Farpointe Data Delta3 Quick Reference Manual Download Page 2

Delta Multi-Technology Readers: Quick Reference Guide 

                                                               2177 Leghorn Street                                              01609-001 Rev 1.0
                                                               Mountain View, CA  94043-1605     USA                                      2 of 2 
                                                               Tel: +1-650-964-2615     Fax: +1-650-988-6687  
                                                               Web: 

http://www.farpointedata.com

    E-mail: [email protected] 

 

7.0

 

Grounding 

Shield (drain) continuity must run from the reader to the access panel.  Shield (drain) and reader ground must be tied 
together at the access panel and connect to an earth ground at one point. 

 
8.0

 

Power and Voltage 

Delta multi-technology readers may be powered by the access panel, so the reader is powered on when the access 
supply is powered on.  However the best case is to power the readers by a separate, linear power supply. Voltage can 
range from 5 to 14 VDC, 12 VDC is nominal. 

 

9.0

 

Reader Wiring 

 

 

10.0

 

Connections in Detail 

Wire Color 

Line 

I/O 

Description 

Red 

Reader input voltage 

Input 

5 to 14 VDC 

Green 

Wiegand data 0/ 
Magstripe Clock 

Output  

Wiegand data or ABA Track II clock 

White 

Wiegand data 1/ 
Magstripe Data 

Output  

Wiegand data or ABA Track II data 

Brown 

Red LED host control 

Input 

LED host control.  In single line LED control 
mode (default mode) pull line low to turn on green 
LED. In dual line LED mode pull line low to turn 
on Red LED 

Orange 

Green LED host 
control 

Input 

LED host control, only used in dual LED mode.  
In dual LED mode pull line low to turn on green 
LED. 

Blue 

Audio tone host 
control 

Input Beeper 

host 

control. 

 Pull line low for beep. 

Purple 

Read mode control 

Input 

Read mode host control.  Pull line low for “Sector 
Only” mode. 

Yellow 

Card Present 

Output (can be 
configured as TTL or 
open collector) 

Card present line for ABA Track II magnetic 
stripe output. 

Black 

Reader Ground 

Input 

Reader Ground 

Silver 

Cable shield 

N/A 

Cable shield (drain), must be grounded 

 

Wire Color

Function

Green

Blue

Red

Purple

Brown

Shield (Drain)

White

Yellow

Black

Silver

Data 0

Beeper

Reader Power

Read Mode

LED line 1

LED line 2

Data 1

Card Present

Reader Ground

Orange

Figure 1: Wiring Connections to Access Panel 

Access 
Panel 

     Reference Documen

t

  Delta Multi-

Technology

Reader

s

Reviews: