Model G-SND 

Sounder for Use in Hazardous 

Locations

Limited Warranty: 

This product’s limited warranty can be found at www.fedsig.com/SSG-Warranty. 

WARNING

 - Failure to follow all safety precautions and instructions may result in property damage, serious injury, or 

death to you or others.

MESSAGES TO INSTALLERS AND USERS

   People’s lives depend on your safe installation of our products. It is 

important to follow all instructions shipped with the products. This device is to be installed by a trained electrician who 

is thoroughly familiar with the National Electric Code and will follow the NEC guidelines as well as local codes.

The selection of the mounting location for the device, its controls and routing of the wiring is to be accomplished 

under the direction of the Facilities Engineer and the Safety Engineer. Listed below are some other important safety 

instructions and precautions you should follow.

• 

Read and understand instructions before installing or operating equipment.

• 

Do not connect this unit to the system when power is on.

• 

All effective warning speakers produce loud sounds, which may cause, in certain situations, permanent hearing 

loss. You should take appropriate precautions, such as wearing hearing protection.

• 

After installation, test the sound system to ensure proper operation.

• 

All effective warning speakers produce loud sounds, which may cause, in certain situations, permanent hearing 

loss. The device should be installed far enough away from potential listeners to limit their exposure while still 

maintaining its effectiveness.

• 

The OSHA Code of Federal Regulations 1910.95 Noise Standard provides guidelines which may be used regarding 

permissible noise exposure levels.

• 

Show these instructions to your Safety Engineer and then file them in a safe place and refer to them when 

maintaining and/or reinstalling the unit.

• 

After installation and completion of the initial system test, a program of periodic testing of this device must be 

established. Refer to NFPA 72G, local Fire Codes and the authority having jurisdiction for this information.

• 

Consult the authority having jurisdiction in your area regarding the proper use and installation of this product.

SHOCK HAZARD - 

To avoid electrical shock hazards, do not connect wires when power is applied.

Certification

Certificate Nos.

ATEX Cert No.: Baseefa15ATEX0155X  

IECEx Cert No.: IECEx BAS 15.0104X

ATEX coding:   II 2 G D

Protection

Ex db IIB T5 Gb or Ex db e IIB T5 Gb

Ex tb IIIC T100°C Db IP66 (Tamb= -55°C to + 49°C)

Ex db IIC T4 Gb or Ex db e IIC T4 Gb

Ex tb IIIC T135°C Db IP66 (Tamb= -55°C to + 70°C)

Standards

EN60079-0: 2012 +A11:2013, EN60079-1: 2014,

EN60079-7: 2007, EN60079-31: 2014, IEC60079-0: 6th Ed.,

IEC 60079-1:7th Ed., IEC 60079-7: 4th Ed.,

IEC 60079-31:2nd Ed.

255000187 Rev B8 0122

Summary of Contents for G-SND

Page 1: ...to ensure proper operation All effective warning speakers produce loud sounds which may cause in certain situations permanent hearing loss The device should be installed far enough away from potential...

Page 2: ...reference to risks to life and property and for conformity to the installation and use in provisions of Articles 505 and 506 of NFPA 70 NEC These models use protections Class I Zone 1 AEx db IIC T4 Gb...

Page 3: ...oduct is Ex db e marked it uses the increased safety terminal enclosures and is only for gas atmospheres If the product is Ex tb marked it is for installation in dust atmospheres Mounting the G SND So...

Page 4: ...suitable for the surface to which the device will be mounted Figure 4 Front view of Ex d e surface mount 2X 8 5 mm 103 2 mm 4 06 in 122 6 mm 4 83 in 3X M20 GLAND ENTRIES 4X COUNTER BORED HOLES TO FIT...

Page 5: ...in the unit are not too slack In all countries the wiring must comply with all national and local codes and standards Ensure that all nuts bolts and fixings are secure Preparing to Wire the Ex d Flame...

Page 6: ...he terminals clear the housing Strip the wire insulation 6 5 mm 0 25 in Maximum screw tightening torque is 0 5 N m 4 5 in lb 5 Follow the instructions starting below for your line voltage and continue...

Page 7: ...the common wire from the remote switching device to the terminal block position marked SEL g Connect the tone select wires from the remote switching device to the terminal block positions marked T1 T...

Page 8: ...he side of the housing until the screw contacts the housing 9 Ensure that the unused wire entry is sealed with the provided brass M20 1 5 x 6 g stopping plug equipment certified Table 1 Tone chart Ton...

Page 9: ...ion shall extend to within 1 mm of the metal of the terminal throat The G SND terminal block is supplied with two conductors per pole The terminal block allows for easy supply in and loop out wiring t...

Page 10: ...tching of tones a Connect the line hot power source wire to the position marked L1 on the terminal block b Connect the neutral common power source wire to the position marked L2 on the terminal block...

Page 11: ...ly seated against the housing when the threads are tightened Turn the M3 set screw on the side of the housing until the screw contacts the housing Safety Messages to Maintenance Personnel Listed below...

Page 12: ...allation and do not change the factory applied finish Ordering Replacement Parts and Accessories A replacement part for the driver PCB assembly and accessories are listed in Tables 2 and 3 Due to cert...

Page 13: ...IP6X certified Table 5 Remote tone selection Terminal Wiring Tone HEX SW SEL1 T4 T3 T2 T1 0 1 1 X X 2 2 X X 3 3 X X X 4 4 X X 5 5 X X X 6 6 X X X 7 7 X X X X 8 8 X X 9 9 X X X 10 A X X X 11 B X X X X...

Page 14: ...t or provide technical assistance with any problems that cannot be handled locally Technical Assistance Contact our Technical Support Team at 1 708 587 3587 or signalsupport fedsig com Repair Service...

Page 15: ...t signaling fedsig com Traducciones adicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 755 7621 1 708 587 3587...

Page 16: ...dicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 755 7621 1 708 587 3587 signalsupport fedsig com signaling fe...

Page 17: ...ertencia efectiva producen sonidos fuertes que pueden ocasionar en ciertas situaciones la p rdida permanente de la audici n El dispositivo debe ser instalado a una distancia suficiente de las personas...

Page 18: ...s de zona cULus Este equipo se utiliza en zonas peligrosas de Clase I Zona 1 y Zona 21 ubicaciones clasificadas Se ha investigado con referencia a riesgos para la vida y propiedad y para la conformida...

Page 19: ...Ex db solamente su uso est previsto en atm sferas con gases Si el producto tiene la marca Ex db e utiliza gabinetes de terminales de mayor seguridad y su uso est previsto solamente en atm sferas con...

Page 20: ...en superficie Monte el generador de sonido a una superficie plana usando los seis orificios de montaje de 8 5 mm Use los sujetadores proporcionados por el instalador que sean aptos para la superficie...

Page 21: ...elve a montar la unidad No se permite el uso de pinturas y acabados de superficie que no sean los aplicados por Federal Signal Corporation La terminaci n de los cables debe ajustarse a las especificac...

Page 22: ...la conexi n principal a tierra masa debe ser igual a la secci n transversal del conductor de fase Para estos modelos la terminaci n de los cables debe ajustarse a las especificaciones que correspondan...

Page 23: ...mentaci n a la posici n del bloque de terminales marcada con la leyenda L2 en la placa de circuito impreso e Conecte el cable de tierra a la posici n del bloque de terminales marcada con la leyenda EA...

Page 24: ...n la leyenda EARTH f Conecte el cable com n del dispositivo selector remoto a la posici n del bloque de terminales marcada con la leyenda SEL g Conecte los cables de selecci n de tono del dispositivo...

Page 25: ...00 Hz constante 700 Hz 700 Hz 5 5 Campanilla Aprox 3 ta idos por s 6 6 Barrido 0 6 kHz to 1 2 kHz 1 2 kHz to 2 6 kHz 6 ciclos por s 7 7 Dos tonos 1 kHz 700 Hz 0 4 s 0 4 s 8 8 700 Hz 700 Hz Silencio 0...

Page 26: ...o de los modelos Ex de DA OS A LA PLACA DE CIRCUITOS Los generadores de sonido de CC son sensibles a la polaridad y PUEDEN DA ARSE por una conexi n el ctrica incorrecta Al conectar el generador de son...

Page 27: ...cada con la leyenda L1 en el bloque de terminales b Conecte el cable neutro com n de la fuente de alimentaci n a la posici n marcada con la leyenda L2 en el bloque de terminales c Conecte el cable de...

Page 28: ...to impreso 6 Coloque la cubierta sobre la carcasa y aj stela haci ndola girar en el sentido de las agujas del reloj 7 Para garantizar la compresi n de la junta t rica la cubierta debe asentarse por co...

Page 29: ...do Limpieza del gabinete El gabinete debe limpiarse peri dicamente con un pa o h medo para mantener la m xima intensidad de sonido Deben realizarse comprobaciones peri dicas para asegurarse de que la...

Page 30: ...i n de dispositivos de entrada de cables para equipos en atm sferas potencialmente explosivas Modelos Atm sferas explosivas Dispositivos de entrada de cables prensaestopas tapones de tope etc G SND XX...

Page 31: ...Vca a 33 Vca NOTA UL solo evalu este producto para el rango de voltaje operativo indicado No se evalu entre el 80 y el 110 del rango de voltaje El generador de sonido viene configurado de f brica con...

Page 32: ...a se reparar n o reemplazar n a criterio de Federal Signal Devoluciones de productos las devoluciones requieren autorizaci n de Federal Signal P ngase en contacto con su distribuidor autorizado para...

Page 33: ...s puissants qui peuvent entra ner dans certaines situations une perte permanente de l ou e Le dispositif doit tre install suffisamment loin des auditeurs potentiels afin de limiter l exposition de ces...

Page 34: ...ertifications de zones cULus Cet quipement est destin tre utilis dans des emplacements dangereux class s de classe I zone 1 et zone 21 Il a t tudi en r f rence aux risques pour la vie et les biens et...

Page 35: ...on d installations combin es Remarque sur les installations combin es Si le produit est marqu Ex db uniquement il est destin tre utilis dans des atmosph res de gaz Si le produit est marqu Ex db e il u...

Page 36: ...ace du r sonateur Ex d 4 ORIFICES LAM S POUR S ADAPTER AUX VIS D ASSEMBLAGE SIX PANS CREUSES M8 105 9 mm 4 17 po 133 8 mm 5 27 po 105 9 mm 4 17 po Installation du r sonateur avec montage en saillie Ex...

Page 37: ...TOUPES M20 4 ORIFICES LAM S POUR S ADAPTER AUX VIS D ASSEMBLAGE SIX PANS CREUSES M8 105 9 mm 4 17 po 23 2 mm 0 91 po 103 2 mm 4 06 po 122 6 mm 4 83 po Illustration 5 Vue de c t du Ex de avec montage e...

Page 38: ...il ne sont pas trop l ches Dans tous les pays le c blage doit tre conforme l ensemble des codes et normes nationaux et locaux Assurez vous que tous les crous boulons et l ments de fixation sont bien m...

Page 39: ...le circuit imprim en le faisant glisser jusqu ce que les bornes se d gagent du bo tier Retirez 6 5 mm 0 25 po d isolant Couple de serrage de la visserie maximum de 0 5 N m 4 5 po lb 5 Suivez les inst...

Page 40: ...ment en 220 240 V c a commutation des tonalit s distance possible a R glez les commutateurs de s lection de tension sur 230 et CA b R glez le commutateur de s lection de tonalit sur 0 c Raccordez le f...

Page 41: ...onnement en 24 V c c commutation des tonalit s distance possible l aide d un syst me d alimentation distance a R glez le commutateur de s lection de tonalit sur 0 b Raccordez le c ble d alimentation n...

Page 42: ...s de fils si le dispositif est sous tension Le non respect de cet avertissement peut entra ner des blessures graves ou la mort Cette partie fournit des consignes de c blage pour les trois mod les s cu...

Page 43: ...ferrule de lacet sertie isol e 3 Pour connecter les c bles appuyez sur le bouton poussoir du bornier avec un tournevis Phillips et ins rez le c ble dans l ouverture circulaire Rel chez le bouton pouss...

Page 44: ...utation distance aux positions du bornier marqu es Alt03 et Alt04 Sur les appareils Ex de 120 V c a seules deux tonalit s sont s lectionnables distance Fonctionnement en 24 V c c commutation des tonal...

Page 45: ...amais cet appareil de quelque fa on que ce soit La s curit peut tre compromise si d autres ouvertures sont ajout es ou si d autres modifications sont apport es aux composants internes ou au coffret La...

Page 46: ...hange Description Num ro de pi ce Kit de r sonateur G SND multi tension comprend les ensembles de cartes de circuits imprim s le support le moteur et les vis de montage K859501404 Tableau 3 Accessoire...

Page 47: ...db G SND XXX E Montage en saillie Ex db e Dust Les dispositifs d entr e de c bles pour le hautparleur et les bo tiers de bornes doivent tre certifi s comme prot g s contre la poussi re Afin de conserv...

Page 48: ...ien Ne peignez pas cet appareil apr s son installation et ne modifiez pas la finition appliqu e en usine Assistance technique Contactez notre quipe d assistance technique au 1 708 587 3587 ou l adress...