9.- MODEL 95 .- RANGES, JUMPERS, CONNECTIONS

The CCT converter can be configured in order to adequate the input and output signal ranges to the final application.2 Wire
measuring technique. Does not apply automatic compensation of the measure wire resistances. Maximum admisible  resistance
is 1 MOhm

RANGE

0/200 Ohms

0/2KOhms

0/20 KOhms

0/200 KOhms

MP Jumpers Closed

5

6

7

None

ME Jumpers Closed

A,B,C OPEN

Minimum Input Span

10% of Full Scale used

Minimum Input Span.- Minimum range at input in order to have a maximum output range in 0/10 Vdc
or 4/20 mA.

7.- MODEL 20 .- RANGES, JUMPERS, CONNECTIONS

The CCT converter can be configured in order to adequate the input and output signal ranges to the final application. For
thermorresitance PT100 / RTD signals, according to DIN 43760, for 2 and 3 wires techniques.

RANGE

0/100ºC

0/200 ºC

0/300ºC

0/400ºC

0/500ºC

0/600ºC

ME Jumpers Closed

B

C

C

Ninguno

Ninguno

Ninguno

Minimum Input Span

50ºC

50ºC

50ºC

50ºC

50ºC

50ºC

Current through Sensor

<  1mA

Sensor Break Detection

Output signa goes lower than the minimum output signal (<4mA for example)

Minimum Input Span.- Minimum range at input in order to have a maximum output range in 0/10 Vdc or 4/20 mA.

OUTPUTS / SALIDAS
        mA          Vdc

INPUT / ENTRADA

SU

PPL

Y

 /

 A

L

IM

EN

T

A

C

IO

N

3    4    5    6

9   10   11   12

7

1

+

Lo

Hi

+

-

-

PT-100

2 wire

OUTPUTS / SALIDAS
        mA          Vdc

INPUT / ENTRADA

S

U

P

P

L

Y

 /

 A

L

IM

E

N

T

A

C

ION

3    4    5    6

9   10   11   12

7

1

+

Lo

Hi

+

-

-

PT-100

3 wire

In 2 wire technique connections
the automatic compensation of the
measure wire resistenace is not
activated.

Personalizer Module
MP-90

7 6 5

8.- MODEL 90.- RANGES, JUMPERS, CONNECTIONS

The CCT converter can be configured in order to adequate the input and output signal ranges to the final application.Accepts
potentiometric type signals. Potentiometer values between 100 Ohms and 1 MOhm. By default, units are configured at 0/100%
of the potentiometer range,aAlthough it is possible to adjust only a part ot the potentiometer range.

RANGE

0/100%

ME Jumpers Closed

A,B,C OPEN

Terminal Connections

3,4 and 5

OUTPUTS / SALIDAS
        mA          Vdc

INPUT / ENTRADA

S

U

P

P

LY

 /

 A

L

IM

E

N

TA

C

IO

N

3    4    5    6

9   10   11   12

7

1

+

Lo

Hi

+

-

-

Potentiometer

OUTPUTS / SALIDAS
        mA          Vdc

INPUT / ENTRADA

SU

PPL

Y

 /

 A

L

IM

E

N

T

A

C

IO

N

3    4    5    6

9   10   11   12

7

1

+

Lo

Hi

+

-

-

Resistencia

Summary of Contents for ASGARD CCT Series

Page 1: ...signal output low level 7 Repeat steps 6 to 9 in order to correct deviations and check adjust Weight 270gr Wire Crossection 4 mm2 maximum HousingandCover IP 40 Terminals IP 20 HousingandCover Polycarbonate Light Grey RAL 7032 UL 94 V 1 Terminals Polycarbonate Dark Grey UL 94 V 2 Mounting Standard DIN rail DIN 46277 DIN EN 50022 35 x 7 5mm 1 38 x 0 3 1 COMMON TECHNICAL SPECIFICATIONS Output 0 20mA ...

Page 2: ...SELECTION AND CONNECTIONS Instrument CCT allows outputs in voltage and current Only one of this outputs is active at the same time Is is possible to reconfigure the instrument to any of the indicated output signals below plus the 4 20 mA and 0 10 Vdc signals allowed by default Resistances in Ohms OUTPUT R18 R24 R25 0 5mA 100 0 10mA 49 9 1 5mA 100K 124 0 20mA 24 9 NOTE resistance NOT installed Resi...

Page 3: ...ak Detection Output signa goes lower than the minimum output signal 4mA for example Minimum Input Span Minimum range at input in order to have a maximum output range in 0 10 Vdc or 4 20 mA OUTPUTS SALIDAS mA Vdc INPUT ENTRADA SUPPLY ALIMENTACION 3 4 5 6 9 10 11 12 7 1 Lo Hi PT 100 2 wire OUTPUTS SALIDAS mA Vdc INPUT ENTRADA SUPPLY ALIMENTACION 3 4 5 6 9 10 11 12 7 1 Lo Hi PT 100 3 wire In 2 wire t...

Page 4: ...a and introduce the electrical noise to the unit therefore Do not install the signal input wires in the same conduit with power lines heaters solenoids SCR controls etc and always far from these elements When shielded wires are used leave unconnected the shield on the transmitter side and connect the other end of the shield to the ground terminal of the machine SAFETY CONSIDERATIONS PRESCRIPTIONS ...

Reviews: