FEC Remote Lighting Controller V4 HP0832
User Installation and Operation Manual
© Interleader Ltd 2020
40 of 64
26/08/2020
8.11 Test
Of the menu options, Managers can access:
•
Test Relays, and
•
Display (Bluetooth) Signal Strength.
Check RTC Oscillator
Only available to OEM for testing and setting up.
Calibrate RTC
Only available to OEM for testing and setting up.
Test Relays
All of the RLCs can be tested.
Relays 1 to 3 have their coil currents measured and reported.
A figure of 100 +/- 15mA is acceptable. Readings outside of this
should be investigated and reported.
For technical reasons neither the Winsock nor Beacon relays have
their coil currents measured.
Display Signal Strength
An assessment of the performance of the Bluetooth radio link
can be made.
Note that this is the signal strength measured at the time of
connection.