www.fas
-
elec.com
IOLink PD
active
0=disabled
1=enable
Port7 Port6 Port5
Port4
Port3
Port2
Port1
Port0
module status
-
-
-
Us overvoltage Ua overvoltage overheat Us undervoltage
Ua
undervoltage
(The rest of the points are reserved)
RWR
(
maximum
256Byte
)
Port 0 process input data(32Byte)
Port 1 process input data(32Byte)
Port 2 process input data(32Byte)
Port 3 process input data(32Byte)
Port 4 process input data(32Byte)
Port 5 process input data(32Byte)
Port 6 process input data(32Byte)
Port 7 process input data(32Byte)
Note:
1. Please set the CCIEBS master port function in the FAS IOLink Tool software.
2. The number of points 64 occupies 1 station, and the number of points used by the slave
station connected to each port is 4 words
3. The number of points 128 occupies 2 stations, and the number of points used by the slave
station connected to each port is 8 words
4. The number of points 192 occupies 3 stations, and the number of points used by the slave
station connected to each port is 12 words
5. The number of points 256 occupies 4 stations, and the number of points used by the slave
station connected to each port is 16 words
6. Refer to chapter 5.1.3 for the setting of points. The CCIEBS master station occupies 4 stations
by default.
5.3 PLC Integration Tutorial
(The module communication protocol should be set before configuring the module, see 5.
1.1 for details)
5.3.1 Siemens S7
-
1200 Portal Integration (PN)
1. Install the GSD file