FB Series SIO Driver

GP-Pro EX Device/PLC Connection Manual

80

8J)

• 1:1 Connection

• 1:n Connection

Number

Name

Notes

(1)

RJ45 RS-485 Cable (5m) by Pro-face

PFXZLMCBRJR81

120

 (1/4W)

Terminal
resistance

Ω

D-Sub 15 pin (plug)

External Device

5

7

10

Signal name

D+

D-

FG

Pin

Display

D0

D1

(1)

Shield

220Ω(1/4W)

Terminal
resistance

220Ω(1/4W)

 

Terminal
resistance

D-Sub 15 pin (plug)

External Device

5

7

10

Signal name

D+

D-

FG

Pin

D-Sub 15 pin (plug)

External Device

5

7

10

Signal name

D+

D-

FG

Pin

Display

D0

D1

(1)

User-created Cable

Summary of Contents for FB Series

Page 1: ...n FB Series SIO Driver 1 System Configuration 3 2 Selection of External Device 8 3 Example of Communication Setting 9 4 Setup Items 32 5 Cable Diagram 37 6 Supported Devices 83 7 Device Code and Address Code 85 8 Error Messages 86 ...

Page 2: ...the model series of the External Device to be connected and its connection method 2 Selection of External Device page 8 3 Example of Communication Settings This section shows setting examples for communicating between the Display and the External Device 3 Example of Communication Setting page 9 4 Setup Items This section describes communication setup items on the Display Set the communication sett...

Page 3: ...ge 38 FBs CB22 Port 1 RS232C Setting Example 3 page 12 Cable Diagram 2 page 38 Port 2 RS232C Setting Example 2 page 10 FBs CB25 Port 1 RS232C Setting Example 3 page 12 Cable Diagram 2 page 38 Port 2 RS422 485 2wire Setting Example 4 page 14 Cable Diagram 4 page 41 FBs CB5 Port 2 RS422 485 2wire Setting Example 4 page 14 Cable Diagram 4 page 41 FBs CB55 Port 1 RS422 485 2wire Setting Example 5 page...

Page 4: ...24 FBe FBn 1 FBe 20MA FBe 28MA FBe 40MA CPU unit Port 0 RS232C Setting Example 11 page 27 Cable Diagram 5 page 53 RS422 485 2wire Setting Example 10 page 26 Cable Diagram 6 page 56 FBe 20MC FBe 28MC FBe 40MC FBn 19MCT FBn 26MCT FBn 36MCT CPU unit Port 0 RS232C Setting Example 11 page 27 Cable Diagram 5 page 53 RS422 485 2wire Setting Example 10 page 26 Cable Diagram 6 page 56 Port 1 RS232C Setting...

Page 5: ...ge 27 Cable Diagram 3 page 39 Port 2 RS422 485 2wire Setting Example 13 page 30 Cable Diagram 6 page 56 1 Set the software s interface to Standard Interface Refer to your External Device manual for the correct settings 2 Available only with a CPU incorporating an RS232 port Series CPU Link I F SIO Type Setting Example Cable Diagram Display External Device Display External Device External Device Ex...

Page 6: ...sed COM3 2 COM3 2 PS 3711A COM1 1 COM2 2 COM2 2 COM2 2 PS4000 3 3 When making communication between an External Device and COM port on the Expansion slot only RS 232C is supported However ER DTR CTS control cannot be executed because of the specification of COM port For connection with External Device use user created cables and disable Pin Nos 1 4 6 and 9 Please refer to the IPC manual for detail...

Page 7: ...to RD RXD None 7 OFF Short circuit of SDA TXA and RDA RXA Not available 8 OFF Short circuit of SDB TXB and RDB RXB Not available 9 OFF RS RTS Auto control mode Disabled 10 OFF DIP Switch Setting Description 1 OFF Reserved always OFF 2 ON SIO type RS 422 485 3 ON 4 OFF Output mode of SD TXD data Always output 5 OFF Terminal resistance 220Ω insertion to SD TXD None 6 OFF Terminal resistance 220Ω ins...

Page 8: ...ration make sure the External Device you are connecting is supported by FB Series SIO 1 System Configuration page 3 Port Select the port of the Display to be connected to the External Device Use System Area Check this option to synchronize the system data area of the Display and the device memory of the External Device When synchronized you can use the External Device s ladder program to switch th...

Page 9: ...ion Settings To display the setup screen from the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add anoth...

Page 10: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 11: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 2 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 12: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 13: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 1 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 14: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 15: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 2 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 16: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 17: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 1 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 18: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 19: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 3 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 20: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 21: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 4 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 22: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 23: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 3 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 24: ...Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device ...

Page 25: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 4 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 26: ...g To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device Settings of External Device The communication setting is fixed For 1 n connection set Wait To Send to a ...

Page 27: ...g To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device Settings of External Device The communication setting is fixed For 1 n connection set Wait To Send to a ...

Page 28: ...ice PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device For 1 n connection set Wait To Send to a value of the PLC scan time plus 5ms or mor...

Page 29: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 1 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 30: ... select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select the external device and click Settings To connect multiple External Devices from Device Specific Settings in the Device PLC window click Add Device to add another External Device For 1 n connection set Wait To Send to a value of the PLC scan time plus...

Page 31: ...ngs reboot the External Device to enable them Refer to your External Device manual for details 1 Start up the ladder software WinProladder 2 Select Setting Port 2 Parameter from the PLC menu 3 In the Comm Parameter Setting dialog box set the following parameters 4 Click OK to complete the port settings Item Settings Baud Rate 9 600 Parity Even parity Data Bit 7 bits Stop Bit 1 bit ...

Page 32: ...ect menu point to System Settings and select Device PLC Setup Items Setup Description SIO Type Select the SIO type for communicating with the External Device Speed Select the communication speed between the External Device and the Display Data Length Select a data length Parity Select how to check parity Stop Bit Select a stop bit length Flow Control Select the communication control method to prev...

Page 33: ... Display retransmits the command from 0 to 255 Wait To Send Enter the standby time ms from when the Display receives packets until it transmits the next command from 0 to 255 RI VCC You can switch between RI VCC of the 9th pin when you select RS232C for the SIO type To connect to the IPC you need to use the IPC selector switch to switch RI 5V Refer to your IPC manual for details Refer to the GP Pr...

Page 34: ...yed for 1 page in the offline mode depends on the Display in use Please refer to the Reference manual for details Setup Items Setup Description SIO Type Select the SIO type for communicating with the External Device In the communication settings set SIO Type correctly according to the serial interface specifications of the Display If you select an SIO type that the serial interface does not suppor...

Page 35: ...Enter the time s for which the Display waits for a response from the External Device from 1 to 127 Retry In case of no response from the External Device enter how many times the Display retransmits the command from 0 to 255 Wait To Send Enter the standby time ms from when the Display receives packets until it transmits the next command from 0 to 255 Setup Items Setup Description Device PLC Name Se...

Page 36: ...o set from the list that appears and touch Option Setup Items Setup Description RI VCC You can switch between RI VCC of the 9th pin when you select RS232C for the SIO type To connect to the IPC you need to use the IPC selector switch to switch between RI 5V Refer to your IPC manual for details GP 4100 series GP 4 01TM LT 4 01TM and LT Rear Module do not have the Option setting in the offline mode ...

Page 37: ... of noise or other factors connect an isolation unit Cable Diagram 1 1A 1B Display Connection Port Cable Remarks GP3000 COM1 GP4000 1 COM1 SP5000 COM1 2 ST COM1 LT3000 COM1 IPC 2 PC AT 1 All GP4000 models except GP 4100 Series and GP 4203T 2 Available only with a COM port that supports RS232C IPC COM Port page 6 1A FBs 232P0 9F 150 by Fatek Automation Corporation GP 4105 COM1 1B User created Cable...

Page 38: ...t page 6 2A User created Cable Cable length 15m or less GP 4105 COM1 2B User created Cable Cable length 15m or less Signal name ER DTR 4 SD TXD 3 DR DSR 6 7 RS RTS SG 5 FG RD RXD 2 CS CTS 8 D Sub 9 pin socket Display Pin Shell Signal name DTR 6 RXD 3 DSR 4 7 SG 5 TXD 2 8 D Sub 9 pin plug External Device Pin Shield Display CTS RTS Signal name ER DTR SD TXD DR DSR RS RTS SG RD RXD CS CTS Terminal Bl...

Page 39: ...e length 15m or less GP 4105 COM1 3B User created Cable Cable length 15m or less LT 4 01TM COM1 LT Rear Module COM1 3C RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable length 5m or less Shield Signal name ER DTR 4 SD TXD 3 DR DSR 6 7 RS RTS SG 5 FG RD RXD 2 CS CTS 8 D Sub 9 pin socket Display Pin Shell Display D Sub 9 pin plug External Device 2 3 5 Signal name TXD RXD SG Pin CD 1 Shield Signa...

Page 40: ...SIO Driver GP Pro EX Device PLC Connection Manual 40 3C Number Name Notes 1 RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 D Sub 9 pin plug External Device 2 3 5 Signal name TXD RXD SG Pin Display GND TXD RXD 1 ...

Page 41: ...ersion adapter by Pro face CA3 ADPTRM 01 User created Cable Cable length 1 000m or less 4D Online adapter by Pro face CA4 ADPONL 01 User created Cable IPC 4 4E COM port conversion adapter by Pro face CA3 ADPCOM 01 Connector terminal block conversion adapter by Pro face CA3 ADPTRM 01 User created Cable Cable length 1 000m or less 4F User created Cable GP 4106 COM1 4G User created Cable Cable length...

Page 42: ... port that supports RS422 485 2wire IPC COM Port page 6 5 Except GP 4203T 6 All GP4000 models except GP 4100 Series GP 4 01TM GP 4201T and GP 4 03T 7 When using a Terminal Block Conversion Adapter CA3 ADPTRM 01 instead of the RS 422 Terminal Block Conversion Adapter refer to Cable Diagram 4A ...

Page 43: ... SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance ON Signal name RDB SDB SG FG CA3 ADPCOM 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance OFF Shield External Device Terminal block Signal name D D FG Terminal resistance ON ...

Page 44: ...A 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display Terminal resistance ON 120 1 2W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name SDA 3 RDB 2 SG 5 4 ERA SDB ERB 7 9 CSB 6 FG RDA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display Terminal resistance OFF 120 1 2W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Terminal ...

Page 45: ... SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance ON Signal name RDB SDB SG FG CA4 ADPONL 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance OFF Shield External Device Terminal block Signal name D D FG Terminal resistance ON ...

Page 46: ... D Sub 9 pin plug Display Pin Shell Display Terminal resistance ON TERMRX 1 CA4 ADPONL 01 User created Cable Shield External Device Terminal block Signal name D D FG Signal name SDA 3 RDB 7 TERMTX 9 5 SG SDB 8 FG RDA 2 D Sub 9 pin plug Display Pin Shell Display Terminal resistance OFF TERMRX 1 CA4 ADPONL 01 User created Cable Shield External Device Terminal block Signal name D D FG Terminal resist...

Page 47: ... SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance ON CA3 ADPCOM 01 CA3 ADPTRM 01 Display User created Cable External Device Terminal block Signal name D D FG Terminal resistance OFF Shield External Device Terminal block Signal name D D FG Terminal resistance ON Signal name RDB SDB SG FG Display Terminal block RDA SDA Shield TERM ...

Page 48: ... 8 D Sub 9 pin socket Display Pin Shell Display Terminal resistance ON 120 1 2W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name NC 3 DATA 2 GND SG 5 4 ERA NC ERB 7 9 CSB 6 FG DATA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display Terminal resistance OFF 120 1 2W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Terminal res...

Page 49: ...t Value 1 OFF 2 OFF 3 ON 4 ON Shield External Device Terminal block Signal name D D FG Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance ON Terminal resistance 1 Shield External Device Terminal block Signal name D D FG Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance OFF Terminal resistance 1 Shield Ex...

Page 50: ...ck Signal name D D FG Signal name NC 1 LINE 8 GND SG 5 4 RS RTS NC NC 2 7 NC 9 FG LINE 3 5V 6 D Sub 9 pin plug Display Pin Shell Display Terminal resistance ON 120 1 2W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name NC 1 LINE 8 GND SG 5 4 RS RTS NC NC 2 7 NC 9 FG LINE 3 5V 6 D Sub 9 pin plug Display Pin Shell Display Terminal resistance OFF 120 1 2W Term...

Page 51: ... SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance ON Signal name RDB SDB SG FG PFXZCBADTM1 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Terminal resistance OFF Shield External Device Terminal block Signal name D D FG Terminal resistance ON ...

Page 52: ...FXZLMCBRJR81 External Device Terminal block Signal name D D FG Terminal resistance ON Display D0 D1 1 User created Cable External Device Terminal block Signal name D D FG Terminal resistance OFF Shield External Device Terminal block Signal name D D FG Terminal resistance OFF Display D0 D1 1 Terminal resistance 220Ω 1 4W Terminal resistance 220Ω 1 4W ...

Page 53: ... 5C User created Cable Cable FB 232P0 9F 150 by Fatek Automation Corporation Cable length 15m or less 5D User created Cable Cable FB 232P0 9M 150 by Fatek Automation Corporation LT 4 01TM COM1 LT Rear Module COM1 5E RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable FB 232P0 9F 150 by Fatek Automation Corporation Cable length 6 5m or less 5F RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable...

Page 54: ...ub 15 pin socket User created Cable Shield Signal name ER DTR SD TXD DR DSR RS RTS SG RD RXD CS CTS Terminal Block Display Display D Sub 9 pin plug Connection Cable 2 3 5 Signal name TXD RXD SG Pin FB 232P0 9F 150 External Device D Sub 15 pin socket User created Cable Shield Signal name ER DTR SD TXD DR DSR RS RTS SG RD RXD CS CTS Terminal Block Display Display D Sub 9 pin socket Connection Cable ...

Page 55: ... Name Notes 1 RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 D Sub 9 pin plug Connection Cable 2 3 5 Signal name TXD RXD SG Pin FB 232P0 9F 150 External Device D Sub 15 pin socket Display GND TXD RXD 1 D Sub 9 pin socket Connection Cable 3 2 5 Signal name TXD RXD SG Pin FB 232P0 9M 150 External Device D Sub 15 pin socket Display GND TXD RXD 1 ...

Page 56: ...nversion adapter by Pro face CA3 ADPTRM 01 User created Cable Cable length 1 000m or less 6D Online adapter by Pro face CA4 ADPONL 01 User created Cable IPC 4 6E COM port conversion adapter by Pro face CA3 ADPCOM 01 Connector terminal block conversion adapter by Pro face CA3 ADPTRM 01 User created Cable Cable length 1 000m or less 6F User created Cable GP 4106 COM1 6G User created Cable Cable leng...

Page 57: ... port that supports RS422 485 2wire IPC COM Port page 6 5 Except GP 4203T 6 All GP4000 models except GP 4100 Series GP 4 01TM GP 4201T and GP 4 03T 7 When using a Terminal Block Conversion Adapter CA3 ADPTRM 01 instead of the RS 422 Terminal Block Conversion Adapter refer to Cable Diagram 6A ...

Page 58: ... RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM 120 1 4W Terminal resistance Ω Signal name RDB SDB SG FG CA3 ADPCOM 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω ...

Page 59: ...G RDA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display 120 1 4W Terminal resistance Ω 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name SDA 3 RDB 2 SG 5 4 ERA SDB ERB 7 9 CSB 6 FG RDA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal res...

Page 60: ... RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM 120 1 4W Terminal resistance Ω Signal name RDB SDB SG FG CA4 ADPONL 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω ...

Page 61: ...DA 2 D Sub 9 pin plug Display Pin Shell Display TERMRX 1 CA4 ADPONL 01 User created Cable 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name SDA 3 RDB 7 TERMTX 9 5 SG SDB 8 FG RDA 2 D Sub 9 pin plug Display Pin Shell Display TERMRX 1 CA4 ADPONL 01 User created Cable Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistanc...

Page 62: ...k Signal name D D FG 120 1 4W Terminal resistance Ω Signal name RDB SDB SG FG Display Terminal block RDA SDA Shield TERM CA3 ADPCOM 01 CA3 ADPTRM 01 Display User created Cable External Device Terminal block Signal name D D FG Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω Signal name RDB SDB SG FG Display Terminal block RDA SDA Shield TERM ...

Page 63: ...ce Ω Signal name NC 3 DATA 2 GND SG 5 4 ERA NC ERB 7 9 CSB 6 FG DATA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Shield External Device Terminal block Signal name D D FG Display 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω Signal name NC 3 DATA 2 GND SG 5 4 ERA NC ERB 7 9 CSB 6 FG DATA 1 CSA 8 D Sub 9 pin socket Display Pin...

Page 64: ...o Set Value 1 OFF 2 OFF 3 ON 4 ON Shield External Device Terminal block Signal name D D FG Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance 1 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance 1 Shield External Devic...

Page 65: ... block Signal name D D FG Display 120 1 4W Terminal resistance Ω 120 1 4W Terminal resistance Ω Signal name NC 1 LINE 8 GND SG 5 4 RS RTS NC NC 2 7 NC 9 FG LINE 3 5V 6 D Sub 9 pin plug Display Pin Shell Shield External Device Terminal block Signal name D D FG Display 120 1 4W Terminal resistance Ω Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω Signal name N...

Page 66: ... RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM 120 1 4W Terminal resistance Ω Signal name RDB SDB SG FG PFXZCBADTM1 Display Display Terminal block RDA SDA User created Cable Shield External Device Terminal block Signal name D D FG TERM Shield External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω ...

Page 67: ...ble 5m by Pro face PFXZLMCBRJR81 External Device Terminal block Signal name D D FG 120 1 4W Terminal resistance Ω Display D0 D1 1 External Device Terminal block Signal name D D FG Shield External Device Terminal block Signal name D D FG 220Ω 1 4W Terminal resistance 220Ω 1 4W Terminal resistance Display D0 D1 1 User created Cable ...

Page 68: ...15m or less GP 4105 COM1 7B User created Cable Cable length 15m or less LT 4 01TM COM1 LT Rear Module COM1 7C RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable length 5m or less Shield Signal name ER DTR 4 SD TXD 3 DR DSR 6 7 RS RTS SG 5 FG RD RXD 2 CS CTS 8 D Sub 9 pin socket Display Pin Shell Display D Sub 15 pin plug External Device 2 1 6 Signal name TXD RXD SG Pin 3 RTS 4 CTS Shield Signal...

Page 69: ...iver GP Pro EX Device PLC Connection Manual 69 7C Number Name Notes 1 RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 D Sub 15 pin plug External Device 2 1 6 Signal name TXD RXD SG Pin Display GND TXD RXD 1 3 RTS 4 CTS ...

Page 70: ... User created Cable Cable length 1 000m or less 8D Online adapter by Pro face CA4 ADPONL 01 User created Cable IPC 4 4 Available only with a COM port that supports RS422 485 2wire IPC COM Port page 6 8E COM port conversion adapter by Pro face CA3 ADPCOM 01 Connector terminal block conversion adapter by Pro face CA3 ADPTRM 01 User created Cable Cable length 1 000m or less 8F User created Cable GP 4...

Page 71: ...e Diagram 8A Signal name RDB SDB SG FG CA3 ADPCOM 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield TERM 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name RDB SDB SG FG CA3 ADPCOM 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield TERM Shield 120 1 4W Terminal resistance Ω D Sub ...

Page 72: ...minal resistance Ω 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Shield Signal name SDA 3 RDB 2 SG 5 4 ERA SDB ERB 7 9 CSB 6 FG RDA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Display 120 1 4W Terminal resistance Ω Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device...

Page 73: ... Cable Shield TERM 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name RDB SDB SG FG CA4 ADPONL 01 CA3 ADPTRM 01 Display Display Terminal block RDA SDA User created Cable Shield TERM Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D FG ...

Page 74: ...User created Cable 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Shield Signal name SDA 3 RDB 7 TERMTX 9 5 SG SDB 8 FG RDA 2 D Sub 9 pin plug Display Pin Shell Display TERMRX 1 CA4 ADPONL 01 User created Cable Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 1...

Page 75: ...xternal Device 5 7 10 Signal name D D FG Pin Signal name RDB SDB SG FG Display Terminal block RDA SDA Shield TERM CA3 ADPCOM 01 CA3 ADPTRM 01 Display User created Cable Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name RDB SDB SG FG Display Terminal block RDA SDA Shield T...

Page 76: ...gnal name NC 3 DATA 2 GND SG 5 4 ERA NC ERB 7 9 CSB 6 FG DATA 1 CSA 8 D Sub 9 pin socket Display Pin Shell Shield Display 120 1 4W Terminal resistance Ω Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name NC 3 DATA 2 GND SG 5 4 ERA NC ERB 7 9 CSB 6 FG DATA 1 CSA 8 D Sub 9 p...

Page 77: ...FF 3 ON 4 ON Shield Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance 1 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Shield Signal name SDA RDB SG ERA SDB ERB CSB RDA CSA Terminal Block Display Display Terminal resistance 1 Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10...

Page 78: ...4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name NC 1 LINE 8 GND SG 5 4 RS RTS NC NC 2 7 NC 9 FG LINE 3 5V 6 D Sub 9 pin plug Display Pin Shell Shield Display 120 1 4W Terminal resistance Ω Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D...

Page 79: ... Cable Shield TERM 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Signal name RDB SDB SG FG PFXZCBADTM1 Display Display Terminal block RDA SDA User created Cable Shield TERM Shield 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin ...

Page 80: ...XZLMCBRJR81 120 1 4W Terminal resistance Ω D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Display D0 D1 1 Shield 220Ω 1 4W Terminal resistance 220Ω 1 4W Terminal resistance D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin D Sub 15 pin plug External Device 5 7 10 Signal name D D FG Pin Display D0 D1 1 User created Cable ...

Page 81: ... 15m or less GP 4105 COM1 9B User created Cable Cable length 15m or less LT 4 01TM COM1 LT Rear Module COM1 9C RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable length 5m or less Shield Signal name ER DTR 4 SD TXD 3 DR DSR 6 7 RS RTS SG 5 FG RD RXD 2 CS CTS 8 D Sub 9 pin socket Display Pin Shell Display D Sub 9 pin plug External Device 2 3 5 Signal name TXD RXD SG Pin 8 RTS 7 CTS Shield Signal...

Page 82: ...SIO Driver GP Pro EX Device PLC Connection Manual 82 9C Number Name Notes 1 RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 D Sub 9 pin plug External Device 2 3 5 Signal name TXD RXD SG Pin Display GND TXD RXD 1 ...

Page 83: ...255 Counter Current Value CTR0000 CTR0199 High speed Counter HC0200 HC0255 1 1 32 bit device Data Register 2 2 The External Device handles data registers HR and R as the same device However their bit write operations differ as shown below Select either register according to your system specifications Device R allows data to be written to each specified bit Device HR sets the 15 bits other than a s...

Page 84: ...8071 and R05000 to R08071 4 Write disable 5 The file register is supported only by the FBs Series Refer to the GP Pro EX Reference Manual for system data area Cf GP Pro EX Reference Manual LS Area Direct Access Method Area Refer to the precautions on manual notation for icons in the table Manual Symbols and Terminology ...

Page 85: ...d by 16 Special Relay WSM 0086 Value of word address 1912 divided by 16 Timer Current Value TMR 0060 Word Address Counter Current Value CTR 0061 Word Address High speed Counter HC 0062 Word Address Data Register HR 0000 Word Address Data Register R 0080 Word Address Data Register D 0081 Word Address Input Register IR 0001 Value of word address 3840 Output Register OR 0002 Value of word address 390...

Page 86: ...le of the External Device set with GP Pro EX Initial value PLC1 Error Message Displays messages related to an error that has occurred Error Occurrence Area Displays the IP address or device address of the External Device where an error has occurred or error codes received from the External Device IP address is displayed as IP address Decimal MAC address Hex Device address is displayed as Address D...

Reviews: