background image

INSTALLATION AND SERVICE INSTRUCTIONS FOR MODEL 154XST STROBE LIGHT 

FOR USE IN HARSH ENVIRONMENTS/HAZARDOUS LOCATIONS

SAFETY MESSAGE TO INSTALLERS, USERS AND MAINTENANCE PERSONNEL

It is important to follow all instructions shipped with this product. This device is to be installed by a 
trained electrician who is thoroughly familiar with the National Electrical Code and will follow the 
NEC Guidelines as well as local codes.
The selection of the mounting location for the device, its controls and the routing of the wiring is to 
be accomplished under the direction of the facilities engineer and the safety engineer. In addition, 
listed below are some other important safety instructions and precautions you should follow:
• Read and understand all instructions before installing or operating this equipment.
• Do not connect this light to the system when power is on.
• After installation, ensure that the set screw is properly tightened and that threaded joints are fully 

engaged.

• After installation, test the light system to ensure that it is operating properly.
• After testing is complete, provide a copy of this instruction sheet to all operating personnel.
• Establish a procedure to routinely check the light installation for integrity and proper operation.
Failure to follow all safety precautions and instructions may result in property damage, serious 
injury, or death to you or others.

I. GENERAL.

The Model 154XST Strobe Light is a UL listed visual signal for hazardous and marine locations 
and has been investigated by UL as meeting Type 4X (water tight and corrosion resistant) enclo-
sure requirements. It provides about 80 high-intensity flashes per minute. The effective candle-
power (ECP) of the light is 165 with a clear globe installed. The unit is available for 12 through 
24VDC.

II. INSTALLATION.

A. Unpacking.

WARNING

Damaged globes can lead to explosions which could result in serious injury or death.

After unpacking the Model 154XST, examine it for damage that may have occurred in transit. If 
the equipment has been damaged, do not attempt to install or operate it, file a claim immediately 
with the carrier stating the extent of the damage. Carefully check all envelopes, shipping labels 
and tags before removing or destroying them.

B. Mounting.

CAUTION

To reduce the risk of fire or explosion, do not install in a hazardous location if the operating tempera-

ture (see table 1) exceeds the hazardous atmosphere’s ignition temperature.

Before proceeding, use table 1 as a guide and determine that the unit’s operating temperature 
DOES NOT exceed the hazardous atmosphere’s ignition temperature.
For marine applications, all wiring including supply wire must be stranded wire and meet the 
USCG (CFR46) Sections (110-113).
The Model 154XST has provisions for mounting to 3/4" pipe and may be mounted in any 
position. Before mounting, ensure that mating threads are clean. To prevent the ingress of water 
and dust, apply conductive sealant to the conduit threads prior to mounting. If non-conductive 
sealant is used, the enclosure must be earthed via the provided internal grounding wire/ground-
ing screw to ensure proper grounding continuity. In high-humidity environments when units are 

-1-