background image

Directive 2014/30/EU (Electromagnetic Compatibility (EMC))

Directive 2012/19/EU (WEEE)

Directive 2011/65/EU (RoHS)

Harmonised standards: EN 61000-6-1  Immunity for residential, commercial and light-industrial environments 

& EN 61000-6-3 Emission standard for residential, commercial and light-industrial environments

INSTALLATION

To install the Faradite Motion 

Sensor 360, cut a 35mm hole using 

a suitable hole saw. Fold the spring 

clips upwards and push through the 

hole. If you are using the optional 

Fire IDR to achieve a 60 minute fire 

rating to BS 476: Part 21 1987, then a 

40mm hole will be required.

USE A 35mm 

HOLE SAW FOR 

INSTALLATION

For further support please visit: faradite.com

CONNECTION TO LOXONE MINISERVER

Connection to Loxone is simple: connect the motion output to a digital 

input and the lux sensor output to an analogue input. There is no need 

to invert the input as the motion sensor is logic high for motion - see 

motion output diagram.

Simply connect directly using a CAT cable; no pull-up resistors required

CONNECTION TO LOXONE NANO DI TREE

LOXONE CONFIG ADJUSTMENT OF ANALOG INPUT

The analog input needs to be mapped correctly so 10V is interpreted as 

1000 Lux. 

To do this:

 click on the correct analog input, which will bring 

up the properties on the left hand side of the Loxone config. Find the 

correction section and change the “Display Value 2” to 1000 (instead of 10). 

If you are installing Faradite TAP-5 / TAP-1 switches as well, the 

recommended option is to connect the Motion Sensor 360 to the 6th 

Digital input of the Nano DI Tree module. 

Please note that Loxone Nano 

DI Tree module does not have an analog  input for the Lux sensor

0V / GND

LUX 0V - 10V 

12V-24V

MOTION

GND

ANALOGUE INPUT 

24V

DIGITAL INPUT

FARADITE MOTION 

SENSOR 360

LOXONE

0V /GND

12V-24V DC

MOTION

GND (WHITE WAGO)

6th INPUT (BLACK WIRE) 

24V (ORANGE WAGO)

FARADITE MOTION 

SENSOR 360

NANO DI TREE

MOUNTING & SAFETY 

PRECAUTIONS

1) Do not under any circumstance 

use these sensors outside the range 

of their ratings shown in the technical 

data.

2) Faradite is committed to making 

products of the highest quality and 

reliability. Nevertheless, all electrical 

components are subject to natural 

deterioration, and the product 

durability will depend on the 

operating environment and 

conditions of use.

3) Please note that the sensor can 

detect heat sources other than the 

human body, such as:

a) Small animals 

b) Direct sun light, incandescent 

lamps, car headlights (even if the heat 

source is outside the detection area)

c) Sudden temperature change inside 

or around the detection area i.e. hot 

or cold winds/drafts or vapour from 

the humidifier can effect the 

performance of the sensor.

4) Please note that the sensor will 

have difficulty sensing the heat 

source if it is behind glass, acrylic or 

similar materials as these materials 

may not allow a correct transmission 

of infrared rays.

CONNECTION TO CONTROL4

Connection to Control4 is simple, the motion sensor output can be 

connected to a contact closure on a Control4 I/O module. The 0-10V LUX 

sensor can be used with Control4 using a driver from Janus Technology.

The driver allows for connection of the 0-10V and digital input via devices 

from Brainboxes Ltd. Search online for Faradite Janus Technology for 

more info.

0V /GND

12V-24V DC

LUX 0V-10V

GND
12V

FARADITE MOTION 

SENSOR 360

CONTROL4

MOTION

Brainboxes ED588 - Digital Input 

OR Control4 - Contact Closure

SENSITIVITY ADJUSTMENT

The sensor has been designed for optimal sensitivity. 

It is not recommended to change the sensitivity 

setting unless it is found to be necessary. To adjust 

the sensitivity, remove the two screws and turn over 

the circuit board. The small potentiometer can be 

used to adjust the sensitivity.

0-10V - Brainboxes ED549  

Reviews: