background image

FEMA ELECTRÓNICA . Series M . M60-C1

22

Type 

of relay 

 

3 contact relay (NC, NO, common)

Current 

maximum 

8A per relay (resistive load)

Voltage 

maximum* 

250 Vac continuous

Type 

of terminal   

plug-in screw terminal, pitch 5.08 mm

Slots

 allowed 

 

‘Opt.1’, ‘Opt.2’, ‘Opt.3’ 

(see section 1.23)

Output

 ranges 

4/20 mA active, 4/20 mA passive 0/10 Vdc

Accuracy

 (at 25 ºC) 

<0.1% FS

Isolation

 

1000 Vdc

Slots

 allowed 

‘Opt.1’, ‘Opt.2’, ‘Opt.3’ 

(see section 1.23)

The R1 module provides 1 relay output to M Series panel meters. 
Up to a maximum of 3 R1 modules can be installed in a single instru

-

ment  (3 relays). 

Note : for more than three relays per instrument or larger relay den-
sity per module, see special modules R2, R4 and R6 at section 2.6
.

Relays  with  3  contacts  each  (common,  normally  closed,  normally 
open), with switching capability up to 250V @ 8A.

Modules R1 are configured from the ‘ALr1’, ‘ALr2’ and ‘ALr3’ alarm 
menus of the panel meter. The ‘ALrX’ menus provide configuration 
for main setpoint, hysteresis, independent activation and deactiva

-

tion delays, and a second setpoint to create windowed alarms.

Modules R1 are installed on slot ‘

Opt.1

’, ‘

Opt.2

’ or ‘

Opt.3’ (see sec-

tion 1.23)

 and are configured from instruments front keypad.

The R1 module can be ordered pre-installed into a M Series panel 
meter, or standalone for delayed installation, as they do not require 
soldering or special configuration.

2. Output and control modules

2.1 Module R1

2.2 Module AO

Terminal A 

Common

Terminal B 

NO - Normally Open

Terminal C 

NC - Normally Closed

Opt.2

Opt.1

Op

t.3

Power

A B C

A B C

A B C

Signal

The AO module provides 1 analog output with 4/20 mA or 0/10 Vdc 
configurable output range. Output current loop configurable as ac

-

tive (the instrument provides the excitation for the loop) or passive 
(the loop is externally powered). Signal output proportional to the 
instruments  reading.  Fully  configurable  scaling,  in  direct  (positive 
slope) or inverse (negative slope) scaling.

Up to a maximum of 3 analog output modules can be installed in a 
single instrument, all outputs isolated between them and isolated 
from the power and input signal circuits.

Configuration from instrument front keypad, through menu entries 
‘Opt.1’, ‘Opt.2’ or ‘Opt.3’, depending on the position the module is 

installed (see section 1.23).

The RTU module can be ordered pre-installed into a M Series panel 
meter, or standalone for delayed installation, as it does not require 
soldering or special configuration.

Terminal A 

Vexc 

Terminal B 

Signal in mA or Vdc 

Terminal C 

GND

Jumper M 

closed for mA  

Jumper V 

closed for Vdc

M V

A B C

M V

A B C

M V

A B C

Opt.2

Opt.1

Op

t.3

Power

Signal

For  more  information  see  document  3510_SERIES-M_MODULE-
R1_i.PDF

For  more  information  see  document  2654_SERIES-M_MODULE-
AO_i.PDF

Summary of Contents for M60-C1

Page 1: ...N Reading with 6 digit display Fast access to alarm setpoints special modes for fast counting and for slow ratemeter applications on power up function configurable reading brightness Universal AC and...

Page 2: ...tion 1 19 10 Function Trigger Sense helps to detect the correct trigger level see section 1 13 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels I...

Page 3: ...ith scalable read ing The quadrature ratemeter mode has 2 inpur channels available for detection of sense of turn when working with quadrature signals Scalable reading with configurable multiplier fac...

Page 4: ...e SnSr menu entry will configure the sen sor parameters to the values indicated in the table The table also indicates the typical con nections for each type of sensor Param eters can be manually modif...

Page 5: ...ee section 3 2 Output and control options relays analog outputs serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0...

Page 6: ...or falling edge after the instrument restart power up or configuration change is used for internal initialization and will not be counted as impulse 1 14 Function cycle counter 1 15 SLOW mode The tri...

Page 7: ...TER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access menu...

Page 8: ...es input at channel A Channel B disabled Access the Decimal point dP menu to select the decimal point position Move the decimal point by pressing the LE 3 key Configure the function mode selected cnF...

Page 9: ...nnel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 4 Configuration for cnI 3 Configuration menu for mode counter control add substract cnc 4 Tot...

Page 10: ...the SLoW mode and assign the Maximum waiting time between 1 and 1000 seconds See section 1 15 for more information on the SLoW mode in case of unstable signals activate the average filter AVr func tio...

Page 11: ...ture cycle Select 1 4 for 4 impulses per quadra ture cycle for slow frequencies activate the SLoW mode and assign the Maximum waiting time between 1 and 1000 seconds See section 1 15 for more informat...

Page 12: ...channel Act r configures the activa tion of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value of the excita tion voltage at 5Vdc 9Vdc 15Vdc an...

Page 13: ...ivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hysteresis value is passed Value from 0 0 to 99 9 sec...

Page 14: ...instrument gives access to a list of functions configurable by the operator See section 1 17 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu allows to sele...

Page 15: ...1 19 20 Firmware version 1 19 21 Brightness The Counter overrange c orG and Counter underrange c urG parameters configure the behavior of the instrument when reading is higher than 9999 overrange or...

Page 16: ...unter inhibition Multiplier Divider Preset Preset value 199999 to 999999 Mode Up Down Inhibition Inhibits if chan nel B is high Inhibits if chan nel B is 0Vdc Multiplier 1 to 999999 Divider 1 to 99999...

Page 17: ...utomatic conf Edges 1 imp per cycle 2 imp per cycle 4 imp per cycle Average filter SLOW mode Max waiting time 1 to 1000 Sec Filter strength by rising edge by falling edge Activation for channel A Trig...

Page 18: ...s Setpoint2 Active Alarm type Alarms Activation delay Deactivation delay Relay inverted Locked alarm Tools Key UP fast access Memory of maximum Memory of minimum Setpoint1 Setpoint2 Setpoint3 Memory o...

Page 19: ...Vdc Activation for channel A on rising edge on_h Excitation voltage 5Vdc Antirrebound filter 0mSeconds Tools Fast access Key UP off On Power Up Delay 0seconds Key LE reset function Memory of maximum 1...

Page 20: ...ation for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Page 21: ...z Criteria A 61000 4 11 0 1 cycle Criteria A 40 10 cycles Criteria A 70 25 cycles Criteria B 0 250 cycles Criteria B Barber del Vall s April 2013 Daniel Junc Quality Manager 1 25 Warranty 1 26 CE decl...

Page 22: ...tandalone for delayed installation as they do not require soldering or special configuration 2 Output and control modules 2 1 Module R1 2 2 Module AO Terminal A Common Terminal B NO Normally Open Term...

Page 23: ...module for M Series of panel meters ASCII protocol with Master Slave archi tecture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visibl...

Page 24: ...patible with standard R1 modules The R2 R4 and R6 modules can be ordered pre installed into a M Series panel meter or standalone for delayed installation as they do not require soldering or special co...

Page 25: ...FEMA ELECTR NICA Series M M60 C1 25 T h i s p a g e b l a n k...

Page 26: ...ve the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front...

Page 27: ...r96x48mm instruments Front IP65 protector for M Se ries and K Series panel meters Benchtop housing for M Series and K Series panel meters Handle with three selectable positions Power connector with ma...

Page 28: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Reviews: