Fema Electronica B Series User Manual Download Page 14

FEMA ELECTRÓNICA . SERIES B . Models Bxx-T

14

1.13.5 Display filters

The available functions are:

•  the  ‘

Steps

’  (‘

StEP

’)  function  defines  the  reading  to  be 

done in steps of 1, 2, 5, 10, 20 or 50 counts.

Example - selecting a step of 20 configures the reading to 

change in steps of 20 counts (‘1420’, ‘1440’, ‘1460’, ...).

• the ‘

Memory of maximum

’ (‘

MAX

’) function displays the 

maximum reading value stored in memory and allows to 

reset this value. This parameter is directly accessible using 

key ‘UP’ (

5

(see section 1.13.6).

• the ‘

Memory of minimum

’ (‘

MIn

’) function displays the 

minimum reading value stored in memory and allows to 

reset this value. This parameter is directly accessible using 

key ‘UP’ (

5

(see section 1.13.6).

1.13.6 

Fast access

The ‘

fast access

’ is an operator configurable menu. The op

-

erator can access this menu with a single press of the front 

key ‘UP’ (

5

). The configured menu entries will be accessible. 

Eligible parameters to be accessed by this menu are:

• access to the alarm setpoints through the ‘UP’ (

5

) key al

-

lows to read and modify the values.
• access to the maximum and minimum alarms through the 

‘UP’ (

5

) key allows to read and reset the values. To reset 

the memory values: visualize the value on display, press the 

‘UP’ (

5

) key, when the ‘

rSt

’ message appears, press ‘SQ’ 

(

<

)

 . The instrument will return to the memory visualiza

-

tion. Press the ‘LE’ (

3

) key to exit his menu.

The ‘

fast access

’ menu is not affected by the password func

-

tion. This means that the configuration menu can be password 

blocked, while some configured functions or parameters can 

still  be  accessible  to  the  operator  through  the  ‘

fast  access

’ 

menu.

• Super fast access

If only a single function is selected for the ‘

fast access

’ menu, 

pressing the the ‘UP’ (

5

) key will shortly display the function 

name and then automatically jump to the function value. 

1.13.7 ‘on power up’ function

The ‘

On Power Up

’ (‘

on.Pu

’) functions allows to define a se

-

ries of actions to activate when the instrument restarts after 

a power loss. Functions available are a delay so the instru

-

ment waits a defined time before starting to measure and 

control, and the state of the alarms at power up. The func

-

tions will apply only after a restart due to power-loss, they 

will not apply after a restart due to changes in configuration.
Delaying the measure and control functions gives additional 

time to elements of the system who are slower, so they can 

start completely before the instrument begins to acquire sig

-

nal and control the outputs.
While on delay mode, the instrument shows all decimal points 

lightened and flashing, all alarms are deactivated, and there 

is no signal acquisition or communications control. When the 

delay time is over, the instrument starts its normal function

-

ing.

1.13.8 ‘LE’ key

The ‘LE’ (

3

) key at the front of the instrument can be config

-

ured to activate several functions. Only one function can be 

assigned to the ‘LE’ (

3

) key. Eligible functions are the alarm 

unlock function 

(see section 1.13.3).

Summary of Contents for B Series

Page 1: ...wires and thermocouple types J K T E S R N C L and X Reading configurable in C or F configurable manual offset configurable compensation of the thermocouplecoldjunction breakprobedetectionand5configur...

Page 2: ...resis manual unlocking see section 1 13 3 Display filters memory of maximum and minimum reading password protection 5 brightness levels 1 Identify the instrument format see section 1 4 2 Power and sig...

Page 3: ...11 Password configuration 16 1 13 12 Default factory configuration 16 1 13 13 Firmware version 16 1 13 14 Brightness configuration 16 1 13 15 Access to the options configuration menu 16 1 14 Factory...

Page 4: ...Power Option2 Option1 Remote keypad Signal Power Slot for option 2 Slot for option 1 Input signal terminal Remote keypad terminal C D E Cable glands B F G Panel cut out see Table 2 1 4 2 Format B44 S...

Page 5: ...1 Size A 436 mm Size B 135 mm Size C 3 mm Size D 55 mm Size E 25 mm Table 5 Sizes B26 Cut out G 418 mm 1 Cut out F 117 mm 1 Table 6 Panel cut out B26 F G Panel cut out see Table 6 1 4 4 Format B46 C D...

Page 6: ...s are independent and can be installed by accessing the internal circuits of the instrument and connecting the mod ule to the connection jumpers of the selected slot Each module is provided with a cab...

Page 7: ...al 6 The connections label attached to the outside of the in strument has some free space left to write the color or local code for each cable 7 To comply with security regulation 61010 1 add to the p...

Page 8: ...ilters steps 1 13 5 On Power Up yes 1 13 7 Alarms simple or double setpoint activation delays deactivation delays hysteresis inverted relays locked alarms 1 13 3 Memory maximum minimum 1 13 6 Password...

Page 9: ...ge en F Offset thermal drift Span thermal drift includes offset thermal drift Pt100 RTD 800 200 C 0 2 C 1562 328 F 0 05 C 0 10 C Thermocouple J 1200 200 C 2 C 2192 328 F 0 05 C 0 20 C Thermocouple K 1...

Page 10: ...y acts as an ENTER It enters into the menu option selected and when entering a numerical value it validates the num ber Key UP 5 press the UP 5 key to access the fast ac cess menu Inside the menu the...

Page 11: ...epted from 100 to 100 counts of display at the Thermoc CJC t cJc parameter activate o de activate the automatic compensation of the thermocouple cold junction When working with real thermocouples comp...

Page 12: ...delays Each alarm can configure independent activation and deactivation delays These delays affect the alarm as a whole and the delay will affect the front led and the as sociated relay Second setpoin...

Page 13: ...pply before the alarm is activated Delay starts to count once the setpoint is reached Value from 0 0 to 99 9 seconds at the Deactivation delay dEL 1 parameter config ure the delay to apply before the...

Page 14: ...t affected by the password func tion This means that the configuration menu can be password blocked while some configured functions or parameters can still be accessible to the operator through the fa...

Page 15: ...fast access menu the Setpoint2 ALr2 function allows to visualize and modify the alarm2 setpoint through the fast access menu the Setpoint3 ALr3 function allows to visualize and modify the alarm3 setpo...

Page 16: ...uments in the vicinity or to the darkness or clarity of your environment Minimum Brightness Maximum Standard The Version VEr menu informs about the firmware ver sion installed on the instrument Versio...

Page 17: ...Alpha 385 Alarms 1 2 and 3 Active off disabled Type as maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverted relay off Locked a...

Page 18: ...tpoint 2 Active Alarm type Activation delay Deactivation delay Pt100 RTD 2 wires Pt100 RTD 3 wires Thermocouple J Thermocouple K Thermocouple T Thermocouple E Thermocouple S Thermocouple R Thermocoupl...

Page 19: ...n Power Up Delay Seconds Alarm 1 Alarm 2 Alarm 3 Password Firmwareversion Factory configuration Key LE Alarm unlock No function Option 1 Access to the optional module installed at slot1 Option 2 Acces...

Page 20: ...ion see the IPB ac cessories at section 3 Side fixations Fixation screws Diameter 4 5mm 30mm between hole centers Figure 11 Hanging mount Diameter 4 5mm 30mm between hole centers Side fixations Fixati...

Page 21: ...period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse ac cident or manipulation by non authorized personnel In case of malfunction get in contact with your local p...

Page 22: ...35 Vdc Max current 50 mA Isolation 3500 Veff optoisolated Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The T1 module provides 1 transistor output to install in...

Page 23: ...on 1 6 on how to install output and control modules For more information http fema es docs 4326_SERIES B_OPTIONS_manual_i pdf 2 3 Module SSR The SSR module provides 1 output for SSR relay control to i...

Page 24: ...output and control modules Protocol Modbus RTU Bus RS 485 up to 57 6 Kbps Isolation 1000 Vdc Terminal plug in screw clamp pitch 5 08 mm Installation allowed at slot1 slot2 slot3 The RTU module provid...

Page 25: ...um Configuration is performed from the front keypad of the in strument by accessing the menu entries Opt 1 Opt 2 or Opt 3 according to the slot where the module is installed Modules S2 can be provided...

Page 26: ...IPB accessories provide IP65 protection to the panel junction Includes 4 accessories for B24 formats JPG 3 3 IPB26 The IPB accessories provide IP65 protection to the panel junction Includes 6 accessor...

Page 27: ...FEMA ELECTR NICA SERIES B Models Bxx T 27 3 6 Output cable 2 meters of cable output power remote keypad signal JPG...

Page 28: ......

Reviews: