-21-
Setting Output Range
Chapter 6.
To set voltage range, use either SDO communication or DIP switch setting method. The setting methods are
following.
6.1
Setting Voltage Output Range
Setting Voltage Output Range through SDO Communication
6.1.1
(Example) Setting Channel 2
①
Set LSET switch (SW3.1) of Output Range Setting Switch (SW3) to OFF before supplying power.
②
On the Output Connector (CN2), wire GND pin (G) and voltage output pin (V2) of Channel 2 to the
analogue device. Then, supply power to the module.
③
Enter the value of the Analogue Output Range Object (2301h) through the Master unit to set the voltage
output range.
④
Supply power to the module again, and complete the setting.
Figure 6-1. Setting Voltage Output Range through SDO Communication
Setting Voltage Output Range with DIP Switches
6.1.2
(Example) Setting Channel 2
to -10~10V Output Range
①
Set LSET switch (SW3.1) of Output Range Setting Switch (SW3) to ON before supplying power to the
module. Set the voltage output range of Channel 2 with SW3.5~SW3.6 switches (SW3.5=OFF, SW3.6=ON).
②
On the Output Connector (CN2), wire GND pin (G) and voltage output pin (V2) of Channel 2 to the
analogue device. Then, supply power to the module.
Figure 6-2. Setting Voltage Output Range with DIP Switches