Ordering Replacement Parts and Accessories
A replacement part for the driver/PCB assembly and accessories are listed in Tables 2 and 3. Due to certification, certain
component parts are not available for field replacement. Sounders with this type of damage must be either replaced
entirely or returned to Federal Signal for service. Refer to instruction manual 25500259 for accessory and replacement
part assembly and operating instructions. To order, call Federal Signal Customer Support at 708-534-4756 or 877-289-
3246.
Table 2 Replacement parts
Description
Part Number
Multi-voltage G-SND Sounder Kit (Includes PCBAs,
Bracket, Driver, & Mounting Screws)
K859501404
Table 3 Accessories
Description
Part Number
Indicator Ring/Legend Kit, Black
G-KIT-RP-BK
Indicator Ring/Legend Kit, Blue
G-KIT-RP-B
Indicator Ring/Legend Kit, Green
G-KIT-RP-G
Indicator Ring/Legend Kit, Magenta
G-KIT-RP-M
Indicator Ring/Legend Kit, Red
G-KIT-RP-R
Indicator Ring/Legend Kit, Yellow
G-KIT-RP-Y
E-Box Endcap with M20 Opening
K859500805-02
E-Box Endcap with M25 Opening
K859500805-01
E-Box Cover Assembly (Includes two terminal blocks,
mounting plate, retention hardware)
K859501414
In-Line E-Box Coupler Kit
G-KIT-EC180
90-Degree E-Box Coupler Kit
G-KIT-EC90
Extension Box Spacer Kit
G-KIT-EXTB
Single Trunnion Kit
G-KIT-ST
Dual Trunnion Kit
G-KIT-DT
Adapter, M20 Male to 1/2" Female NPT
K231246A
Adapter, M20 Male to 3/4" Female NPT
K231247
15 W Audible Acoustic Insert
G-KIT-15WINSERT
Table 4 Choosing cable-entry devices for equipment in potentially explosive atmospheres
Models
Ex Atmospheres Cable Entry Devices
(cable glands, stopping plugs, etc.
G-SND-XXX-D (Ex db
surface mount)
Gas
Cable entry devices shall be equipment certified as flameproof. To
maintain the ingress protection of the flameproof sounder enclosure, we
recommend the cable entry device be IP66 certified.
G-SND-XXX-E
Gas
For the flameproof enclosure, cable entry devices shall be equipment
certified as flameproof. To maintain the ingress protection of the
flameproof enclosure, we recommend the cable entry device be IP66
certified. For the increased safety terminal enclosures (terminal boxes),
cable entry devices shall be equipment certified as increased safety and
shall maintain an IP rating of IP54.
G-SND-XXX-D (Ex db
surface mount)
G-SND-XXX-E (Ex db e
surface mount)
Dust
Cable entry devices for the and terminal enclosures shall be equipment
certified as dust protected. To maintain the ingress protection of the
sounder and terminal enclosures, the cable entry devices shall be IP6X
certified.