Switch Definitions 

 

SW1 

 

SW2 

Pole Description 

Function 

  Pole Description 

Function 

Address 0 

 

Fault Shut down 

For M/S and AC only.  When 

ON

 an 

Abnormal condition on any controller 
it will shut down all STPs 

2 Address 

  2 Unused 

Unused 

Switch 

3 Address 

  3 Master/Slave

**

 

ON

 for Master controller 

OFF

 for Slave(s) and Stand Alone 

4 Address 

  4 Alternating 

Circuit

**

 

ON

 for Master Controller 

OFF

 for Slave(s) and Stand Alone 

5 Address 

Controller Addressing switches for 
use with Master/Slave and 
Alternating Circuit configurations  
See Table 1 

 5 Extended 

Run 

Disable* 

ON

 disables Extended Run Fault 

OFF

 Extended Run detection active 

Fault Read out

*

 

ON

 Displays the last 5 abnormal 

conditions the controller encountered 

 6 Unused 

Bypass

*

 

ON

 Bypasses diagnostics for 10 

minutes. Use as Troubleshooting aid 

 7 Unused 

Auto Restart

*

 When 

ON,

 controller will attempt to 

restart STP with Empty Tank error 
when hook signal is applied. 

 8 Unused 

Unused switches 

*

 See trouble shooting guide for detailed description 

**

 See Figure 1 for configuration switch settings 

 

Selectable features to aid Troubleshooting 

See Figure 1 for location and See Switch Definitions table for brief description of the following features: 

Fault Read Out Mode

 (SW1, Pole 6) 

With this mode selected, switch in the ON position, the controller will display the last 5 abnormal conditions it 
encountered.  The controller will beep once and then the red LED will flash the most recent abnormal condition.  It will 
then beep twice and the red LED will flash the second to last abnormal condition.  The controller will follow this sequence 
through 5 beeps and then repeat the sequence.  It will continue to repeat the sequence while in this mode.  If there is less 
then 5 abnormal conditions the controller will continue the beep sequence but the red LED will not flash after the beep.  
With the appropriate equipment the last 5 abnormal conditions can be read through the RS485 port. 

Bypass Mode

 (SW1, Pole 7) 

With this mode selected, switch in the ON position, the controller will operate as a standard control box.  It will not indicate 
or shut down any abnormal condition with the exception of an over current condition (short or locked rotor).  The controller 
will stay in this mode for 10 minutes.  After the 10 minutes the controller will revert to its normal operation.  Pushing the 
reset button will allow it to run another 10 minutes in the Bypass mode. 

Auto Restart Mode

 (SW1, Pole 8) 

With this mode selected, switch in the ON position, If the controller detects an empty tank/under load condition, it will shut 
down the pump and it will attempt to start the pump when a hook signal is removed and reintroduced to the controller.  If 
the empty tank condition is still present the controller will shut down the pump.  If the empty tank condition is corrected 
(tank is refilled) the controller will run the STP and clear the abnormal condition. In M/S configuration, if the Master is in 
the under load condition, it will wait until the Slave controller calls for help before attempting to restart. 

Fault Shutdown Mode

 (SW2, Pole 1) 

For Master-Slave and Alternating Circuit configurations only, this mode only needs to be selected on the Master 
controller.  When this mode is selected, switch in the on position, the entire system will shutdown if any of the controllers, 
Master or Slaves, detect an abnormal condition.  The system will not run until the abnormal condition is corrected and the 
reset button is pushed or the Fault Shutdown mode switch is turned off and the reset button is pushed. 

Extended Run Disable

 (SW2, Pole 5) 

This switch, when in the ON position, will disable the Extended Run Fault detection of the STP-SCI.  The Extended Run 
Fault will shut off the STP if it has been running for 60 minutes without a change in product flow.  A possible application of 
this switch is in an emergency generator where the STP is running at all times. 

Do not disable the Extended Run if the system requires the pump to be off for line leak detection 
i.e. Mechanical Leak Detectors, Electronic Line Leak detection.  Disabling the Extended Run Fault 
and running the STP continuously could mask a leak in the system. 

Table 2 

Caution 

Summary of Contents for STP-SCI

Page 1: ...klin Fueling 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com Installation and Owner s Manual Software Revision 1 4 SMART CONTROLLER I STP...

Page 2: ...identally turned on while the STP SCI is being installed electrical power could be applied to the STP SCI creating the risk of potentially lethal electrical shock hazard ALWAYS tag and lock breakers s...

Page 3: ...gure 5 for Master Slave AC Configurations Connect Communication cable RS 485 to terminals G and wire together G together and together then wire the shielded cable drain wire to Ground G at one end onl...

Page 4: ...c line leak detection is used make sure the STP SCI is in calibration mode all three lights flashing alternately before the dispenser handle is turned on If it is not the STP SCI will not turn on and...

Page 5: ...n Off Off Slave 8 Off Off Off On Off Slave 9 On Off Off On Off Slave 10 Off On Off On Off Slave 11 On On Off On Off Slave 12 Off Off On On Off Slave 13 On Off On On Off Slave 14 Off On On On Off Slave...

Page 6: ...ed switch in the ON position the controller will operate as a standard control box It will not indicate or shut down any abnormal condition with the exception of an over current condition short or loc...

Page 7: ...y still be power present at the STP SCI Hook Terminal If this condition exists call FE Petro Technical Service for assistance Red Light Flashing Alarm Beeping Abnormal condition Determine the number o...

Page 8: ...acement Inspection 2 Disconnect input voltage at load center lock and tag out circuit breakers 3 See PMA Replacement Instructions P N 400289002 included with New PMA Disengage the 3 4 securing bolt of...

Page 9: ...t step 7 Remove the junction box cover and do conductivity test on wires in the junction box after the capacitor through the extractable discharge head orange to orange red to red and black to black I...

Page 10: ...10 Figure 2 STP SCI Stand Alone Wiring Diagram...

Page 11: ...11 Figure 3 STP SCI Master Slave Wiring Diagram...

Page 12: ...12 Figure 4 STP SCI Alternating Circuit Wiring Diagram...

Page 13: ...13 Figure 5 STP SCI Master Slave Alternating Circuit Wiring Diagram...

Page 14: ...14 REPLACEMENT PARTS Upper Board Relay Assembly P N 225005930 Lower Board Control Assembly P N 225000930 Lower Board Upper Board Picture 4...

Page 15: ...15 This page intentionally left blank...

Page 16: ...2004 FE Petro Form No 223987101 Rev 4...

Reviews: