FEMA ELECTRÓNICA . Series K . K40-232
10
1.16 Registers in ‘Process slave’ mode
List of registers accessible
for an instrument configured
in ‘Process slave’ mode.
• register 0 contains the value to show on display. It is a numerical
value, with or without polarity at the first character (‘+’ or ‘-’) and
with a single decimal point, or without decimal point.
Example 1 : send characters ‘+’ ‘7’ ‘4’ ‘.’ ‘6’ ‘1’ to read on dis
-
play ‘74.61’
Example 2 : send characters ‘-’ ‘0’ ‘4’ ‘6’ to read on display
‘-46’
• registers 3, 4 and 5 contain the setpoint values for alarms 1, 2
and 3. By default, write access to these registers is disabled (set
-
point value is modified through the front keypad). To enable read
Register
number
Name
Type
(R=Read, W=Write)
Description
0
Display
R / W
Register with the display value, including the decimal point and polarity.
1
Reserved
---
---
2
Reserved
---
---
3
Setpoint 1
R / W*
Value of the alarm setpoint. *Write to these registers is disabled by default
4
Setpoint 2
R / W*
5
Setpoint 3
R / W*
6
Alarm status
R
Status of alarms 1, 2 and 3 (see section 1.20).
Table 3 - Registers in ‘Process slave’ mode
and write access to these registers through the bus, see section
.
• write frames to the setpoint registers when they are dis-
abled will return error 8 ‘Read only register’.
• to save into the E2PROM the values written through the bus
into these registers, (values will be maintained incase of pow
-
er loss) enable parameter ‘E2Pr’
• after power loss, the instrument will start-up with all registers
initialized to a value of ‘0’
• the alarm status is accessible at register 6. The format of this
register is explained at section
.
1.17 Registers in ‘Full slave’ mode
Register
number
Name
Type
(R=Read, W=Write)
Description
0
Display
R / W
Register with the display value, including the decimal point and polarity.
1
Reserved
---
---
2
Reserved
---
---
3
Reserved
---
---
4
Reserved
---
5
Reserved
---
6
Alarm status
R / W
Status of alarms 1, 2 and 3 (see section 1.20).
Table 4 - Registers in ‘Full slave’ mode
List of registers accessible
for an instrument configured
in ‘Full slave’ mode.
• register 0 contains the value to show on display. It is a numerical
value, with or without polarity at the first character (‘+’ or ‘-’) and
with a single decimal point, or without decimal point.
Example 1 : send characters ‘+’ ‘7’ ‘4’ ‘.’ ‘6’ ‘1’ to read on dis
-
play ‘74.61’
Example 2 : send characters ‘-’ ‘0’ ‘4’ ‘6’ to read on display
‘-46’
• the alarm status is accessible at register 6. The format of this
register is explained at section
.
• after power loss, the instrument will start-up with all registers
initialized to a value of ‘0’
Summary of Contents for K Series
Page 32: ......