Installation and Maintenance Instructions

Model 450E Electronic Horn

Wiring the Horn

SHOCK HAZARD — To avoid electrical shock hazards, do not 

connect wires when power is applied.

 Failure to heed this 

warning may cause serious injury or death.

WIRING PRECAUTION — An uninsulated section of a single 

conductor must NOT be looped around a terminal and used 

as two separate connections. NFPA 72 requires that the wire 

is severed to provide electrical supervision of the connection 

if the wire becomes dislodged from under the terminal. 

Failure to sever the wire may render the horn inoperable, 

causing serious injury or death.

WIRING PRECAUTION — National Electrical Codes as well 

as local codes must be adhered to in the installation of the 

Model 450E horn. All electrical wiring must be routed through 

approved conduit and fittings as specified. Failure to heed 

this warning may cause an electrical shock or render the horn 

inoperable, causing serious injury or death.

WIRING PRECAUTION — Refer to NFPA 70 and NFPA 72 

(NEC) and CSA C22.1 Canadian Electrical Code, Part 1, Safety 

Standard for Electrical Installation, Section 32. Failure to heed 

this warning may cause an electrical shock or render the horn 

inoperable, causing serious injury or death.

For power connections, use only wire sized 12 AWG to 18 AWG 

(2.5 mm

2

 to 1.0 mm

2

). Strip no more than 0.25

"

 (6 mm) of 

insulation from the ends of the power wires. Torque the terminal 

screws to 4.5 in-lb (0.51 Nm) maximum.

Summary of Contents for 450E

Page 1: ...25500096 Rev A3 0814 Printed in U S A Model 450E Electronic Horn Installation and Maintenance Instructions fran ais page 15 espa ol p gina 29...

Page 2: ...Industrial Systems 2645 Federal Signal Drive University Park IL 60484 3167 Tel 708 534 4756 Fax 708 534 4852 Email elp federalsignal com www federalsignal indust com...

Page 3: ...unting 10 Weatherproof Panel Mounting 11 Getting Repair Service or Technical Assistance 12 Returning the Product for Credit 12 Tables Table 1 Specifications 7 Figures Figure 1 Dimensions for panel mou...

Page 4: ...7 mm TYP 3 3 8 85 7 mm TYP 3 5 8 92 1 mm TYP 1 13 16 46 mm TYP 4 3 16 4 8 mm 1 11 16 42 9 mm TYP 45 0 TYP OUTLINE OF CLEARANCE HOLE FOR DEVICE 2013 Federal Signal Corporation All rights reserved Figu...

Page 5: ...n listed below are some other important safety instructions and precautions you should follow Read and understand all instructions before installing operating or maintaining this equipment Do not conn...

Page 6: ...may have occurred in transit If the horn has been damaged do not attempt to install or operate it File a claim immediately with the carrier stating the extent of the damage Carefully check all envelop...

Page 7: ...ox used When used with the weatherproof Model WB back box it meets Type 4X and IP66 requirements Table 1 Specifications Operating Voltage Fire Alarm Use Regulated 24 Vdc 16 33 Vdc General Signaling Us...

Page 8: ...ING PRECAUTION National Electrical Codes as well as local codes must be adhered to in the installation of the Model 450E horn All electrical wiring must be routed through approved conduit and fittings...

Page 9: ...E This device is polarized by a diode for use in supervised systems Refer to local fire alarm codes if an End of Line Device is necessary Figure 3 Wiring connections Vdc POWER END OF LINE DEVICE RECOM...

Page 10: ...6 in lb 1 8 Nm Use the two remaining 8 32 screws and Keps nuts to cover the two unused holes in the horn grille Figure 4 Non weatherproof mounting 290A7585 8 32 KEPS NUT 2 8 32 x 1 5 8 4 Weatherproof...

Page 11: ...e must be flat and smooth and all four screws must be used To panel mount the horn 1 Detach the template page 4 and place it against the mounting surface 2 Mark the locations of the four mounting hole...

Page 12: ...assistance from Federal Signal call 708 534 4756 or 877 289 3246 For instruction manuals and information on related products visit www federalsignal indust com Industrial Systems www fs isys com Inte...

Page 13: ...not been previously repaired The product is a standard product The product is not a service part All returns are subject to a re stock fee Defective products that are returned within the warranty per...

Page 14: ...14 Industrial Systems 2645 Federal Signal Drive University Park IL 60484 3167 Tel 708 534 4756 Fax 708 534 4852 Email elp federalsignal com www federalsignal indust com...

Reviews: