FDC Orion-M Manual Download Page 9

Orion-M

  

 

 

 

 

 

 

      

       

 

 

CONFIGURING THE UDC2500/3200 CONTROLLER 

 

 

 

 

 

 

 

 

 

 

 

        

 

FDC Orion-M 

3.1 

 

3  Configuring the Honeywell UDC2500/3200 Controller 

The unique and inherently flexible design of the Orion-M system allows the OEM to tailor each component of 
the system to the application.   By using independent loop controls, each one can be configured for various 
input and output types, control algorithms, etc., based on the requirements of the application.  It also allows 
control  loops  to  be  added  or  replaced  on  the  system at  any  time,  simply  by  connecting  the  controller  to  the 
Orion-M’s control module, RS-485 communication link. 
 
If the application requirements change and a different input or output type is required, or if the controller were 
to  fail,  it  can  be  replaced  quickly,  and  at  a  lower  cost  as  compared  to  having  to  repair  or  replace  larger, 
integrated  multi-loop  controllers.    The  Orion-M  only  requires  that  the  communications  settings  for  each  loop 
control  be  properly  assigned,  and  that  the  input  type  of  the  controller  is  set  in  the  Orion-M  Configurator,  so 
that the control loop input and set point can be displayed and set properly through the Orion-M interface. 
 
 

3.1  Assigning the Proper Communications Settings 

The Orion-M can support up to 15 UDC2500 and/or UDC3200 controls.  They can be mixed and matched as 
required,  but  each  one  must  have  its  own  communication  address.    The  allowable  address  range  is  1  –  15 
corresponding  to  Loop  Input  #1  –  15  in  the  Orion-M  Configurator.    Communication  addresses  must  be 
assigned to all controllers on the communications link beginning with 1, up to the total number of controllers. 
 
As control loops are enabled in the Orion-M Configurator, the Orion-M will automatically use the Loop Input # 
as the corresponding controller address.  If more than one UDC controller  has the same address, or a loop 
input  is  enabled  but  a  controller  is  not  assigned  to  that  address,  the  Orion-M  will  report  a  communications 
alarm for that loop input when the runtime application is started. 
 

NOTE:

 

The  order  of  the  loop  controls  on  the  communication  link  is  not  important.    The  communications 
address for a controller can be assigned regardless of its position on the link.  

 
In addition to the communications address, the baud rate, floating point format, shed enable and computer set 
point  options  must  also  be  set  to  match  the  control  module  of  the  Orion-M.    The  Orion-M  uses  a  default 
communication rate of 9600 baud, 8 data bits, 1 stop bit and no parity, which are typical settings for Modbus 
RTU communications and compatible with the UDC2500/3200 controller.  
 

*

Required UDC2500/3200 Communications Group Settings: 

 

 

Communications station address (ComADR):  1-15 

(based on system design)

 

 

Communications selection (COMSTA):   

 

MODBUS 

 

Infrared communications (IRENAB):   

 

 

DIS 

(recommended but not required)

 

 

Baud rate (BAUD):   

 

 

 

 

 

 

 

9600 

 

Transmit delay (TX DLY):   

 

 

 

 

 

 

Floating point data format (WS FLT):  

 

 

FP B 

 

Shed enab le (SDENAB): 

 

 

 

 

 

 

ENAB 

 

Shed time (SHDTIM) :   

 

 

 

 

 

 

60  

(recommended – minimum of 30 seconds)

  

 

Shed mode (SDMODE):  

 

 

 

 

 

 

LAST 

 

Shed set point (SHD SP):   

 

 

 

 

 

CSP 

 

UNITS:  

 

 

 

 

 

 

 

 

 

 

 

EGR 

 

Computer set point ratio (CSP RATIO):   

 

 

Computer set point b ias (CSP BIAS);  

 

 

0  

 
*

See  section  3  Configuration,  in  the  Honeywell  UDC2500/3200  Product  Manual  for  instructions  on 

accessing the control’s configuration menus and setting the above parameters as required.

 

Summary of Contents for Orion-M

Page 1: ...Orion M Honeywell UDC2500 3200 Series Controller System Guide Rev C February 7 2011 Supersedes Rev B March 25 2010 Orion M Honeywell UDC2500 3200 Controller System Guide...

Page 2: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance by dialing 1...

Page 3: ...1 1 Communications Wiring 2 1 3 Configuring the Honeywell UDC2500 3200 Controller 3 1 3 1 Assigning the Proper Communications Settings 3 1 3 2 Input Type Assignments 3 2 3 2 1 Input 1 Operation 3 2 3...

Page 4: ......

Page 5: ...No other control system on the market provides the flexibility functionality and configurability of the Orion M 1 1 Features The digital inputs of the Orion M can be configured as alarm inputs with a...

Page 6: ...includes the following interface features Overview screen that displays all runtime information Profile run and monitor views Profile entry open save and download interface screens Current alarm and a...

Page 7: ...ring to and form the UDC controllers be routed away from all high voltage and or output control wiring This will minimize the chances of electrical transients or spikes in the power control wiring fro...

Page 8: ...UDC2500 or UDC3200 Product Manual for all other connections including power sensor and control wiring Since no two applications are the same it is up to the system designer to insure that the control...

Page 9: ...munications link beginning with 1 up to the total number of controllers As control loops are enabled in the Orion M Configurator the Orion M will automatically use the Loop Input as the corresponding...

Page 10: ...he Orion M Configurator the temperature units in the Orion M must match the UDC controllers for the drybulb wetbulb calculation to be performed correctly If the temperature units do not match the rela...

Page 11: ...f the loop control is visible to the operator it is recommended that the Monitor Input Offset screen be hidden see Section 3 6 Orion Functions Startup View in the Orion M Configuration Manual or even...

Page 12: ...M is designed to send the shed timer reset command to the UDC controller to take it out of computer set point control when the set point permission is enabled This allows control via the keypad of the...

Page 13: ...Orion M APPENDIX FDC Orion M A 1 Appendix...

Page 14: ...ter delivery to the first purchaser for use There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth Limitations Future Design Controls provides no warra...

Reviews: