Thank you for purchasing the Fuji module type temperature controller.

Once you have confirmed that this is the product you ordered, please use it in 

accordance with the following instructions.

For detailed information on operating this equipment, please refer to the separate 

user's manual.

In addition, please keep this instruction manual within easy reach of the actual person 

using this equipment.

Model : PUMA/B

Multi-loop module type Temperature Controller

Control Module

Instruction Manual (Installation)

CAUTION

The contents of this manual are subject to change without notice.

This manual is complied with possible care for the purpose of accuracy, however, 

Fuji Electric shall not be held liable for any damages, including indirect damage, 

caused by typographical errors,

absence of information or use of information in this manual.

Confirming Specifications and Accessories

Before using the product, confirm that it 

matches the type ordered.

(For model code, please refer to page 4.)

Confirm that all of the following 

accessories are included.

Temperature Controller Control Module  1 Unit
Instruction Manual 

1 copy

I/V unit (250 ohm resistance) 

1 unit per voltage/current input

Related Information

Refer to "Module Type Temperature 

Controller Control Module User's Manual" 

for details about the items described in 

this manual.

Content

Material 

name

Material No.

Specification

Catalog

ECNO 1162

Operating 

instruction

Control 

module 

User's 

manual

INP-

TN5A0198-E

Tool

PUM 

parameter 

loader

INP-

TN5A0201-E

Please Read First (Safety Warnings)

Please read this section thoroughly before using and observe the mentioned safety 

warnings fully.

Safety warnings are categorized as "Warning" or "Caution".

 Caution

Improper use of the equipment may result in death or serious injuries.

 Warning Improper use of the equipment may cause injury to the user or property 

damage.

 Warning

1-1 

Installation and Wiring

• 

This equipment is intended to be used under the following conditions.

Ambient temperature

-10 to 50 degree C

Ambient humidity

90% RH or below (with no condensation)

Vibration

10 to 70Hz less than 9.8m/s² (1G)

Warm-up time

30 min. or more

Installation category

IEC1010-1: class II

Pollution level

IEC1010-1: degree 2

• 

Between the temperature sensor and the location where the voltage reaches or 

generates the values described below, secure clearance space and creepage 

distance as shown in the table below.

If such space cannot be secured, the EN61010 safety compliance may become 

invalid

Voltage used or generated 

by any assemblies

Clearance Space [mm]

Creepage Space [mm]

Up to 50 Vrms or Vdc

0.2

1.2

Up to 100 Vrms or Vdc

0.2

1.4

Up to 150 Vrms or Vdc

0.5

1.6

Up to 300 Vrms or Vdc

1.5

3.0

Above 300 Vrms or Vdc

Please consult our distributor

• 

For the above, if voltage exceeds 50Vdc (called danger voltage), basic insulation is 

required between the earth and all terminals of the equipment.

Note that the insulation class for this equipment is as follows. Before installing, 

please confirm that the insulation class for the equipment meets usage requirements.

Power

Loader communication port

RS-485 communication port

CT Input (CT1A, B - CT4A,B)

OUT1 (relay contact output)
OUT2 (relay contact output)

OUT4 (relay contact output)

OUT3 (relay contact output)

PV1 Input
PV2 Input
PV3 Input
PV4 Input

OUT1 (SSR drive, current)
OUT2 (SSR drive, current)
OUT3 (SSR drive, current)
OUT4 (SSR drive, current)

Basic insulation (1500Vac)

Functional insulation (500Vac)

Functional insulation (1000Vac)

 -

In cases where damage or problems with this equipment may lead to serious 

accidents, install appropriate external protective circuits.

 -

To prevent damage and failure of the equipment, provide the rated power voltage.

 -

To prevent electric shock and equipment failure, do not turn the power ON until all 

wiring is complete.

 -

Before turning the power ON, confirm that clearance space has been secured to 

prevent shock or fire.

 -

Do not touch the terminal while the machine is ON. Doing so risks shock or 

equipment errors.

 -

Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal 

operation, shock or fire.

1-2 

Maintenance

 -

When installing or removing the equipment, turn the power OFF. Otherwise, shock, 

operational errors or failures may be caused.

 -

Periodic maintenance is recommended for continuous and safe use of this 

equipment.

 -

Some parts installed on this equipment have a limited life and/or may deteriorate with 

age.

 -

The warranty period for this unit (including accessories) is one year, if the product is 

used properly.

 Caution

2-1 

Cautions when Installing

Please avoid installing in the following locations.

 -

Locations in which the ambient temperature falls outside the range of 0 to 50 degrees 

C when equipment is in use.

 -

Locations in which the ambient humidity falls outside the range of 45 to 85% RH 

when equipment is in use.

 -

Locations with rapid temperature changes, leading to dew condensation

 -

Locations with corrosive gases (especially sulfide gas, ammonia, etc.) or flammable 

gases.

 -

Locations with vibration or shock directly.

 -

Locations in contact with water, oil, chemicals, steam or hot water.

(If the equipment gets wet, there is a risk of electric shock or fire, so have it 

inspected by Fuji distributor.)

 -

Locations with high concentrations of atmospheric dust, salt or iron particles.

 -

Locations with large inductive interference, resulting in static electricity, magnetic 

fields or noise.

 -

Locations in direct sunlight.

 -

Locations that build up heat from radiant heat sources, etc.

2-2 

Cautions when Mounting to Cabinets / DIN rails

 -

In case of mounting the temperature controllers to DIN rails, remember to push up 

the locking tabs to fasten the controllers onto DIN rail.

 -

To connect controllers, first release all locking tabs. Then, connect controllers and 

push up all locking tabs. Make sure that all locking tabs are fastened.

 -

Never fail to turn the power OFF, before detaching the terminal block or removing the 

main unit from the base part.

 -

In order to aid heat dissipation, do not block the top and the bottom of the equipment.

 -

When mounting / dismounting controllers to / from DIN rails, 30mm of clearance 

above and under the controllers should be provided.

 -

Use terminal screws in this product only.

2-3 

Cautions for Wiring

 -

For thermocouple input, use the designated compensation lead. For resistance bulb 

input, use wires with small lead wire resistance and without any resistance difference 

among three wires.

 -

To avoid the influence of inductive noise, input signal wires should be separated from 

electric power lines or load lines.

 -

Input signal wire and output signal wire should be separated from each other. And 

both should be shielded.

 -

If the output operation frequency is high, selecting a SSR/SSC drive output type is 

recommended.

[Proportionate cycles] Relay output: 30 sec. or more, SSR/SSC drive output: 1sec. 

or more

 -

When inductive loads such as magnetic opening/closing equipment, etc. as relay 

output equipment are connected, use of "Z-trap," manufactured by Fuji Electric 

Device Technology Co., Ltd., is recommended in order to protect the contacts against 

opening/closing surges and to ensure long-term use.

Model names  : ENE241D-07A (For 100V power 

voltage)

 

:  ENE471D-07A (For 200V power 

voltage)

Attachment position : Please connect between the 

relay control output contacts.

 -

To comply with CE marking (EMC), we recommend to 

attach ferrite core to communication cable and power 

cable.

 -

For wiring to the terminal block, apply crimp type 

terminals size M3.

Screw size 

: M3 x 7 (with square washer)

Screw tightening torque : 0.78N-m (8kgf-cm)

2-4 

Error Operation

 -

The alarm function does not work properly when an error occurs unless the settings 

are made correctly. Always verify its setting before operation.

 -

In case of error input, PWR LED will flash. When replacing the sensor, make sure to 

turn the power OFF.

- 1 -

INP-TN1PUMAa-E

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

Z-trap connecting diagram