FBs-CM25/CM55/CBE
Ethernet Module
User’s Manual
Ver. 2.1
Fatek Automation Corp.
7/1/2004
www.manasanat.ir
Page 1: ...FBs CM25 CM55 CBE Ethernet Module User s Manual Ver 2 1 Fatek Automation Corp 7 1 2004 www manasanat ir...
Page 2: ...10 5 2 2 Cable Wiring 11 5 3 Software Configuration 12 5 3 1 Configuration Software and its Function 12 5 3 2 Configuration thru Local Area Network 13 5 3 3 Configuration thru Internet 13 5 3 4 Commo...
Page 3: ...dge the communication between the management level and field level To meet this trend FATEK provides a series of Network interface modules with which an economic and effective network solution for FAT...
Page 4: ...LED Transmit LED Receive LED Signal Connector Euro 4pin Connector Port4 CM25E CM55E CPU Connected Port Port1 Port2 CBE 9600 19200 38400 57600 115200 230400 CM25E CM55E CPU Connected Speed 115200 CBE...
Page 5: ...connector but using Euro 4 pin plug connector 2 port4 connector The signals in this connector is RS485 level 3 port3 connector The signals in this connector can be RS232 CM25E or RS485 CM55E This port...
Page 6: ...unction of Ethernet Serial Converter The operation principle of Ethernet serial converter is to take this module as interface and receive all the messages from network that intend to the PLCs managed...
Page 7: ...ed by network the Ethernet module will pack the message into data packet for network transmission and send it to network After send the message to network the Ethernet module will wait for the reply m...
Page 8: ...ure The PLCs connect the Ethernet module with the RS485 interface of port4 The work station A and work station B are master that can send the command message actively to FBs PLC Upon receiving the com...
Page 9: ...1 Standard Client Mode When work at this mode the master PLC connected with Ethernet module can use LINK instruction mode0 send the command message to other PLC The target PLC that master PLC intend...
Page 10: ...net module attached to group 2 PLC is configured as server mode which means all the PLCs covered by this module are work as slave PLC and wait for the command passively It must emphasis that the PLCs...
Page 11: ...the slave PLCs that attached to network 5 2 Hardware Installation 5 2 1 DIP Switch Setting 5 2 1 1 Termination resistor installation FBs CM25E CM55E In order to meet the termination requirement of RS...
Page 12: ...on 5 2 2 Cable Wiring Serial port connectors Please refer Appendix A B for the Port3 Port4 signal description Network connector The connector type of FBs CM25E 55E is Euro 4pin plug connector while FB...
Page 13: ...C by executing the LINK instruction of mode0 and with the help of Ethernet module the master PLC does not know the remote PLC is connected by network In other words the maximum number of slave station...
Page 14: ...ocal Area Network Step 1 Use the network cable to connect the Ethernet module and Hub Step 2 Connect the PC to network and execute the software Ether_cfg exe Use the mouse click the Intranet option in...
Page 15: ...configuration After click the Get Map button it will start to connect Ethernet module When the connection is established will show the information regard the connected Ethernet module in the table at...
Page 16: ...et module At most can consist of 11 characters Comment For documentation can be used to distinguish Ethernet module At most can consist of 21 characters Operation mode Client or server mode selection...
Page 17: ...screen will be shown Message Time Out The time out time for PLC the default setting is 300ms Ethernet module will wait for the same amount time of this field before the PLC can reply the command messa...
Page 18: ...e setting of authorized IP to prevent the illegal access of data After click the Access Control tab the screen changes to Move the cursor to the Grant IP table and click the right mouse button then th...
Page 19: ...e of IP addresses in Group Size filed 5 3 6 Station IP mapping Setup This setting can only need to perform when Ethernet module is work at client mode When the working mode is set to client mode the b...
Page 20: ...iption of each field shown in above Local Station The station number of local PLC Remote Station The station number of remote PLC Remote IP The IP address of Ethernet module connected by the remote PL...
Page 21: ...ng of configuration data please click the OK button of the adaptor s properties window to update the Ethernet module When finish the update and without error the screen will change to main window and...
Page 22: ...beds the FATEK serial communication message in the TCP or UDP data packet The port number used to convey the FATEK TCP UDP message is configurable default is 500 refer 5 3 7 for detail D Modbus TCP Co...