Figure 3.3-1 Installation space of one inverter
·
Inverter cannot be installed near flammable, explosive or strong electro-
magnetic equipment.
· Please select a vertical wall with load-bearing capacity for installation, suitable for installation on
concrete or other non-flammable surfaces, installation is shown below.
· Install this inverter at eye level in order to allow the LCD display to be read at all times.
· The ambient temperature should be between -25~60℃ to ensure optimal operation.
· Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat
dissipation and have enough space for removing wires.
Lateral
Top
Bottom
500mm
450mm
450mm
Minimum clearance
Table 3-3-1 Detailed installation space
·
Do not open the cover of the inverter or replace any part as incomplete inverter
may cause electric shock and damage the device during operation.
Figure 3.3-2 Installation position
The installation of inverter should be protected under shelter from direct sunlight or badweather
like snow,rain, lightning etc.
Figure 3.3-3 Installation position
3.4 Mounting
The inverter is suitable for mounting on concrete or other non-combustible surface only.
Step 1.
Please use the mounting bracket as a template to drill 5 holes in the right positions (10mm
in diameter,and 80mm in depth). Use M8 expansion bolts in accessory box and fix the mounting
With a 12mm drill
bracket onto the wall tightly.The installation of inverter support is shown in
Figure 3.4-1.
·
The inverter is heavy, please be careful when removing it from the package.
Considering the following points before selecting where to install:
07
08
959
510
M8
Screw locking
torque 12N. m
500
500
100
0