When working with products which are in contact to dangerous electrical voltages, attention must
be payed to the relevant valid VDE / IEC / EN regulations. Especialy with refrence to the following
rules:
VDE 0100, VDE 0550 / 0551, VDE 0711, VDE 0860, IEC 664, IEC 742, IEC 570, IEC 65
In case of non-observance of this instructions, the unit or other equipment might be damaged
and no warranty or liability could be accepted.
When it is necessary to use tools with the units, components parts or subassemblies make it
sure, that the power is disconnected from the units and all electric charge which is stored in
components inside the unit are discharged.
Before opening the equipment disconnect the power cord or make sure, that the power is off
and the unit is currentless. It is only allowed to set components parts, subassemblies or units
into operation, if they are mounted in a shockproof housing. During the installation the unit
has to be currentless and the power has to be off.
Lifeparts (power cords and leads) which are connected to the units, components or
subassemblies have to be inspected for damage insulation or breaking. If a failure at the
power cord is detected the unit or the subassembly has to be put out of service at once. It is not
allowed to reopen the unit or the subassembly before replacing the damaged power cord.
It is the user’s responsibility to see that the marginal values of the equipment are not exeeded.
If it is not to distinguished for the not industrial ultimate user by the presented operating
instruction, which electrical data are the correct for the unit or the subassembly, a technical
adviser has always to be asked for technical information.
The observance of construction requirements and safety rules (VDE, IEC, employers liability
insurenance i.e.) is subject to the user/customer.
Beim Umgang mit Produkten, die mit elektrischen Spannungen in Berührung kommen, müssen die
gültigen VDE / IEC / EN Vorschriften beachtet werden. Besonders sei auf folgende Vorschriften
hingewiesen:
VDE 0100, VDE 0550 / 0551, VDE 0711, VDE 0860, IEC 664, IEC 742, IEC 570, IEC 65
Bei Nichtbeachtung der Bedienungsanleitung oder der Anschlußvorschrift, z.B. bei
Vertauschen der Anschlußklemmen, kann das Gerät oder die Anlage beschädigt werden und
der Betreiber verliert seinen möglichen Haftungsanspruch.
Werkzeuge dürfen an Geräten, Bauteilen oder Baugruppen nur benutzt werden, wenn
s i c h e r g e s t e l l t i s t , d a ß d i e G e r ä t e v o n d e r Ve r s o r g u n g s s pa n n u n g g e t r e n n t
sind und elektrische Ladungen die in im Gerät befindlichen Bauteile gespeichert
sind, vorher entladen wurden.
Vor dem Öffnen des Gerätes den Netzstecker ziehen oder sicherstellen, daß das Gerät
stromlos ist. Bauteile, Baugruppen oder Geräte dürfen nur in Betrieb genommen werden,
wenn sie vorher in ein berührungssicheres Gehäuse eingebaut wurden. Während des
Einbaus müssen sie stromlos sein.
Spannungsführende Kabel oder Leitungen mit denen das Gerät, das Bauteil oder die
Baugruppe verbunden sind müssen stets auf Isolationsfehler oder Bruchstellen untersucht
werden. Bei Feststellen eines Fehlers in der Zuleitung muß das Gerät unverzüglich aus dem
Verkehr genommen werden, bis die defekte Leitung ausgewechselt worden ist.
Der Anwender hat dafür Sorge zu tragen, daß die angegebenen Gerätedaten nicht
überschritten werden.
Wenn aus den vorgelegten Beschreibungen für den Anwender oder Erwerber nicht eindeutig
hervorgeht, welche Kennwerte für ein Gerät oder Bauteil gelten, so muß stets ein Fachmann
um Auskunft ersucht werden.
Im übrigen unterliegt die Einhaltung von Bau- und Sicherheitsvorschriften aller Art ( VDE, TÜV,
Berufsgenossenschaften ) dem Anwender / Käufer.
Allgemeine Sicherheitsvorschriften :
General safety rules :
- konform
Betriebsanleitung
Bitte sorgfältig beachten!
Operating instructions
Please observe carefully!
PSU90 / 100
PSU140 / 160
Anschlußschema 115V/230V / Cable arrangement 115V/230V
Laststromdiagramm / Load-current diagram
0
0
10
2
4
6
8
5
10
15
20
25
30
yp 4V
T
2
24V
12V
Ty 12
p V
Volt DC
Amp.
Ausgangsstrom / Output current
A
u
s
g
a
n
g
s
s
p
a
n
n
u
n
g
/
O
u
tp
u
t
v
o
lt
a
g
e
Eingangsspannungstoleranz
Frequenz
Verbrauch
PSU90 / 100 / 140 / 160
Eingangsstrom PSU90 / 100 / 140 / 160
Ausgangsgrößen
Ausgangsspannungen U
NENN
Ausgangsstrom I
NENN
Restwelligkeit
Betriebsdaten
Einschaltdauer (ED)
Arbeitstemperatur
Temperaturkoeffizient
Lagertemperaturbereich
Wirkungsgrad
Kühlung
Schutzeinrichtungen
Vorsicherung PSU90 / 100 / 140 / 160
Ausgangssicherung
Überlastschutz
Netzausfallüberbrückung
MTBF
Sicherheitsdaten
Prüfspannung Trafo
Hochspannungsfestigkeit
Luft- und Kriechstrecken
Funkenentstörgrad
Anwendungsklasse
Umgebungsfeuchte
Schutzart Gehäuse
Schutzart Klemmen
Rüttelfestigkeit
Angewandte Bauvorschriften
gemäß VDE
IEC
EN
CSA / UL
Mechanik
Befestigung
Maße PSU90
PSU100
PSU140
PSU160
Maße
Maße
Maße
Gewicht PSU90 / 100 / 140 / 160
Eingangsspannung
siehe Gehäuseaufdruck des Gerätes
+15% und -15%
45 - 66 Hz
max. 65VA / 105 VA / 140VA / 175VA
max. 0,3A / 0,5A / 0,65A / 0,8A
siehe Gehäuseaufdruck des Gerätes
siehe Gehäuseaufdruck des Gerätes
< 3%
100%
-40°C bis +70°C
< 500ppm / K
-40°C...+105°C
ca. 87%
natürliche Konvektion (S)
5,0Amp. träge
nicht erforderlich da kurzschlußfest
20 mSek. typ.
> 400.000 h
5 kVac gemäß VDE 0551
Eingang / Ausgang 3,75 kVac
nach VDE 0806 / IEC 380
Primärkreis - Sekundärkreis >8mm
nach VDE 0110
< K nach VDE 0871 und EN 55022/B
KSE nach DIN 40040
95% relative Feuchte im Jahresdurchschnitt
Betauung möglich - tropentauglich
IP 65
IP 20 (VGB4)
>30g bei 33Hz in X, Y und Z,
nach IEC 68 und DIN 41640
VDE 0100, 0110, 0113, 0551, 0160, 804-8
IEC 380, 742, 950
EN 60950, EN50081, EN50082
CSA 22.2 / UL1012
Auf Schiene nach DIN 46277
47mm x 99mm x 118mm BxHxT)
64mm x 99mm x 118mm (BxHxT)
79mm x 99mm x 118mm (BxHxT)
94mm x 99mm x 118mm (BxHxT)
ca. 1,3kg / 1,85kg / 2,35kg / 2,85kg
Input voltage
Consumption PSU100 / 140 / 160
Input current PSU90 / 100 / 140 / 160
Output data
Output voltage U
NOMINAL
Output current I
NOMINAL
Residual ripple
Operating data
Duty circle
Operating temperature
Temperature coefficient
Efficiency
Cooling
Safety devices
Output fuse
Overload protection
Hold-up time
MTBF
Safety data
Test voltage transformer
High-voltage resistance
Air gaps and leakage paths
Degree of EMI suppression
Class of application
Ambient humidity
Protective class enclosure
Protective class terminals
Vibration proof
Applied construction regulations
according to VDE
IEC
EN
CSA / UL
Mechanics
Mounting
Dimensions PSU90
PSU100
PSU140
PSU160
Dimensions
Dimensions
Dimensions
Weight PSU90 / 100 / 140 / 160
Eingangsgrößen
Input data
Input voltage tolerance
Frequency
Storage temperature range
Fuse for input PSU90 / 100 / 140 / 160
Technische Daten
Technical Data
im Gerät integriert
Die Geräte sind für sinusförmige Eingangsspannungen ausgelegt.
Ausgang Potentialfrei nach VDE 0551
Technische Daten siehe Tabelle rechts.
see face plate
+15% and -15%
45 - 66Hz
max. 65VA / 105 VA / 140VA / 175VA
max. 0,3A / 0,5A / 0,65A / 0,8A
EN 60950, EN50081, EN50082
see face plate
see face plate
< 3%
100%
-40°C to +70°C
< 500 ppm / K
-40°C...+105°C
ca. 87%
selfcooling (S)
5,0 Amp. delayed
not necessary - cont. short-circuit proof
20 msec. typical
> 400.000 h
5 kVac in accordance to VDE 0551
Primary circuit - secondary circuit 3,75 kVac
acc. to VDE 0806 / IEC 380
Primary circuit - secondary circuit >8mm
acc. to VDE 0110
< K in acc. to VDE 0871 and EN 55022/B
KSE according to DIN 40040
95% rel. humidity, yearly average dewing
allowed for use in tropical ambient
IP 65
IP 20 (VGB4)
>30g at 33Hz in X, Y and Z,
acc. to IEC 68 and DIN 41640
VDE 0100, 0110, 0113, 0551, 0160, 804-8
IEC 380, 742, 950
CSA 22.2 / UL1012
on rails acc. to DIN 46277
47mm x 99mm x 118mm (W x H x D)
64mm x 99mm x 118mm (W x H x D)
79mm x 99mm x 118mm (W x H x D)
94mm x 99mm x 118mm (W x H x D)
ca. 1,3kg / 1,85kg / 2,35kg / 2,85kg
integrated into device
Die Geräte vom Typ PSU100 / 140 / 160 sind anschlußfertige,
ungeregelte Netzgeräte.
Tropentauglich - Gießharzvollverguß
Die grüne LED signalisiert den Betrieb des Gerätes.
Kurzschlußfest, leerlauf- und überlastsicher
Die Geräte eignen sich zur Montage auf 35mm Hutprofil-
schienen
. Befestigungsalternativen siehe
R ckseite dieser Bedienungsanleitung.
gemäß DIN 46277
ü
The power supplies are suitable to be fitted on 35mm rail
. Mounting alternatives are shown on backpage.
acc. to DIN 46277
The correct operation of the unit is indicated by the green LED.
Short- circuit proof, no-load and overload safe
Suitable for the tropics - Epoxy resin casted
Output separated according to VDE 0551
The units are constructed for sinus-oidal input voltage.
The power supply units of the series PSU100 / 140 / 160 are
ready for installation on delivery.
Technical data see table on the right side.
Vorsicherung
PS1U90 / 100 / 140 / 160
Vorsicherung
PS2U100 / 140 / 160
8,0 Amp. träge
2,0 Amp. träge
Fuse for input
PS1U90 / 100 / 140 / 160
Fuse for input
PS2U100 / 140 / 160
8,0 Amp. delayed
2,0 Amp. delayed
GmbH
Postfach 1521
D - 22905 AHRENSBURG
Telefon: 04102 - 42082
Telefax: 04102 - 40930
www.feas.de
© 2004
®
Eingangsstrom
PS1U90 / 100 / 140 / 160
Eingangsstrom
PS2U100 / 140 / 160
max. 0,6A / 1,0A / 1,25A / 1,6A
max. 0,3A / 0,4A / 0,5A
Input current
PS1U90 / 100 / 140 / 160
Input current
PS2U100 / 140 / 160
max. 0,6A / 1,0A / 1,25A / 1,6A
max. 0,3A / 0,4A / 0,5A
PS2U100
Netzspannung
line-voltage
PS2U100 - 400 V~
+
-
Verbraucher
consumer
L1
PE
L2
PSU100 / PS1U100
+
-
Verbraucher
consumer
Netzspannung
line-voltage
PSU100 - 230 V~
PS1U100 - 115 V~
L1
PE
N
PSU140 / PS1U140
+
-
Verbraucher
consumer
Netzspannung
line-voltage
PSU140 - 230 V~
PS1U140 - 115 V~
L1
PE
N
PS2U140
+
-
Verbraucher
consumer
Netzspannung
line-voltage
PS2U140 - 400 V~
L1
PE
L2
PSU160 / PS1U160
PS2U160
Netzspannung
line-voltage
PS2U160 - 400 V~
+
-
Verbraucher
consumer
L1
PE
L2
0
0
6
12
5
10
15
20
25
30
Typ 24V
24V
12V
y
T p 12V
PSU160
Volt DC
Amp.
Ausgangsstrom / Output current
A
u
s
g
a
n
g
s
s
p
a
n
n
u
n
g
/
O
u
tp
u
t
v
o
lt
a
g
e
bei nominaler Eingangsspannung
at nominal input voltage
3
9
PSU100
bei nominaler Eingangsspannung
at nominal input voltage
15
Anschlußschema 400V / Cable arrangement 400V
+
-
Verbraucher
consumer
L1
PE
N
PSU90 / PS1U90
Netzspannung
line-voltage
PSU90 - 230 V~
PS1U90 - 115 V~