FCI ADP-R Installation And Maintenance Instructions Download Page 3

FC200-12-00                                                                                             6                                                                                          I56-2214-004R

Figure 11. System Wiring Diagram 
for ADP-R Duct Smoke Detector with 
RTS451/RTS451KEY

Figure 10. Wiring Diagram for ADP-R Duct Detector
with optional RA400Z

5 7

RA400Z

5 = Alarm Signal
7 = Aux. Power (–)

ALARM SIGNAL

AUX. POWER (–)

TEST +

TEST –

ALARM SIGNAL

NOT USED

NOT USED

CIRCUIT

REFERENCE

TEST

SWITCH

FOR RTS451, TERMINAL 3 IS NOT 

USED. (RTS451 DOES NOT HAVE 

A TERMINAL 6.) FOR RTS451KEY, 

TERMINALS 3 AND 6 ARE NOT USED.

RTS 451/RTS451KEY

5

7

4

3

1

3

6

2

4

5

FC200-12--00                                                                                            3                                                                                          I56-2214-004R

SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.

Figure 3. Installation of foam gaskets over sampling 
tube bushings:

Figure 5. Tube mounting configurations with varying 
air flow direction:

length using Table 1. Otherwise, trim the end of the tube protruding 
through the duct so that 1

 to 2

 of the tube extend outside the duct. 

Plug this end with the end cap and tape closed any holes in the pro-
truding section of the tube. Be sure to seal the duct where the tube 
protrudes.

NOTE: 

The sampling tube end cap is critical to the proper operation of the 

duct smoke detectors. The end cap is needed to create the proper air flow 
to the sensor of the duct smoke detector.

Table 1. Sampling tubes recommended for different
duct widths:
       

Outside Duct Width                Sampling Tube Recommended*

        1 to 2 ft. (0.3 to 0.6 m)                               ST-1.5
        2 to 4 ft. (0.6 to 1.2 m)                                 ST-3
        4 to 8 ft. (1.2 to 2.4 m)                                 ST-5
       8 to 12 ft. (2.4 to 3.7 m)                                ST-10
*Must extend a minimum of 

2⁄3

 the duct width

SAMPLING

TUBE

END CAP

AIR HOLES

ARROW

MUST FACE

INTO AIR FLOW

AIR FLOW DIRECTION

FLANGE

Figure 4. Air duct detector sampling tube:

H0108-02

AIR FLOW

DIRECTION

DETECTOR

HOUSING

DOTS INDICATE POSITION OF

SAMPLING TUBE HOLES

AIR FLOW

DIRECTION

DETECTOR

HOUSING

SAMPLING

TUBE

EXHAUST

TUBE

AIR FLOW

DIRECTION

EXHAUST

TUBE

SAMPLING

TUBE

SAMPLING

TUBE

EXHAUST

TUBE

DETECTOR

HOUSING

AIR FLOW

DIRECTION

DETECTOR

HOUSING

A.

B.

C.

D.

HORIZONTAL MOUNTING OF HOUSING

VERTICAL MOUNTING OF HOUSING

NOTE: Only metal sampling tubes can be installed in 

orientations C and D.

H0109-01

H0107-00

[4.2] Installation For Ducts More Than 8 Feet Wide

NOTE:

     To install sampling tubes in ducts more than 8 feet wide, work 

must be performed inside the air duct. Sampling of air in ducts 
wider than 8 feet is accomplished by using the ST-10 sampling 
tube. If the tube is shorter than the width of the air duct, install 
the end cap into the sampling tube as shown in Figure 4 and 
support the end opposite the duct smoke detector.

Install the sampling tube as follows:

1.  Drill a 

3

⁄4

-inch hole in the duct directly opposite the hole already drilled 

for the sampling tube. Make sure the hole is 1

 to 2

 below the inlet 

hole on the opposite side of the duct to allow for moisture drainage.

2.  Slide the sampling tube with the flange into the housing bushing that 

meets the air flow first. Position the tube so that the arrow points into 
the air flow. Secure the tube flange to the housing bushing with two 
#6 self-tapping screws.

3.  From inside the duct, couple the other sections of the sampling tube 

to the section already installed using the 

1

⁄2

-inch conduit fittings sup-

plied. Make sure that the holes on both of the sampling tubes are lined 
up and facing into the air flow.

4.  Trim the end of the tube protruding through the duct so that 1

 to 2

 of 

the tube extend outside the duct. Plug this end with the end cap and 
tape closed any holes in the protruding section of the tube. Be sure to 
seal the duct where the tube protrudes.

NOTE:

     An alternate method to using the ST-10 is to use two ST-5 sam-

pling tubes. Remove the flange from one of the tubes and install 
as described above. After the installation, use electrical tape to 
close off some of the sampling holes so that there are a total of 
10 to 12 holes spaced as evenly as possible across the width of 
the duct.

NOTE:

     Air  currents  inside  the  duct  may  cause  excessive  vibration, 

especially  when  the  longer  sampling  tubes  are  used.  In  these 
cases a 3 inch floor flange (available at most plumbing supply 
stores)  may  be  used  to  fasten  the  sampling  tube  to  the  other 
side  of  the  duct.  When  using  the  flange/connector  mounting 
technique, drill a 1-inch to 1

1

⁄4

-inch hole where the flange will 

be used.

[5] Install The Filters 

To install the sampling tube filters, simply push the filters into the sam-
pling and exhaust tube holes, as shown in Figure 6. If a metal sampling 
tube is used, install the filters over the tube end.

Figure 6. Sampling tube filter installation:

H0131-00

5 7

PA400

5 = Alarm Signal
7 = Aux. Power (–)

Figure 12.  Wiring Diagram for ADP-R with          
optional PA400

Figure 13. Insulator Card for ADP-R Duct Smoke 
Detector 

[9.2.2] Alarm Tests
[9.2.2.1] M02-04-00 Magnet Test

1.  Place the painted surface of the magnet onto the TEST  locator on the 

bottom of the detector housing (Figure 14).

2.  Verify system control panel alarm status and control panel execution 

of all intended auxiliary functions (i.e. fan shutdown, damper control, 
etc.)  

3.  The detector is self-restoring when the magnet is removed. Verify that 

the system control panel has reset; panel may have to be reset.

Figure 14. Testing detector alarm:

H0130-00

[9.2.2.2] RTS451/RTS451KEY Remote Station Test

The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm 
capability  of  the  duct  smoke  detector.    These  accessories  provide  the 
stimulus  to  initiate  an  alarm  condition  at  the  detector.    The  detector  is 
self-restoring when the accessory test stimulus is removed. Verify that the 
system control panel has reset; panel may need to be reset.   

[9.2.3] Sensitivity Tests

Notify the proper authorities that the smoke detector system is undergo-
ing maintenance, and that the system will temporarily be out of service. 
Disable the device or system undergoing maintenance to prevent unwant-
ed alarms and possible dispatch of the fire department.

[9.3] Maintenance of Duct Smoke Detectors
[9.3.1] Air Filters

1.  Turn off power to the system.
2.  Remove and inspect sampling tube filters.
3.  If  filters  are  heavily  coated  with  dirt,  replace  them  with  new  filters 

(p/n F36-09-11). If they are not heavily coated, use a vacuum cleaner 

or compressed air nozzle to remove dust, then reinstall the filters. 

H0132-00

H0150-00

H0136-00

H0133-00

Reviews: