarm

Reading

Time

setpoint

hysteresis

Alarm as maximum, 

 

no hysteresis, no delays

on

off

Time

activation 

delay

on

off

deactivation 

delay

Time

Alarm as maximum, 

 

with hysteresis and delays

on

off

Time

Alarm as minimum, 

 

no hysteresis, no delays

Reading

Time

Setpoint 2

Setpoint 1

Alarm as minimum,

 

with double setpoint,

 

no hysteresis, no delays

on

off

Time

Summary of Contents for S40-C1

Page 1: ...with 4 digit display Fast access to alarm setpoints special modes for fast counting and for slow ratemeter applications on power up function configurable reading brightness Universal AC and DC power...

Page 2: ...15 Direct configuration for most usual sensor at the SnSr Auto menu see section 1 19 10 Function Trigger Sense helps to detect the correct trigger level see section 1 13 Multiple display filters memor...

Page 3: ...tor 1 to 9999 and configurable divider factor 1 to 9999 For low frequency applications the SLOW mode provides the best response time for each application see section 1 15 Maximum frequency up to 500 K...

Page 4: ...n sor parameters to the values indicated in the table The table also indicates the typical con nections for each type of sensor Param eters can be manually modified Connections are indicated for a sin...

Page 5: ...d control options relays analog outputs serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0 weight 150 grams front s...

Page 6: ...restart power up or configuration change is used for internal initialization and will not be counted as impulse 1 14 Function cycle counter 1 15 SLOW mode The trigger level is automatically configured...

Page 7: ...ENTER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access me...

Page 8: ...e Impulses input at channel A Channel B disabled Access the Decimal point dP menu to select the decimal point position Move the decimal point by pressing the LE 3 key Configure the function mode selec...

Page 9: ...hen channel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 4 Configuration for cnI 3 Configuration menu for mode counter control add substract cn...

Page 10: ...in formation on the SLoW mode in case of unstable signals activate the average filter AVr func tion It activates a recursive filter on the reading the filter is stronger for higher values from 0 0 to...

Page 11: ...the SLoW parameter configuring the tIME parameter between 1 and 1000 seconds Configure the nuMb parameter between 1 and 32 impulses See section 1 15 for more in formation on the SLoW mode in case of u...

Page 12: ...nnel Act r configures the activa tion of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value of the excita tion voltage at 5 Vdc 9 Vdc 15 Vdc an...

Page 13: ...s at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hysteresis value is passed Value from 0 0 t...

Page 14: ...tpoint2 ALr2 function allows to visualize and modify the alarm2 setpoint through the fast access menu the Memory of maximum MAX or Memory of minimum MIn func tions allow to visualize the maximum or mi...

Page 15: ...et FAct menu select yes to load the default factory configuration for the instrument see section 1 21 1 19 20 Factory reset 1 19 21 Firmware version 1 19 16 Menus Overrange underrange The Counter over...

Page 16: ...unter inhibition Multiplier Divider Preset Preset value 1999 to 9999 Mode Up Down Inhibition Inhibits if chan nel B is high Inhibits if chan nel B is 0 Vdc Multiplier 1 to 9999 Divider 1 to 9999 Confi...

Page 17: ...3 wire PNP 2 wire PNP 3 wire Push pull TTL CMOS Pick up Inductive Vac 30 V Multiplier 1 to 9999 Divider 1 to 9999 Conf ratemeter Multiplier Divider Time window Seconds SLOW mode Average filter Filter...

Page 18: ...h To zero To preset Counter underrange Flash To zero To preset 1 20 Full configuration menu cont On alarm Continue To zero To preset Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Alarms Act...

Page 19: ...ory of cycles 0 Counter overrange flash Counter underrange flash Left zeros off Vexc control off Password off Brightness 3 Alarms 1 and 2 Active off disabled Type maximum Setpoint 1000 Hysteresis 0 co...

Page 20: ...nt slide out of the housing To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module Place all the set into the housing assuring that the modules...

Page 21: ...s and regulations 1 25 Warranty This instrument is warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse accident...

Page 22: ...pt 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per in...

Page 23: ...yed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more informa...

Page 24: ...ration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_en pdf Protocol Modbus RTU Functi...

Page 25: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum an...

Page 26: ...FEMA ELECTR NICA Series S S40 C1 26 Notes...

Page 27: ...FEMA ELECTR NICA Series S S40 C1 27 Notes...

Page 28: ......

Reviews: